MINiBOX 0-10V X3/X2/X1
Technical Support:
18
ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, regardless of any other values permitted by the bus, given the object size, may be of useful or have a particular meaning
because of the specifications or restrictions from the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
2
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Device Recovery
Send 0
3
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Device Recovery
Send 1
4
1 Bit
I/O
C R W - -
DPT_Enable
0/1
Manual Control Lock
0 = Unlock; 1 = Lock
1 Bit
I/O
C R W - -
DPT_Enable
0/1
Manual Control Lock
0 = Lock; 1 = Unlock
5, 12, 19
1 Byte
O
C R - T -
DPT_Value_1_Ucount
0 - 255
[AIx] Measured Value
(1-Byte) Unsigned
1 Byte
O
C R - T -
DPT_Value_1_Count
-128 - 127
[AIx] Measured Value
(1-Byte) Signed
2 Bytes
O
C R - T -
DPT_Value_2_Ucount
0 - 65535
[AIx] Measured Value
(2-Byte) Unsigned
2 Bytes
O
C R - T -
DPT_Value_2_Count
-32768 - 32767
[AIx] Measured Value
(2-Byte) Signed
2 Bytes
O
C R - T -
9.xxx
-671088.64 - 670433.28
[AIx] Measured Value
(2-Byte) Float
4 Bytes
O
C R - T -
14.xxx
[AIx] Measured Value
(4-Byte) Float
1 Byte
O
C R - T -
DPT_Scaling
0% - 100%
[AIx] Measured Value
(1-Byte) Percentage
6, 13, 20
1 Bit
O
C R - T -
DPT_Alarm
0/1
[AIx] Lower Range Error
0 = No Alarm; 1 = Alarm
7, 14, 21
1 Bit
O
C R - T -
DPT_Alarm
0/1
[AIx] Upper Range Error
0 = No Alarm; 1 = Alarm
8, 15, 22
1 Bit
O
C R - T -
DPT_Alarm
0/1
[AIx] Lower Threshold
0 = No Alarm; 1 = Alarm
9, 16, 23
1 Byte
I
C - W - -
DPT_Value_1_Ucount
0 - 255
[AIx] Lower Threshold Value
(1-Byte) Unsigned
1 Byte
I
C - W - -
DPT_Value_1_Count
-128 - 127
[AIx] Lower Threshold Value
(1-Byte) Signed
2 Bytes
I
C - W - -
DPT_Value_2_Ucount
0 - 65535
[AIx] Lower Threshold Value
(2-Byte) Unsigned
2 Bytes
I
C - W - -
DPT_Value_2_Count
-32768 - 32767
[AIx] Lower Threshold Value
(2-Byte) Signed
2 Bytes
I
C - W - -
9.xxx
-671088.64 - 670433.28
[AIx] Lower Threshold Value
(2-Byte) Float
4 Bytes
I
C - W - -
14.xxx
[AIx] Lower Threshold Value
(4-Byte) Float
1 Byte
I
C - W - -
DPT_Scaling
0% - 100%
[AIx] Lower Threshold Value
(1-Byte) Percentage
10, 17, 24
1 Bit
O
C R - T -
DPT_Alarm
0/1
[AIx] Upper Threshold
0 = No Alarm; 1 = Alarm
11, 18, 25
1 Byte
I
C - W - -
DPT_Value_1_Ucount
0 - 255
[AIx] Upper Threshold Value
(1-Byte) Unsigned
1 Byte
I
C - W - -
DPT_Value_1_Count
-128 - 127
[AIx] Upper Threshold Value
(1-Byte) Signed