16
3.1.5
Wizard Menu Structure
Extract High
Rotate button to choose either RH (Right Hand) or LH (Left Hand) Configuration
Factory airflow set at 66%, rotate button to required airflow %
Port Configuration
Supply High
Factory airflow set at 66%, rotate button to required airflow %
Extract Low
Factory airflow set at 33%, rotate button to required airflow %
Supply Low
Factory airflow set at 33%, rotate button to required airflow %
Extract AUX
Factory set at 50%, variable option 15%-100%, rotate button to required airflow %
Supply AUX
Factory set at 50%, variable option 15%-100%, rotate button to required airflow %
Smart Humidity
Rotate button to choose either ON or OFF (Default setting: ON)
Smart Timer
Rotate button to choose either ON or OFF (Default setting: ON)
Setup Complete
Rotate button to EXIT and press button to select
Installer Settings
3.1.6
Valve Set-up
• Set the fan speed approximately to achieve the desired extract high flow rate.
• Close all windows and doors, including the rooms in which measurements are being carried out.
• The index terminal (the one furthest away) should be set to fully open.
• All other terminals are adjusted to achieve the required flow rate.
• If the index terminal has to be closed to achieve the correct flow rates, then reduce the fan speed and
balance the terminals.
• Switch the unit to low speed to achieve the desired extract low flow rate.
It should not be necessary to adjust the extract valves further.
• Repeat tests for supply air valves.