3
PRODUCT
Specification
A48-40-01/A48-40-02
Nominal Capacity (25°C ± 5°C)
1.93KWh (40Ah)
Chemistry
Lithium Titanate (LTO)
Dimensions (Height x Width x Depth)
1600 x 155 x 145 mm / 1635 x 155 x 145 mm
Nominal Voltage
48.3V
Charge Cut-off Voltage (Bulk/Absorption
Voltage)
55.5V
Float Voltage
54.5V
Discharge Cut-off Voltage (Low Cut-off
Voltage)
42V
Low Restart Voltage (Reconnect Voltage)
45V
Mass
36kg
Max Continuous Charge /Discharge Current
(25°C ± 5°C)
50A (1.25C)
Max Pulse Charge/Discharge Current (10s,
25°C ± 5°C)
120A (3C)
Battery Management System
Internal cell balancing, Over-current trip /
Internal cell balancing, failure detection and trip.
Under-Voltage, Over-Voltage, Over-Current, Over-
Temp, Under-Temp protection and trip
Isolation & Distribution Block Requirement
50A per battery connected in parallel
Operating Temperature
-40°C to 60°C (recommended 5°C to 35°C)
Storage Temperature
-5°C to 35°C
Cycle Life (1C, 25°C ± 5°C)
22,000
Depth of Discharge
100%
Round Trip Efficiency (1C, 25°C ± 5°C)
96%
Ingress Rating
IP65
Installation
Indoors or outdoors
Connections
8mm² (8 AWG) (Ø3mm) wire per pole
Warranty
20 Years or 22,000 cycles, whichever comes first, see
warranty document for details
3.2
Technical information