The Fan Speeds function allows sending the A/C unit orders to switch the ventilation
speed along the available levels. To that end, KLIC-PA provides a
percentage
control.
In addition, KLIC-PA allows activating the
automatic fan speed mode
, in case of being
available in the unit.
The number of fan speeds of KLIC-PA will be always three levels. This determines the
values of the "
[AC]
Speed: Percentage Control
”
and "
[AC]
Speed: Percentage
Control (Status)
" 1-Byte objects, which allow setting and reading the fan speed,
respectively. The following table show the percentage values that correspond to the three
levels:
Control Values
Status Value
Level Sent to the Unit
1-33%
33%
1 (minimum)
34-66%
66%
2
67-100%
100%
3 (maximum)
Table 4. Fan speed.
The value 0% of the above objects will be reserved for activating the automatic speed
function or reporting whether it is currently active.
•
Individual Object for Automatic Speed
[
disabled
/enabled
]: 1-Bit objects
“[AC] Speed: Automatic”
and
“[AC] Speed: Automatic (Status)”
activate
automatic speed and informs the currently state, respectively.
Moreover, the
polarity of this parameter can be selected:
➢
Automatic Speed Object Polarity
[
0 = Automatic On; 1 = Automatic Off /
0 = Automatic Off; 1 = Automatic On
]: sets the polarity of the above objects.
TEMPERATURE SETPOINT