The following objects to control and supervise setpoint temperature will be available by
default:
•
“[AC] Temperature Setpoint”:
2-Byte object that allow selecting decimal
temperature values that belong to the range [10ºC - 32ºC].
•
“[AC] Temperature Setpoint (Status)”
: 2-Byte object that provides the
Temperature setpoint status.
Note
:
A X.Y value will be rounded to X.0 if [Y < 5] o
r to X.5 if [Y ≥ 5].
Status object will be updated to the last setpoint temperature value received by the A/C
unit after a complete communication cycle and will be sent to KNX bus every time that
its value changes.
Setpoint limits can be configured by parameter:
•
Setpoint Limits
[
disabled
/enabled
]: allows restricting the range of the
temperature setpoint (from below in the Cooling, Dry and Auto modes and from
above in the Heating and Auto modes), provided that the limits are still within
the predefined limits of the A/C unit. When KLIC-PA receives an order to send
the A/C unit a setpoint, which is greater (or lower) than the configured limits, it
will actually send the limit value.
➢
Minimum (Cooling/Auto/Dry Mode)
[
10…
18
…32
][
ºC
]: sets the upper limit.
➢
Maximum (Heating/Auto Mode)
[
10…
30
…32
][
ºC
]: sets the lower limit.
Once these limits are enabled, several objects to modify them at run time will be
available. The values of this objects will be restricted to an interval which is defined by
the absolute limits established by the A/C unit (10ºC to 32ºC).
•
“[AC] Temperature Setpoint: Lower Limit”
: 2-Byte object that allows
changing the lower limit at run time.
•
“[AC] Temperature Setpoint: Lower Limit (Status)”
: 2-Byte object with the
lower limit current value.
•
“[AC] Temperature Setpoint: Upper Limit”
: 2-Byte object that allows
changing the upper limit at run time.