background image

10

    When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take    

    place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.

    Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.

13.Charging procedures

    In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination 

    of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to 

    minimise the amount of refrigerant contained in them.

    Cylinders shall be kept upright.    

    Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. 

    Label the system when charging is complete (if not already).

    Extreme care shall be taken not to overfill the refrigeration system.

    Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of 

    charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

14.Decommissioning

    Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its 

    detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an 

    oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential 

    that electrical power is available before the task is commenced.

a)Become familiar with the equipment and its operation.

b)Isolate system electrically.

c)Before attempting the procedure ensure that:

   Mechanical handling equipment is available, if required, for handling refrigerant cylinders; 

   All personal protective equipment is available and being used correctly;

   The recovery process is supervised at all times by a competent person;

   Recovery equipment and cylinders conform to the appropriate standards.

d)Pump down refrigerant system, if possible.

e)If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

f)Make sure that cylinder is situated on the scales before recovery takes place.

g)Start the recovery machine and operate in accordance with manufacturer's instructions.

h)Do not overfill cylinders. (No more than 80 % volume liquid charge).

i)Do not exceed the maximum working pressure of the cylinder, even temporarily.

j)When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment 

  are removed from site promptly and all isolation valves on the equipment are closed off.

k)Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

15.Labelling

   Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated 

   and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

16.Recovery

   When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that

   all refrigerants are removed safely.When transferring refrigerant into cylinders, ensure that only appropriate refrigerant

   recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.

   All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special

   cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off

   valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

   The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at

   hand and shall be suitable for the recovery of flammable refrigerants.In addition, a set of calibrated weighing scales shall

   be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition.

   Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and

   that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult

   manufacturer if in doubt.

   The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant

   Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or

   compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that

   flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning

   the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process.

   When oil is drained from a system, it shall be carried out safely.

   When flammable refrigerant are employed, appliance shall be stored in a well -ventilated area.

Summary of Contents for ZWACR0723V

Page 1: ...e Please check the applicable models technical data from the nameplate pasted on the unit This appliance is using R32 mildly flammable refrigerant 此設備使用輕度易燃製冷劑R32 在安裝或操作新空調機組之前 請仔細閱讀本手冊 請妥善保管本手冊以備將來參考 適用的型號 技術資料見機身銘牌 重 要 提 示 Window Type Room Air Conditioner User Manual 窗式空調器 用戶使用手冊 19 2 CN EN ZWACR0723V ZWACR0923V ZWACR1223V ZWACR1823V ZWACR2123V MODEL ...

Page 2: ...nce of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants 5 Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer 6 The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an o...

Page 3: ... damage to the equipment inside the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations Explanation of symbols displayed on the unit 3 WARNING CAUTION CAUTION CAUTION This symbol shows that this appliance used a mildly flammable refrigerant If the refrigerant is leaked and exposed ...

Page 4: ... packaging indicates that this product may not be treated as household waste Instead it shall be handed over to the applicable collection point for the recycling of electrical and electronic equipment By ensuring this product is disposed of correctly you will help prevent potential negative consequences for the environment and human health which could otherwise be caused by inappropriate waste han...

Page 5: ...directly to cool air for a prolonged period of time If the air conditioner is used together with burners or other heating devices thoroughly ventilate the room to avoid oxygen deficiency Warning Do not allow children to play with the air conditioner Children must be supervised around the unit at all times operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposur...

Page 6: ...t and the circuit breaker fuse rating should be the same as that of the power cord and wall outlet Power cord conductors are distinguished according to the color as shown in Wiring Diagram located on the top of the machine WARNINGS FOR PRODUCT INSTALLATION 1 Installation must be performed by an authorized dealer or specialist Defective installation can cause water leakage electrical shock or fire ...

Page 7: ... circuit should hold a current valid certificate from an industry accredited assessment authority which authorises their competence to handle refrigerants safely in acc ordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried...

Page 8: ...it may lead to the risk of fire or explosion All possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed to make sure that there are no flammab...

Page 9: ... atmosphere from a leak 9 Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 10 Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be ...

Page 10: ... j When the cylinders have been filled correctly and the process completed make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off k Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked 15 Labelling Equipment shall be labelled stating that it has been de com...

Page 11: ...e This is because the noise in the surroundings is comparatively low at night If your feel that the noise is too loud switch the thermostat to lower numbers UNIT PARTS IDENTIFICATION NOTE Different models have different front panels and cabinets Illustrations in this manual are for explanatory purposes The actual shape of your indoor unit may be slightly different The actual shape shall prevail Se...

Page 12: ...re TIMER on some models When the unit is on press the Timer button will initiate the Auto stop program the TIMER OFF indicator light illuminates Press the UP or down button to select the desired time Press the TI MER button again within 10 seconds the Auto start program is initiated And the TI MER ON indicator light illuminates Press the up or down button to select the desired Auto start time When...

Page 13: ... shows On for 3 seconds for some units The UV UltraViolet C radiation feature will help to purify the air inside Press it for 3 seconds again to stop the UV feature and the UV light turn dark the LED DISPLAY shows OF for 3 seconds for some units Shows Error codes Inverter Type E0 Indoor EEPROM error E1 Indoor outdoor communicaiton error E3 Indoor fan motor speed out of control E4 Room temperature ...

Page 14: ...ith fresh water then shake off excess water 6 Dry it in a cool dry place and refrain from exposing it to direct sunlight Winter Storage CAUTION NEVER operate the air conditioner without the air filter as dust dirt particles can contribute to equipment failure Model A If your filter has a small air freshening filter optional it can be installed at any of the four positions install it at the postion...

Page 15: ...emove all packaging from inside the carton along with any inserts placed into the side louvers CAUTION All side louvers of the cabinet must remain exposed to the outside of the structure Remove inserts placed into the side louvers 1 To avoid vibration and noise make sure the unit is installed securely and firmly 2 Install the unit where the sunlight does not shine directly on the unit If the unit ...

Page 16: ...around the inside and outside to provide satisfactory appearance and protection against the weather insects and rodents see Fig 7 Flash or seal around external wall frame or architrave Drain pan Preferred method of installation into a timber framed wall partition or window Sturdy timber frame all round unit Timber framed wall or partition External support frame at balance point of air conditioner ...

Page 17: ...rom coil Room temperature below 18 C 64 F Cooling may not occur until room temperature rise above 18 C 64 F Unit turned off and then on too quickly Turn unit off and wait for 3 minutes before restarting House fuse blown or circuit breaker tripped Replace fuse with time delay type or reset circuit breaker Selector Control in OFF position Turn selector to the desired FAN or COOL setting Unit turned ...

Page 18: ...e size of the power supply cable signal cable fuse and switch needed is determined by the maximum current of the unit The maximum current is indicated on the nameplate located on the side panel of the unit Refer to this nameplate to choose the right cable fuse or switch Rated Current of Appliance A Nominal Cross Sectional Area mm 3 and 6 0 75 1 1 5 2 5 4 6 NOTE TO be in compliance EN61000 3 11 the...

Page 19: ...19 安裝必須由授權經銷商及受過專業訓練的人員進行 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ...

Page 20: ...20 警告 小心 小心 小心 此符號表示本電器使用輕度易燃製冷劑 如果製冷劑洩漏並暴 露於外部火源 則有著火的風險 此符號表示應仔細閱讀用戶使用手冊 此符號表示用戶使用手冊或安裝手冊提供相關資訊 此符號表示維修人員應參考安裝手冊處理此設備 ...

Page 21: ...項 此設備使用輕度易燃製冷劑R32 請聯絡授權的棄置點處理您的舊空调器 為保持家園整潔貢獻力量 產品或其包裝材料中的 符號表示本產品不可作為家庭垃圾處理 應將其運送至適當的回收點 確保妥善回收電氣電子設備 確保正確棄置本產品 幫助 避免因本產品廢棄物處理不當而導致對環境和人類健康造成潛在有害影響 有關回收本產品的更多詳情 請聯絡您當地的市政機構 您的家庭垃圾處理服務機構或 您購買本產品的商店 22 28 29 31 31 32 34 35 ...

Page 22: ...此設備使用輕度易燃製冷劑R32 22 ...

Page 23: ...23 ...

Page 24: ...輕度易燃製冷劑R32 輕度易燃製冷劑 24 ...

Page 25: ...25 用戶使用手冊 用戶使用手冊 此符號表示本電器使用輕度易燃製 冷劑 如果製冷劑洩漏並暴露於外 部火源 則有著火的風險 ...

Page 26: ...26 ...

Page 27: ...27 ...

Page 28: ... C 32 C 62 F 90 F 5 C 24 C 23 F 76 F 0 C 27 C 32 F 80 F 18 C 43 C 64 F 109 F 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 MODE SLEEP LED CLOCK CANCEL TIMER FAN RESET LOCK CLOCK E ON OFF SET TEM P FAN SPEED AUTO F SWING 10 28 空氣過濾器 空氣過濾器 ...

Page 29: ...無線操作 僅限部分型號 首次使用WiFi功能時 長按SWING鍵3秒以啟動WiFi連接模式 當LED顯示屏顯示 AP 時 可設置WiFi連接 若在8分鐘內連接 路由器 成功 設備將自動退出WiFi連接模式 且無線指示燈亮起 若在8分鐘內連接失敗 設備將自動退出WiFi連接模式 29 ...

Page 30: ...ECO功能 僅限部分型號 在COOL模式下 按遙控器的ECO鍵 進入節能模式 30 紫外線 紫外線 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 ...

Page 31: ... 31 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣清新過濾器 過濾器 過濾器 空氣過 濾器 空氣清新過濾器 空氣過濾器 清潔空氣過濾器 排水 1 2 3 4 ...

Page 32: ...32 空氣過濾器 空氣過濾器 空氣過濾器 ...

Page 33: ...33 空氣過濾器 空氣過濾器 ...

Page 34: ...34 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 空氣過濾器 ...

Page 35: ...0 75 1 1 5 2 5 4 6 35 5000 6000 445x320x415 450x346x535 450x346x535 450x346x585 450x346x585 560x400x640 600x380x560 660x428x680 660x428x780 7000 9000 9000 12000 15000 24000 450x350x675 450x350x675 ...

Page 36: ......

Reviews: