Step 2
3.0 On Site Commissioning / Set Up
3.1.1
3.1.2
3.1.3
This section covers set up, configuration of the unit for installation (either intermittent or
continuous running) and altering pre-set factory settings.
The control panel can be accessed by inserting a large flat bladed screwdriver into the slot
located on the side of the OF100GIP and eased out, care should be taken while doing this to
ensure the slot area is not damaged.
On first power up, all LED’s should flash in sequence and then both Bathroom and Kitchen Room
selection button lights should start to flash to indicate that an appropriate installation setting
needs to be selected.
To enter the commissioning mode press and hold [-/+] buttons simultaneously for approximately 3 seconds until the Bathroom & Kitchen
lights flash simultaneously - airflow settings from previous commissioning should be recalled, these settings can now be re-adjusted.
Note: To ‘factory reset’ press and hold [-/+] buttons simultaneously for approximately 10 seconds until all lights flash to indicate the fan
has been reset to factory settings and then revert to both room selection lights at start of commissioning mode.
Press Bathroom or Kitchen button
- light will go solid
Press button again
- light will now flash at a slower rate
to indicate intermittent mode
Press Bathroom or Kitchen button
- light will go solid
High Airflow (Boost) button will flash
– factory setting:
Press speed adjustment buttons to required
level and verify with an airflow meter -
re-press Boost button to confirm
Low Airflow (Trickle) button will flash
– factory setting:
Press speed adjustment buttons to required
level and verify with an airflow meter
- re-press Trickle button to confirm
Selection lights should remain on for approximately 10 seconds to enable the setup and status of the fan to be
observed and checked, upon which time the commissioning section of the controls should lock out.
Note:
Pullcord and Switch Live will be ignored when in commissioning mode.
For Intermittent Mode
For Continuous Mode
Step 1
Step 2
Press respective “Airflow” button for
required intermittent room airflow
- factory settings
Press speed adjustment buttons to required
level and verify with an airflow meter -
re-press Airflow Button to confirm
For HumidiSMART press
button to turn on
- light will go solid
For TimerSMART press
button to turn on
- light will go solid
Step 5
Step 4
Step 3
To Reactivate Commissioning Mode or carry out a Factory Reset
Step 1
WC 6 l/s Bathroom 15 l/s
Utility 30 l/s Kitchen 60 l/s
Step 3
For HumidiSMART press
button to turn on
- light will go solid
For TimerSMART press
button to turn on
- light will go solid
Step 5
Step 4
Bathroom 8 l/s Kitchen 13 l/s
Bathroom 5 l/s Kitchen 8 l/s