Page - 38/81
AFCZP0BC- COMBIACX & ACEX - User Manual
for a time established by AUXILIARY TIME parameter.
-
OFF: The stop on ramp feature is not performed. That means the truck
comes down slowly during the AUXILIARY TIME.
After this “auxiliary time”, the electromechanical brake is applied and the 3-
phase bridge is released; if the electromechanical brake is not present the truck
comes down very slowly (see the AUX OUTPUT #1 option programming and
see also 13.4).
7) QUICK
INVERSION
It can be set:
-
NONE:
The quick inversion function is not managed (no effect when
CNC#2 switches over).
-
TIMED:
The quick inversion function is timed.
-
BELLY: The quick inversion function is managed but not timed.
8) SET MOTOR TEMPERATURE
It can be set:
-
OPTION#1: An analog sensor for the control of the motor temperature is
connected to CND#3. The temperature sensor is a KTY 84-130 PTC
(positive thermal coefficient resistance).
-
OPTION#2: An analog sensor for the control of the motor temperature is
connected to CND#3. The temperature sensor is a KTY-83 PTC.
1. DIGITAL: A digital (on/off) sensor for the motor temperature monitoring is
connected to CND#3 input.
2. NONE:
No temperature sensor is connected.
9) EPS
It can be set:
-
NONE:
NO EPS is present on the truck, CombiACX does not wait for
CAN messages by the EPS and it does not apply EPS and braking steer
cutback.
-
OPTION#1: EPS is present and it is an EPS-AC0, E TOGGLE
SWITCHES type.
-
OPTION#2: EPS is present and it is an EPS-AC0, POT + ENCODER type.
10) INVERSION MODE
ON/OFF:
This parameter sets the logic of the Quick Inversion input. If set = ON,
the Quick Inversion switch is Normally Closed (function active when switch
opens). If set = OFF, the Quick Inversion switch is Normally Open (function
active when switch closes).
11) EV1
PRESENT/ABSENT: If set = PRESENT the EV1 output is driven and the
diagnosis “EV1 DRIVER SHORTED” relative to the load connected to CNA#1 is
activated. When set = ABSENT the diagnosis is not implemented and the EV1
output is NOT driven.
12) EV2
PRESENT/ABSENT: If set = PRESENT the EV2 output is driven and the
diagnosis “EV2 DRIVER SHORTED” relative to the load connected to CNA#8 is
activated. When set = ABSENT the diagnosis is not implemented and the EV2
output is NOT driven.
13) EV3
PRESENT/ABSENT: If set = PRESENT the EV3 output is driven and the
Summary of Contents for ACEX
Page 27: ...AFCZP0BC COMBIACX ACEX User Manual Page 27 81 8 DRAWINGS 8 1 Mechanical drawing COMBIACX...
Page 28: ...Page 28 81 AFCZP0BC COMBIACX ACEX User Manual 8 2 Mechanical drawing ACEX...
Page 29: ...AFCZP0BC COMBIACX ACEX User Manual Page 29 81 8 3 Connection drawing COMBIACX...
Page 30: ...Page 30 81 AFCZP0BC COMBIACX ACEX User Manual 8 4 Connection drawing ACEX...