Zenitel Vingtor Stentofon SPA-AC6 Configuration & Installation Manual Download Page 48

48

A100K10370 

SPA-V2 Public Address & General Alarm System

Installation & Configuration Manual

3.6 

Startup Procedure

Power switching is provided by external power equipment.

The following procedure has to be completed before the system can be 

used.
Carry out the start-up and test procedure for all functions and equipment 

in the installation.

Step Requirements

1

Inspection of the following according to section 2.1 - 2.5 :

 

-

Mechanical

 

-

Cable

 

-

Power

 

-

Function configurations

2

System operates on 230V AC main and 24V DC emergency

 

-

Switch on the 230V main power supply and check that we have 24V DC on terminal X1 on the main terminal board.

 

-

Switch on the 24V DC emergency and check that we have 24V DC on terminals X2 on the main terminal board.

Power failure output - SPA-FAIL

 

-

Switch off the 230V AC main and check that the power failure output is activated when the system operates on 24V DC 

Emergency

3

System operates on 230V AC main and 230V AC Emergency/UPS

 

-

Switch on the 230V main power supply and check that we have 24V DC on terminal X1 on the main terminal board.

 

-

Switch off the 230V AC mains and check that the power failure output is activated when the system operates on 230V AC 

Emergency/UPS.

4

Switch ON amplifier - Type VPA

 

-

Switch marked “ON/OFF” and light marked “POWER”

 

-

If the LED marked “OVERLOAD” turns red

 

L

If other adjustments or settings are required, the 

amplifiers must be taken out of the cabinet for ac

-

cess to the controls at rear side. 

The factory settings are:

 

-

MASTER VOLUME to approximately 80%

 

-

BASS and TREBLE to “0” position

 

-

BMG to “0” position

 

-

Chime OFF Chime volume “0”

Switch ON amplifier - Type EA1400/EA1600

 

-

Check that the Power LED is lit

 

-

Fault and Line Error LEDs may blink shortly at the start but it 

should not be lit continuously

 

-

None of the VU meter LEDs should be lit

All system and functional equipment in a standard SPA system is now powered up and 

ready for use.

5

Input from 3x Mic Input – X8, X9 and X10 main terminal board

 

-

Zone 1 to 6 and “ALL CALL”

 

-

Priority between the microphone panels

 

-

EMS – Emergency PA messages

 

-

EMS can only be activated from the Alarm panels SPA-AC6 and SPA-W6A4

 

-

Audio from PA panels is 0db (0.7 VAC) signal and can be decreased by operating the potentiometer P2, P3 and P4 on the main 

terminal board.

 

-

Bass and discant tone can be changed by operating the potentiometer on the main PA panel

Do this test for all PA panels.

6

Input from PABX X11 main terminal board

 

-

Input from PABX has to be 0db signal and one potential-free contact.

 

-

Zone selections from PABX give standard “ALL CALL”.

 

-

Can be changed by setting Zone jumpers to required zones. When used with SMIII-PA, an analog trunk line will apply.

7

Mute of external alarm when PA massages is active.

 

-

Potential-free output signal N, NC, NO on terminals X5 on main terminal board. 

8

SPA-EE3-V2 alarm generator (first)

 

-

Start alarms from Alarm panels – X16/17

 

-

GA

 

-

Abandon

 

-

Manual/Fire

 

-

Reset Alarms

 

-

Start Fire All and Crew/Engine – X16/17

 

-

All zones

 

-

Select zones by setting jumpers J5, J6, J7, J8, J26, J27 to required zones

 

-

Select required PROM setup according to section 2.11 by operating the PROM selector on the EE3 board

 

-

Test that PA mutes alarms

Summary of Contents for Vingtor Stentofon SPA-AC6

Page 1: ...icrophone Alarm panel Alarm panel Entertainment LS zone 5 LS zone 6 Engine area Open deck GENERAL ABANDON MANUAL RESET EMS SPARE SPA A6CD 1 2 3 4 5 6 ALL SPA M6D TALK DIM Open deck ACM Integrated Syst...

Page 2: ...ng SPA M1 V2 SPA AC6 15 2 7 4 Connecting SPA M1 D SPA AC6 D 16 2 7 5 Connecting SPA M6 SPA AC6 17 2 7 6 Connecting SPA M6 D SPA AC6 D 18 2 7 7 Connecting SPA W1 V2 19 2 7 8 Connecting SPA W1 D 19 2 7...

Page 3: ...3 Commissioning 47 3 1 General 47 3 2 Mechanical Inspection 47 3 3 Cable Connection Inspection 47 3 4 Power Supply Consumption Check 47 3 5 Function Configuration Check 47 3 6 Startup Procedure 48 4...

Page 4: ...ings in AutoCAD Amplifier and Entertainment manuals 1 4 Rules and Regulations The SPA V2 Public Address and General Alarm System is designed to meet the requirements in accordance with SOLAS Section I...

Page 5: ...he carton carefully remove the contents and check for any signs of mechanical damage The SPA delivery package can depending on the order contain the following equipment see attached packing list Rack...

Page 6: ...comply with SOLAS Ch II 1 45 5 2 The PA system has been fully tested and fulfills all requirements according to EN 60945 and IACS E10 standard Cables for service required to be operable under fire con...

Page 7: ...MASTER VOLUME POWER 10 10 0 10 10 10 0 0 5 OUTPUT LEVEL OVERL ON dB 40 12 6 0 1 SERIES POWER AMPLIFIER I 0 BASS TREBLE MASTER VOLUME POWER 10 10 0 10 10 10 0 0 5 OUTPUT LEVEL OVERL ON dB 40 12 6 0 1...

Page 8: ...here are four 12 mm fastening holes for mounting the rack to the floor as standard There are air ventilation slots on both sides and rear of all units Free space on both sides should be minimum 300 mm...

Page 9: ...n Configuration Manual A100K10370 2 6 2 Microphone Panels Indoors SPA M1 V2 SPA M1 D SPA M6 V2 SPA M6 D L SPA M1 V2 version are equipped with 2x cable gland PG 16 2 6 3 SPA M6BOKS For SPA M1 and SPA M...

Page 10: ...A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 6 5 ACBOKS For SPA AC6 and SPA AC6 D when wall mounted 2 6 6 SPA W1 V2 SPA W1 D Weatherproof PA Panels 96 66...

Page 11: ...A V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 6 7 SPA W1AR V2 SPA W1AR D Weatherproof PA and alarm panel 2 6 8 SPA W6A4 SPA W6A4 D Weatherproof PA and alarm p...

Page 12: ...tion Configuration Manual 2 6 9 SPA REM7 Remote panel for message recorder 2 6 10 SPA BOXM1 For VM15 R and VM50 R when wall mounted 2 6 11 VM15 RD VM50 RD VM15 RDF VM50 RDF Volume Controls 5 96 17 5 8...

Page 13: ...d the SPA rack Typical system configurations are shown at the end of this section All drawings are also available in AutoCAD 2 7 1 Connecting Power Supply 1 230V AC main and 24V DC emergency Figure 4...

Page 14: ...m System Installation Configuration Manual 2 7 2 Connecting Power Supply 2 230V AC main and 230 V AC emergency with failure unit SPA FAIL Figure 5 230 230 VAC with SPA FAIL board SHIP S EMERGENCY 230V...

Page 15: ...15 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 3 Connecting SPA M1 V2 SPA AC6...

Page 16: ...16 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 4 Connecting SPA M1 D SPA AC6 D...

Page 17: ...17 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 5 Connecting SPA M6 SPA AC6...

Page 18: ...18 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 6 Connecting SPA M6 D SPA AC6 D...

Page 19: ...19 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 7 Connecting SPA W1 V2 2 7 8 Connecting SPA W1 D...

Page 20: ...20 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 9 Connecting SPA W1AR V2...

Page 21: ...21 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 10 Connecting SPA W1AR D...

Page 22: ...22 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 11 Connecting SPA W6A4...

Page 23: ...23 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 12 Connecting SPA W6A4 D...

Page 24: ...24 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 13 Connecting Loudspeaker in Single System...

Page 25: ...F X14 11 12 10 9 8 6 7 5 3 4 2 1 ZONE 1 F 100V LINE OUT X14 ZONE 2 0 ZONE 3 F ZONE 3 0 ZONE 4 F ZONE 4 0 ZONE 5 F ZONE 5 0 ZONE 6 F ZONE 6 0 3 4 2 1 24V 3 4 2 1 24V 24V 24V X61 SPA ENT4 V2 1 2 6 5 4...

Page 26: ...26 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 15 Connecting Loudspeaker Volume Controls in A B System in Two Racks...

Page 27: ...2 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 2 1 1 2 3 4 5 6 1 2 3 1 2 3 1 2 3 1 2 3 4 5 NO NC N F F O F F O F F O A30 1 2 3 4 5 6 7 8 9 10 11 1...

Page 28: ...28 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 18 Configuration Example 1 Microphone panels PABX...

Page 29: ...29 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 19 Configuration Example 2 Microphone Alarm Panels PABX...

Page 30: ...30 A100K10370 SPA V2 Public Address General Alarm System Installation Configuration Manual 2 7 20 Configuration Example 3 Dual PA GA...

Page 31: ...31 SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 2 7 21 Configuration Example 4 Required PA GA Connection between Racks 1 2...

Page 32: ...2 and PRIO 3 in upper N position and PRIO 4 in lower position X4 X5 X6 X7 X8 X11 X15 X14 X13 X2 X1 EXTERN AMPLIFIER PA MUTE POTFREE OUTPUT ENTERT OUTPUT AUDIO OUT TO AMPLIFIER ALARM INPUT 1 PABX INPU...

Page 33: ...igure 10 Jumpers for fire crew alarm per zone Zone selection for PABX Default setting PABX audio to all zones right position If PABX audio shall be distributed to different zones the jumper must be se...

Page 34: ...ntertainment board 990 363 or J37 on the SPA multi 4 way entertainment 6 zones board have to be set to Normal and Emergency or Emergency Only This setting will override volume control The default sett...

Page 35: ...N Disconnect ENT zone s by DIPSWITCH to position ENT Select the PA zone s 1 6A by DIPSWITCH to position ON Disconnect ENT zone s by DIPSWITCH to position PA Entertainment Public address output selecti...

Page 36: ...rminal block X10 2 9 3 Signal Adjustment PABX Input Trim potentiometer marked P5 PABX VOL for audio input from Automatic Telephone System on terminal block X11 1 2 2 9 4 Signal Adjustment Entertainmen...

Page 37: ...the number of loudspeakers and do the power tappings in accordance with available output power for the zone Make sure to NOT exceed the total amplifier output capacity Power tapping options can be fo...

Page 38: ...of frequency must be undertaken by Zenitel personnel at customer site or the ship yard The procedure for changing the frequency is Change the value of the register OCR2 of the micro controller on one...

Page 39: ...ched SPA AL REL6 V2 Steady Button 4 N A N A constantly Button 5 Press and hold Release Latched N A N A The MANUAL button is also used to manually generate alarm tone patterns 2 11 5 Alarm 2 L Refer to...

Page 40: ...SPA AL REL6 V2 Steady constantly Button 4 Press and hold Release MOB Latched N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 7 Alarm 4 L Refer to the SPA AL REL V2 and SPA REL...

Page 41: ...Latched SPA AL REL6 V2 Steady constantly Button 4 Press and hold Release MOB Latched N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 9 Alarm 6 L Refer to the SPA AL REL V2 and...

Page 42: ...anual Release Manual Latched SPA AL REL6 V2 Steady Button 4 Press Release Toggle N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 11 Alarm 8 L Refer to the SPA AL REL V2 and SPA...

Page 43: ...hed SPA AL REL6 V2 Steady Button 4 Press Release Toggle N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 13 Alarm 10 L Refer to the SPA AL REL V2 and SPA REL V2 figures in secti...

Page 44: ...l Release Manual Latched SPA AL REL6 V2 Steady Button 4 Press Release Toggle N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 15 Alarm 12 L Refer to the SPA AL REL V2 and SPA RE...

Page 45: ...AL REL6 V2 Steady Button 4 Press and hold MOB Release Latched N A N A constantly Button 5 Press and hold Release Latched N A N A 2 11 17 Alarm 14 L Refer to the SPA AL REL V2 and SPA REL V2 figures in...

Page 46: ...g 800 810Hz Woobling 3 Manual Continuous 800Hz Continuous 4 MOB 1 x long 1 short 800Hz 1s Short 3s Long 5 Abandon LED Manual LED MOB LED SPA AC6 Activation button Termination button Activation type Co...

Page 47: ...re signal cables 0 75 mm2 approved ship cable of type twisted pair with outer braided copper shield Check that the shields are interconnected in junction boxes if used and grounded in ground terminals...

Page 48: ...ttings are MASTER VOLUME to approximately 80 BASS and TREBLE to 0 position BMG to 0 position Chime OFF Chime volume 0 Switch ON amplifier Type EA1400 EA1600 Check that the Power LED is lit Fault and L...

Page 49: ...low instructions in the SPA V2 User Manual section 2 10 L If other signal levels are required after installation adjust the signal by using trimming potentiometer marked P1 CTB ETB VOL for audio from...

Page 50: ...output that is connected to the coil of the relay This triggers when only this panel is activated giving an active 24VDC out which breaks the audio going to the local speaker s Local mute outputs are...

Page 51: ...SPA V2 Public Address General Alarm System Installation Configuration Manual A100K10370 5 Appendix B Custom Alarm Configuration Example The configuration example shown below is for a standard 4002 Ala...

Page 52: ...alarm time s 805 frequency Hz 0 800 Start alarm time s GENERAL ALARM ABANDON 500 1K 1 5K frequency Hz 0 800 Start alarm time s MANUAL FIRE Stop alarm LATCHED START PULSE START PULSE STOP Start alarm...

Page 53: ...alarm time s Stop alarm 1s 1s 1s 1s repeating sequence ABANDON GERMAN FLAG MUSTER ABANDON NORSOK PFEER 500 1K 1 5K frequency Hz 1 2K repeat sequence 1s 1s 1s 1s 1s 1s 1s 1s 1s 500 1K 1 5K frequency Hz...

Page 54: ...writing with Zenitel Any authorized reproduction in part or in whole must include this legend Zenitel All rights reserved The WEEE Directive does not legislate that Zenitel as a producer shall collec...

Reviews: