![Zenitel Vingtor Stentofon SPA-AC6 Configuration & Installation Manual Download Page 46](http://html1.mh-extra.com/html/zenitel/vingtor-stentofon-spa-ac6/vingtor-stentofon-spa-ac6_configuration-and-installation-manual_929037046.webp)
46
A100K10370
SPA-V2 Public Address & General Alarm System
Installation & Configuration Manual
2.11.18 Alarm 15
Priority
Alarm Type
Audio Sequence
Frequency "Timing Sequence
(sec)"
General LED Steady LED
Pulsing w. Mute
LED
Pulsing w. Mute
LED
1
General
7 short 1/2 long
800Hz
1s Short, 6s Long
Constantly
Constantly
Blinks
Blinks
2
Abandon
Woobling
800/810Hz
Woobling
3
Manual
Continuous
800Hz
Continuous
4
MOB
1 x long, 1 short
800Hz
1s Short, 3s Long
5
Abandon LED Manual LED
MOB LED SPA-AC6 Activation button Termination
button
Activation
type
Contact Output
NO
NC
Failsafe
SPA-AL-REL-V2 or
SPA-AL-REL6-V2
Pulsing & Steady
Constantly
NO
NC
Failsafe
SPA-AL-REL6-V2
Steady
Constantly
NO
NC
Failsafe
SPA-AL-REL6-V2
Steady
NO
NC
Failsafe
N/A
N/A
N/A
N/A
2.11.19 FIRE Alarm
Activate the jumpers / DIP switches J5 ... J8, and J26 and J28.
Press and hold the FIRE button down and the alarm will start.