STAIRCASE LIGHTING TIMER ASM-04 

USER’S MANUAL

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 32 210 46 65, Fax +48 32 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: asm-04_inst_ext_gb | modyfikacja:17.07.2019

APPEARANCE

FEATURES

TECHNICAL DATA

DESCRIPTION

ASM-04

Power input terminals: L; N

Rated supply voltage: 230 V AC

Supply voltage tolerance: -15 to +10%

Rated mains frequency: 50 / 60 Hz

Rated current load:  26 mA

Release  terminals: IN; IN; IN

Release control current: 0.5 mA

Time delay setting range: 10 s to 10 min (with a rotary potentiometer)

Time delay setting resolution:  ±10%

Time delay setting repeatability: ±5%

Power threshold setting: 0.1 to 2 kW

Power threshold trip off delay: 40 s

Power overload indication: red LED

Transmitter contact ratings: 1NO – 16 A / 250 V AC1 4,000 VA

Wiring terminals: 7

Wiring size: 0,2 ÷ 2,50 mm

2

Operating temperature:  -20 ÷ +45

o

C

Installation orientation:  any

Installation type:  DIN rail

Protection grade: IP20

Overvoltage category:  II

Pollution class: 2

Dimensions: single module 90 x 17,5 x 66 mm

Weight: 0,079 kg

●  Controls time delay to turn staircase 

lamps off

●  Smooth lamp turn-off time delay 

setting from 10 s to 10 min

●  Power threshold setting from 0.1 to 2 

kW for overload protection

●  Works with single-pole backlit lamp 

switches

●  Forced lamp off override

●  Power overload LED indicator

●  Function of permanent switching on 

the lighting

●  Single-module enclosure

●  For installation on a DIN rail

The ASM-04 staircase lighting timer 

controls lamps in coridors and staircases.

Once tripped to turn on the lamps, the 

staircase lighting timer turns them off au-

tomatically after a time delay preset by the 

user. The time delay can be set between 

10 seconds to 10 minutes with a potenti-

ometer on the front panel of the staircase 

lighting timer. The staircase lighting timer 

features a power limiter to isolate the con-

trolled lamp power line when the power 

threshold, which can be set between 0.1 

and 2 kW, is exceeded.

Input (supply) terminals

The device is designed for a 

single-phase installation and 

must be installed in accordance 

with standards valid in a particu-

lar country. Installation, connec-

tion and control should be carried 

out by a qualified electrician staff, who act in 

accordance with the instruction manual and 

the device functions. In case of casing dis-

mantling, the guarantee is lost and an electric 

shock may occur. Before installation make 

sure the connection cables are not under volt-

age. The cruciform head screwdriver 3,5 mm 

should be used to install the device. Improper 

transport, storage, and use of the device influ-

ence its wrong functioning. It is not advisable 

to install the device in the following cases: 

if any device part is missing or the device is 

damaged or deformed. In case of improper 

functioning of the device contact the producer.

CAUTION

Do not dispose of this device with 

other waste! In order to avoid 

harmful effects on the environment 

and human health, the used device 

should be stored in designated 

areas. For this purpose, you can 

dispose of household waste free 

of charge and in any quantity to 

a collection point set up, as well 

as to the shop when you buy new 

equipment.

Release  terminals   

(IN, IN, IN)

Power supply indicator
Power overload indicator

Time delay adjustment

Power threshold adjustment

Output (load) terminals