20 - EN
EN - 21
(Malfunction) information values
Sub-menu
Description
Minimum
Maximum
Factory
reset
P76
Selftesting the ComfoAir.
0
1(= activate)
0
Note:
■
The LEDs on the display of the ComfoAir will start flashing.
■
The ComfoAir will start running at its maximum speed (RPM).
■
The bypass valve of the ComfoAir will open and close.
■
The frostfree element valve of the ComfoAir will open and close once the bypass valve is
closed (if a frostfree element is registered).
P77
Resetting filter dirty counter.
0
1(= activate)
0
Note:
This resets the counter that triggers a dirty filter alert on the ComfoAir.
This allows the filter to be cleaned or replaced before the dirty filter alert appears.