2.7

 

MANUAL CONTROL 

The MINiBOX 0-10V devices, include manual control of its outputs through the respective 

pushbuttons on the top of the device. Therefore, a specific pushbutton is available per 

output. 

Manual operation can be done in two different ways, named as 

Test On Mode 

(for testing 

purposes during the configuration of the device) and 

Test Off Mode 

(for a normal use, 

anytime). Whether both, only one, or none of these modes can be accessed needs to be 

parameterised  in  ETS.  Moreover,  it  is  possible  to  enable  a  specific  binary  object  for 

locking and unlocking the manual control in runtime.  

Notes

:  

 

The Test Off mode will be active (unless it has been disabled by parameter) 

after  a  download  or  a  reset  with  no  need  of  a  specific  activation 

–  the 

pushbuttons will respond to user presses from the beginning.  

 

On  the  contrary,  switching  to  the  Test  On  mode  (unless  disabled  by 

parameter)  needs  to  be  done  by  long-pressing  the  Prog./Test  button  (for  at 

least three seconds), until the LED is no longer red and turns yellow. From that 

moment, once the button is released, the LED light will remain green to confirm 

that the device has switched from the Test Off mode to the Test On mode. After 

that, an additional press will turn the LED yellow and then off, once the button 

is released. This way, the device leaves the Test On mode. Note that the device 

will also leave this mode if a bus power failure takes place or if a manual control 

lock is sending from KNX bus

Test Off Mode 

Under the Test Off Mode, the outputs can be controlled through both their communication 

objects and the actual pushbuttons located on the top of the device.  

When one of these buttons is pressed, the output will behave as if an order had been 

received through the corresponding communication object. 

 

Individual  voltage  output

:  only  the  analog  outputs  configured  as  "

generic 

outputs

" can be controlled manually. 

Summary of Contents for MINiBOX 0-10V X3

Page 1: ...MINiBOX 0 10V X3 X2 X1 Multifunction Actuator with 3 2 1 fold 0 10V analog input output ZIO3X010 ZIO2X010 ZIO1X010 USER MANUAL Application program version 1 2 User manual edition 1 2 _a www zennio com...

Page 2: ...s 3 1 Introduction 4 1 1 MINiBOX 0 10V X3 X2 X1 4 1 2 Installation 5 1 3 Start Up and Power Loss 6 2 Configuration 7 2 1 General 7 2 2 Analog Input 9 2 3 Analog Voltage Output 10 2 3 1 Operating Time...

Page 3: ...al Support https support zennio com 3 DOCUMENT UPDATES Version Changes Page s 1 2 _a New devices MINiBOX 0 10V X2 y MINiBOX 0 10V X1 Changes in the software library Analog inputs module is added Optim...

Page 4: ...MINiBOX 0 10V X1 1 channel and all their characteristics will be mentioned respectively and following this order along the entire document 3 2 1 fan coil analog modules to control 2 and 4 pipes units...

Page 5: ...e into the programming mode making the associated LED 5 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode In such case the LED wi...

Page 6: ...ticular state and whether the device should send certain objects to the bus after the power recovery Please consult the next sections of this document for further details On the other hand when a bus...

Page 7: ...ssible to activate deactivate all the required functionality The following image corresponds to the MINiBOX 0 10V X3 The reduced versions only show the number of channels corresponding to each device...

Page 8: ...tification Note The first sending after download or bus failure takes place with a delay of up to 255 seconds to prevent bus overload The following sendings match the period set Device Recovery Object...

Page 9: ...puts which can be used to connect different sensors with different voltage 0 10V 0 1V y 1 10V or current 0 20mA y 4 20mA measurement ranges Please refer to the specific user manual Analog Inputs avail...

Page 10: ...tionality and the configuration of the related parameters 2 3 1 OPERATING TIME COUNTER When an analog output is enabled it is possible to configure the operating time counter a function that offers th...

Page 11: ...ounter record in hours of the time that the output remains switched on off The maximum value is 65535 when the maximum limit is reached this value is maintained Counting Mode Output Off Output On sets...

Page 12: ...s incorporate three two one modules to control the fan and valves of a 2 or 4 pipes fan coil unit Please refer to the specific user manual Fan Coil Analog available in the MINiBOX 0 10V product sectio...

Page 13: ...ncorporate three two one Zennio thermostats that can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the MINiBOX 0 10V product sections...

Page 14: ...The execution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result af...

Page 15: ...the beginning On the contrary switching to the Test On mode unless disabled by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer re...

Page 16: ...ontrol the outputs through the on board pushbuttons Orders received through communication objects will be ignored regardless of the channel or the output they are addressed to Individual output the ac...

Page 17: ...while switching to Test On mode does require long pressing the Prog Test button Lock Manual Control disabled enabled unless the above parameter has been Disabled the Lock Manual Control parameter prov...

Page 18: ...8 32767 AIx Measured Value 2 Byte Signed 2 Bytes O C R T 9 xxx 671088 64 670433 28 AIx Measured Value 2 Byte Float 4 Bytes O C R T 14 xxx AIx Measured Value 4 Byte Float 1 Byte O C R T DPT_Scaling 0 1...

Page 19: ...7 62 1 Bit I C W DPT_DayNight 0 1 AOx Day Night Mode 0 Day Mode 1 Night Mode 1 Bit I C W DPT_DayNight 0 1 AOx Day Night Mode 0 Night Mode 1 Day Mode 33 48 63 1 Bit I C W DPT_Switch 0 1 AOx Day Night M...

Page 20: ...Protection Status 0 Not Active 1 Active 1 Bit O C R T DPT_Switch 0 1 FCx Valve Anti Seize Protection Status 0 Not Active 1 Active 81 114 147 1 Bit I C W T U DPT_Switch 0 1 FCx Heating Valve Control V...

Page 21: ...FCx Manual Fan Enumeration Control S0 0 S1 25 S2 50 S3 75 S4 100 1 Byte I C W T U DPT_Fan_Stage 0 255 FCx Manual Fan Enumeration Control S0 0 S1 100 99 132 165 1 Byte I C W T U DPT_Scaling 0 100 FCx M...

Page 22: ...oor 0 1 Tx Window Status Input 0 Closed 1 Open 180 218 256 1 Bit I C W DPT_Trigger 0 1 Tx Comfort Prolongation 0 Nothing 1 Timed Comfort 181 219 257 1 Byte O C R T DPT_HVACMode 1 Comfort 2 Standby 3 E...

Page 23: ...ntrol 1 Bit O C R T DPT_Switch 0 1 Tx Sx Control Variable PI Control PWM 201 207 239 245 277 283 1 Bit O C R T DPT_Switch 0 1 Tx Sx PI State Cool 0 PI Signal 0 1 PI Signal Greater than 0 202 208 240 2...

Page 24: ...0 100 LF Function x Result 1 Byte Percentage 2 Bytes O C R T DPT_Value_2_Count 32768 32767 LF Function x Result 2 Byte Signed 2 Bytes O C R T 9 xxx 671088 64 670433 28 LF Function x Result 2 Byte Flo...

Page 25: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...

Reviews: