7 - EN
2.4 Installation conditions
In order to determine whether the ComfoAir can
be installed in a certain area, the following aspects
must be taken into account:
• The ComfoAir must be installed according to the
general and locally applicable safety and instal-
lation regulations of power and water compa-
nies, as well as the instructions in this manual.
• The system must be fitted to allow sufficient
room around the ComfoAir for the air connec-
tions and supply and exhaust ducts as well as
for carrying out maintenance activities.
•
The ComfoAir must be installed in a frost-free
space. The condensation must be drained off
frost-free, at a gradient and incorporate a 'U' bend.
We do not recommend installing the Com-
foAir in areas with a higher average humidity
(such as bathroom or toilet). This will prevent
condensation on the outside of the ComfoAir.
• The room must offer the following provisions:
- Air duct connections.
- 230V electrical connection.
- Provisions for the condensation drain.
- Wiring for an wired 3-position switch
(optional).
• The cable used to connect the CC Ease panel
or the CC Luxe panel must have the following
specifications:
- Cable type: shielded twisted pair 4x0.34mm
2
.
- Cable lengtth: 10m maximum.
The connections of the CC Ease panel must
be crossed. (Rx must be connected to Tx).
• A gap should be left near the doors in order to
ensure effective and draughtfree airflow in the
house. A gap under the inside doors must be
atleast 10mm.
If these openings are obstructed, due to
draught excluders or deep-pile carpet, the
airflow in the house will stagnate. As a result,
system performance will be compromised or
fail altogether.
2.5 Installation of the ComfoAir
2.5.1 Transport and unpacking
Take the necessary precautions when transporting
and unpacking the ComfoAir.
Make sure the packing material is disposed
of in an environmentally friendly manner.
2.5.2 Checking the delivery
Contact your supplier immediately in case of dam-
age or an incomplete delivery. The delivery must
include:
• ComfoAir;
Check the identification plate to ensure that it
is the required type.
•
Mounting bracket;
• Documentation.
The ComfoAir is supplied in the following types:
Type
ComfoAir 550 L Luxe
ComfoAir 550 R Luxe
ComfoAir 550 L Luxe ERV
ComfoAir 550 R Luxe ERV
ComfoAir 550 L Luxe VV
ComfoAir 550 R Luxe VV
Meaning of the suffixes:
* L
= Left version
* R
= Right version
* VV = Contains a preheater element by default.
* ERV = Contains a enthalpy exchanger by default.
* Luxe = Contains a connection board with extra func-
tion by default.
CC Ease panel or CC Luxe panel (optional) can be ordered
separately.
2.6 Mounting of the ComfoAir
2.6.1 Mounting on the wall
Mount
the ComfoAir against a wall with a minimum
mass of 200 kg/m
2
. For other types of wall, we rec
-
ommend using the Zehnder mounting frame on the
floor (available as an optional extra). This reduces
contact noise as much as possible. The ComfoAir
does not require any space at the sides for effective
operation.
Do not mount the side of the ComfoAir
against the wall due to the risk of impact
sound.
1. Fasten the mounting bracket to the wall. Make
sure it is level and at least 878mm from the floor
(depending on the type of condensation drain
selected).
Leave a minimum space of 1m in front of the
ComfoAir for carrying out maintenance.
2. Hang the ComfoAir on the mounting bracket.
3. Mount the condensation drain under the Com-
foAir. The stated dimension of 235 mm is an in-
dication only, and is dependent on the type of
condensation drain selected.