4.9 Temperature calibration
If after several days’ operation of your radiator, you notice a discrepancy bet-
ween the temperature observed in your room and the programmed temperature on the
appliance, you can recalibrate the radiator in 0.5°C intervals, using the following
procedure.
Access advanced settings (
see next chapter
). Press button
P2
several times
to find the temperature settings calibration function (parameter 4).
1) The setting shows the existing calibration
(default 0.0°C)
.
2) Measure the ambient temperature near the radiator with a reference
thermometer.
NOTE:
your thermometer must be placed in the middle of the
room, about 1.30 m above the floor, with no furniture between it and the
radiator.
3) If the temperature measured differs from that indicated by your appliance,
press the
–
or
+
keys to make them match.
EXAMPLE:
The reference temperature is 19° in your room, while the temperature setting
on your remote control is 20°. Press the key twice
+
when you are in setting 4, until the
display shows +1°C
(so 19+1=20°C)
.
4.10 Advanced remote control settings
Some of the remote control parameters can be adjusted. The following informa-
tion will allow you to access these parameters and modify them according to your
intended use.
Access to the parameter settings is made with the remote control switched off.
If necessary, press and hold to switch it off (the blower emits two audible
signals).
Once the remote control has been switched off, press and hold keys
P1
and
P2
together to access the settings menu. The following information will then be
displayed on the remote control screen:
Press
P2
to access the next parameter. (0
1
2…)
Press
P1
to access the previous parameter. (2
1
0)
Parameter number
Parameter value
No Parameter
Description
Default setting
Setting
0
Boost time
Adjustable from 15 to 120
minutes in 15-minute
increments
30 minutes
Press the
+
or
-
key
1
Programme P1
time
Adjustable from 15 to 120
minutes in 15-minute
increments
- If parameter 3 = 0
or 2: 30 minutes
Press the
+
or
-
key
- If parameter 3 = 1:
60 minutes
2
Programme P2
time
Adjustable from 15 to 120
minutes in 15-minute
increments
- If parameter 3 = 0
or 2: 30 minutes
Press the
+
or
-
key
- If parameter 3 = 1:
60 minutes
3
Type of
programme
P1/P2
Value 0 (blower only),
1 (radiator on boost) or 2
(radiator on boost + blower)
2
Press the
+
or
-
key
4
Setpoint tempera-
ture calibration
Adjustable between -5.0°C
to 5.0°C in 0.5°C increments 0,0°C
Press the
+
or
-
key
5
Room temperature
calibration
Not available on this model 0
6
Type of energy
source
Not available on this model 1
7
Default display
Value 0 (time) or 1 (setpoint
temperature)
1
Press the
+
or
-
key
8
Version number
display and reset
Reset to factory settings.
x.x
Press the
+
key
for 10 seconds
The time will have to be
re-set.
9
Window open/close
detection function
Value 0 (function disabled)
or 1 (function enabled)
1
Press the
+
or
-
key
End
Quitting parameter
settings display
Quit parameter setting menu