8. Installation
8.1. Handling in an upright position
It is recommended that the units be handled on their transport
brackets (1) and removed at the last moment, as close as possible to
the installation site.
If the equipment is handled by a forklift truck, care should be taken
to ensure that it supports the supporting structure. Adapt the choice
of handling equipment to the weight of the equipment received (refer
to the weight given at the beginning of the document).
During transportation, the connections are fastened to the inside of
the unit to facilitate handling and prevent damage to the
connections.
Control board terminal blocks
8.2. Lifting in horizontal position
Under no circumstances should the unit be lifted using the mounting
bracket as fitted in the factory.
Particular attention should be paid when lifting it off the floor and placing
it on the floor to avoid shocks that could damage the structure and
integrity of the product.
If the unit is transported by crane, use a cross-bar and belt it to keep it in
horizontal position (air flow).
Do not obstruct the opening of the side doors to attach the unit to
the ceiling.
Support areas under the central part:
■
Recessed from door joints and locks
■
From the bottom edge of the front panel to the bottom edge
of the back panel.
8.3. Installation precautions
Make sure that there are no obstacles in front of the unit's supply jet.
■
If the ceiling slopes, it is recommended to install the unit on the upper part of the slope.
■
There must be no beams perpendicular to the unit's supply jet.
■
If there are light fixtures protruding from the ceiling, the air stream must be able to pass over the light fixtures so that it
is not blocked by them.