STAIRCASE LIGHTING TIMER ASM-04
USER’S MANUAL
ZAMEL
Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 32 210 46 65, Fax +48 32 210 80 04
www.zamel.com
, e-mail: [email protected]
plik: asm-04_inst_ext_gb | modyfikacja:17.07.2019
APPEARANCE
FEATURES
TECHNICAL DATA
DESCRIPTION
ASM-04
Power input terminals: L; N
Rated supply voltage: 230 V AC
Supply voltage tolerance: -15 to +10%
Rated mains frequency: 50 / 60 Hz
Rated current load: 26 mA
Release terminals: IN; IN; IN
Release control current: 0.5 mA
Time delay setting range: 10 s to 10 min (with a rotary potentiometer)
Time delay setting resolution: ±10%
Time delay setting repeatability: ±5%
Power threshold setting: 0.1 to 2 kW
Power threshold trip off delay: 40 s
Power overload indication: red LED
Transmitter contact ratings: 1NO – 16 A / 250 V AC1 4,000 VA
Wiring terminals: 7
Wiring size: 0,2 ÷ 2,50 mm
2
Operating temperature: -20 ÷ +45
o
C
Installation orientation: any
Installation type: DIN rail
Protection grade: IP20
Overvoltage category: II
Pollution class: 2
Dimensions: single module 90 x 17,5 x 66 mm
Weight: 0,079 kg
● Controls time delay to turn staircase
lamps off
● Smooth lamp turn-off time delay
setting from 10 s to 10 min
● Power threshold setting from 0.1 to 2
kW for overload protection
● Works with single-pole backlit lamp
switches
● Forced lamp off override
● Power overload LED indicator
● Function of permanent switching on
the lighting
● Single-module enclosure
● For installation on a DIN rail
The ASM-04 staircase lighting timer
controls lamps in coridors and staircases.
Once tripped to turn on the lamps, the
staircase lighting timer turns them off au-
tomatically after a time delay preset by the
user. The time delay can be set between
10 seconds to 10 minutes with a potenti-
ometer on the front panel of the staircase
lighting timer. The staircase lighting timer
features a power limiter to isolate the con-
trolled lamp power line when the power
threshold, which can be set between 0.1
and 2 kW, is exceeded.
Input (supply) terminals
The device is designed for a
single-phase installation and
must be installed in accordance
with standards valid in a particu-
lar country. Installation, connec-
tion and control should be carried
out by a qualified electrician staff, who act in
accordance with the instruction manual and
the device functions. In case of casing dis-
mantling, the guarantee is lost and an electric
shock may occur. Before installation make
sure the connection cables are not under volt-
age. The cruciform head screwdriver 3,5 mm
should be used to install the device. Improper
transport, storage, and use of the device influ-
ence its wrong functioning. It is not advisable
to install the device in the following cases:
if any device part is missing or the device is
damaged or deformed. In case of improper
functioning of the device contact the producer.
CAUTION
Do not dispose of this device with
other waste! In order to avoid
harmful effects on the environment
and human health, the used device
should be stored in designated
areas. For this purpose, you can
dispose of household waste free
of charge and in any quantity to
a collection point set up, as well
as to the shop when you buy new
equipment.
Release terminals
(IN, IN, IN)
Power supply indicator
Power overload indicator
Time delay adjustment
Power threshold adjustment
Output (load) terminals