en32
Display indication
Factory setting
From the standard display, you get to the menu when
automatic mode has been switched off. In order to
start, you must press the MENU button for about 3
seconds.
This screen area shows that access to the menu level
is being carried out. The display will disappear shortly
thereafter.
You can choose between the following languages:
“SPRACHE DEUTSCH“, “LINGUA ITALIANA”,
“LANGUE FRANÇAISE”, “LANGUAGE ENGLISH”,
“IDIOMA ESPAÑOL”.
Deutsch
Here the value of the motor limiting current [A]
is entered at which the motor protection shall be
triggered.
3~ max. 10 A
1~ max. 9 A
Here the direction of rotation could be reversed.
Normally, this is not required. Using the button Enter,
confirm the rotation direction pre-set by the factory.
Only appears if “Motor 3~ UVW“ has been set in the
expert menu (as factory-set).
Clockwise
direction of
rotation
(clockwise)
We recommend to take over the factory
setting of 28 Hz. A frequency of 25 Hz may
never be undercut!
15 Hz
For plants with a collection tank, the pump can
be protected against dry-running by using a float
switch, for example, when the minimum water level is
undercut in the collection tank. (
Chapter 6.5.1).
If such a dry-running protection is available, the
factory setting must be changed from NO to YES.
This switching input can also be used as enabling
contact, for example in case of a irrigation system.
YES
This screen area shows that an other level is reached
in the menu.
Here the output-side target pressure of the pump is
set. For plants with a collection tank, the factory setting
of 3.5 has proven.
For plants with direct connection to the drinking water
line, it has to be taken into consideration that the target
pressure consists of the flow pressure of the water
supply and the pressure generated by the pump.
The target value to be set must orientate to the fact
that in case of little water withdrawal (e.g. hand basin),
which is common in a household, the pump keeps on
running permanently and does not swap into a steady
start-stop operation (
Chapter 5.4.1).
3.5 bar
!
ZP SPEEDCONTROL COMFORT
en
English
6.4.1 Sequence of parameters in the menu