ID098
HwBusOVP
Bus
hardware
overvoltage
ID099
HwBuckBoostOCP
Excessive
BuckBoost
hardware flows
ID100
HwBatOCP
Excessive
battery
hardware flows
ID102
HwPVOCP
Excessive PV hardware
flows
ID103
HwACOCP
Excessive AC hardware
output flows
ID110
Overload1
Overload protection 1
Check whether the inverter is
running in overload
ID111
Overload2
Overload protection 2
ID112
Overload3
Overload protection 3
ID113
OverTempDeratin
g
Internal
temperature
too high.
Make sure that the inverter is
installed in a cool, well-ventilated
place, below the temperature limits
and away from direct sunlight. Check
that the inverter has been installed
according to the instructions in the
manual.
ID114
FreqDerating
AC frequency is too high. Make sure that the grid frequency
and voltage are within the acceptable
range
ID115
FreqLoading
AC frequency is too low
ID116
VoltDerating
AC voltage is too high
ID117
VoltLoading
AC voltage is too low
ID124
BatLowVoltageAla
rm
Low battery voltage
protection
Check that the battery voltage on the
inverter side is not too low
ID125
BatLowVoltageSh
ut
Battery shutdown due to
low voltage
ID129
unrecoverHwAcO
CP
Permanent
hardware
error due to output
overcurrent
Internal inverter errors. Switch it off,
wait 5 minutes and switch it on
again. If the errors still occur, contact
technical support.
ID130
unrecoverBusOVP
Fixed bus overvoltage
error
ID131
unrecoverHwBus
OVP
Bus
hardware
overvoltage error