14 - EN
5.3 Wall mounting, restricted height
minimum
150mm
450mm
minimum
150mm
minimum
332mm
minimum 549mm
1
2
Mount the unit against a wall
with a minimum mass of 200
kg/m2.
The stated height is an indication, and
is dependent on the type of air ducts
and condensation drain selected.
Remove the top 2 screws from the
rear.
If no display is fitted:
Use the air-flow direction sticker on
top of the unit to determine which side
is the rear.
Use the screws removed to secure 1
of the mounting brackets supplied and
2 of the spacers supplied to the unit.
■
Place the flat side of the mounting
bracket against the unit;
■
Place the sloping side of the
mounting bracket upwards;
Allow the notches in the spacers to
slot over the mounting bracket.
3
4
5
Remove the bottom 2 screws from
the rear.
Use the screws removed to secure 2
of the spacers supplied to the unit.
Mount the second mounting bracket
supplied to the wall, ensuring it is
level.
■
Place the flat side of the mounting
bracket against the wall;
■
Place the sloping side of the
mounting bracket downwards;
6
Example of
controllers(s)
7
Example air duct
8
Example siphon
Connect the required controllers(s) as
described in the relevant controller
manual.
We recommend using the
front-most connector for the
ComfoSense.
Fit the air ducts to the unit as
described in the section on mounting
air ducts.
Fit the siphon to the bottom of the
unit as described in the section on
mounting the condensation drain.
9
10
Example valve
Example grille
11
0
50
100
150
200
250
300
350
400
0
50
100
150
200
250
300
p
st
[Pa
]
Qv [m
3
/h]
100%
40%
30%
15%
90%
80%
70%
60%
50%
Example graph
Hang the unit on the mounting bracket
fixed to the wall.
Screw the 4 spacers to the wall.
Fit the valves and/or grilles as
described in the section on mounting
valves and/or grilles.
Programme the required air-flow
volumes and time delays as described
in the service manual.
Fill in the installation report.