background image

EN - 19

Meaning symbols:

1

SHIFT

The second function of 
the buttons is active.

1

TIMER

The ventilation setting 
is overruled by a timer 
function.

4

ComfoHood* is active.

5

Supply fan is switched 
off.

5

Exhaust fan is switched 
off.

6

High fan speed.

6

Medium fan speed.

6

Low fan speed.

6

Fan is running at very 
low speed.
(Only choose this option 
when nobody is home.)

7

Night cooling is active.

D

Q

 Manual operation 

indicator;

Q

 Auto operation 

indicator.

2.1  AUTO operation

In  Automatic  operation  mode  the  device 
can  tell  the  ventilation  unit  automatically 
which  ventilation  setting  is  wanted.  The 
default ventilation setting of the ventilation 
unit  is  “Medium”  (position  2).  Eight 
exceptions  to  this  default  setting  can  be 
programmed  into  the  device  (see:  Setting 
the PROG).

The device is in Automatic operation mode 
when   is pointing to AUTO.
Press  AUTO  MAN,  to  switch  to  the 
Automatic operation mode.

2.2  MAN operation

In 

Manual 

operation 

mode 

the 

preprogrammed ventilation settings of the 
device will be overruled (temporarily).

Overrule temporarily:  

Directly  press 

  or 

  to  increase  or 

decrease the fan speed.
The manual operation mode overrules the 
current program. 
The   is blinking next to MAN.
The next program will overrule the manual 
operation mode again.
Press  AUTO  MAN  to  return  to  the 
Automatic operation mode immediately.

Overrule permanently:  

1.  Press AUTO MAN, to go to Manual 

mode. 

2.  Press 

 or 

 to increase or 

decrease the fan speed. 

The   is pointing to MAN.
The  device  will  stay  in  the  Manual 
operation  mode  until  AUTO  MAN  is 
pressed again. 

Only available if the mentioned 
function is connected.

Summary of Contents for ComfoSense CH

Page 1: ... ComfoSense Manual ComfoSense Betriebsanleitung ComfoSense Manuel ComfoSense Manuale ComfoSense Podręcznik ComfoSense Manual ComfoSense Heating Cooling Fresh Air Clean Air ComfoSense CH ComfoSense 55 ComfoSense 67 ...

Page 2: ...he ComfoHood 20 2 5 Switching the ComfoHood Timer 20 2 6 Switching the PARTY TIMER 20 2 7 Ventilation program PROG 21 2 8 Setting the CLOCK 23 2 9 Setting the COMF Comfort temperature 23 2 10 Switching the FAN 23 2 11 Setting PARAM Parameters 24 2 12 CLOCK Back up 24 3 Error messages 25 4 Installation 26 5 Commissioning 26 5 1 Power up 26 5 2 Setting P menu s 26 I Figures 95 ...

Page 3: ...r installation to a maximum of 30 months after production date of the device The warranty becomes invalid if Q The installation has not been carried out according to the applicable regulations Q The defects are due to incorrect connection inexpert use or contamination of the device Q Parts are used that have not been supplied by the manufacturer or repairs are made by unauthorized persons On site ...

Page 4: ...nu Q Exit menu Display 1 Q Text Q Time 2 Value program parameter temperature 3 Q Degree Celsius Fahrenheit Q Percentage 4 ComfoHood 5 Q Supply fan off Q Exhaust fan off 6 Fan speed 7 Night cooling active 8 External sensor overrules the ventilation setting 9 Q Start time of a program Q End time of a program Only available if the mentioned function is connected Shown temperature in F will be changed...

Page 5: ...efault setting can be programmed into the device see Setting the PROG The device is in Automatic operation mode when is pointing to AUTO Press AUTO MAN to switch to the Automatic operation mode 2 2 MAN operation In Manual operation mode the preprogrammed ventilation settings of the device will be overruled temporarily Overrule temporarily Directly press or to increase or decrease the fan speed The...

Page 6: ...rm The text says OFF for 2 seconds 2 5 Switching the ComfoHood Timer This function is only visible if a ComfoHood cooker hood with sensor is connected and a delay time is programmed in PARAM P20 Turning on the ComfoHood Timer 1 Press MENU The text says HOOD 2 Press to choose HOOD TIMER 3 Press OK to confirm The text says ON for 2 seconds The text TIMER is visible in the main screen Turning off the...

Page 7: ...ram with the shortest time is the leading program In the example above Prog 3 overrules Prog 2 When both overlapping programs have an equally long period the program with the smallest program number will be the leading program In the example above Prog 3 overrules Prog 5 Every day in the program starts at 3 00 and ends at 2 59 Setting a program 1 Press MENU 2 Press or to choose PROG 3 Press OK to ...

Page 8: ... for 2 seconds After this SET is blinking The next program number is visible 18 Press MENU to return to the main menu Or go back to step 4 to set another program Deleting a program 1 Press MENU 2 Press or to choose PROG 3 Press OK to confirm SET is blinking The program number is visible 4 Press or to choose the program to delete PROG is blinking The program number is visible 5 Press OK seven times...

Page 9: ... IN or exhaust OUT fan of the ventilation unit can be turned off manually This may be desired to keep out unpleasant odors from outside Bear in mind that switching off a fan will temporarily immobilize your dwelling s balanced ventilation system so do not forget to turn the fans on again When can the FAN not be switched To prevent air being sucked back from the chimney of a fireplace the ventilati...

Page 10: ... 4 Press OK to confirm The parameter number P1 is blinking 5 Press or to choose the main parameter menu number 6 Press OK to confirm A second number next to the chosen number is blinking 7 Press or to choose the sub parameter menu number 8 Press OK to confirm The parameter value appears 9 When the appeared value is blinking press or to change the parameter value Only a parameter value that is blin...

Page 11: ...elf automatically Resetting error messages 1 Press MENU 2 Press OK 4 Installation Disconnect the ventilation unit from the main power before installing the device Always follow local safety regulations The letters mentioned in this chapter refer to the installation figures fig 1 2 or 3 at the back of this document 1 If ordered Attach the wall mounting casing I with the plugs H and screws G to the ...

Page 12: ... result will be 1 Press OK The text says SHIFT for 2 seconds 2 Press MENU before the text SHIFT disappears The text says COMF 3 Press or to choose PARAM 4 Press OK to confirm The parameter number is blinking 5 Press twice to choose PASSW 6 Press OK to confirm The password number 0 appears 7 Press to choose 14 8 Press OK to confirm P3 is blinking 9 Press or to choose the main parameter menu number ...

Page 13: ... in Default Screen 1 Q Clock not visible Default Screen 0 895 0 1 0 Q Night cooling symbol visible in Default Screen 1 Q Night cooling symbol not visible in Default Screen 0 896 0 1 0 Q Degrees in Fahrenheit 1 Q Degrees in Celsius 0 897 0 255 Software version read only value 898 1 5 Quality RF reach Q 1 bad Q 5 good 899 0 1 0 Reset ventilation program PROG Only available if the mentioned function ...

Reviews: