background image

Set and unset associations:

 (Note: All association information will be cleared automatically once the wall controller 
is excluded from a network.)

Associations can be assigned and remove either via Z-Wave commands or using the 
device itself.

1. Set association by operating primary controller/gateway to send packets to the wall 
controller:

The primary controller/gateway sends packets to the wall controller using “Command 
Class ASSOCIATION” or “Command Class Multi Channel Association”

2. Set association by operating the wall controller and devices to be controlled:

To control a Z-Wave device from the Wall Controller the node ID of this device needs to 
be assigned to one of the four association groups. This is a three-step process: 

1. Press and hold down “ALL ON/OFF” button on the wall controller for over 3 seconds, 
LED indicator turns on.
2. Click any Group number button on the wall controller within 25 seconds to add the 
device to be controlled to the association group, double click any Group number button 
on the wall controller within 25 seconds to remove the device to be controlled to the 
association group.
3. Operate the device to be controlled to send Node Information Frame (please refer to 
the device manual) within 15 seconds, or set the device to exclusion mode within 15 
seconds, since it will send Node Information Frame in exclusion mode, LED indications 
are as follows:

LED blinks 5 times to indicate that the wall controller failed to add the associated device 
(the association group has already added maximum quantity associated devices that it 
supports ).

LED blinks 10 times to indicate that the wall controller added the associated device 
successfully.

LED blinks 8 times to indicate that the wall controller removed the associated device 
successfully.

To remove all associated devices in an association group on the wall controller directly:

1. Press and hold down “ALL ON/OFF” button on the wall controller for over 3 seconds, 
LED indicator turns on.

2. Click any Group number button on the wall controller 5 times continuously within 25 
seconds to remove all associated devices of this group, LED indicator blinks 8 times to 
indicate that the associated devices are removed successfully.

Operating the device

Summary of Contents for SR-ZV9002T4-CCT-RU

Page 1: ...ufacturers and or other applications All non battery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network Although it is controlling othe...

Page 2: ...upplied as complete set for flush mounting in the standard Dimensions Material 86x86x29 1mm Tempered glass panel with capacitive touch buttons Z Wave Controller L N SR ZV9002T4 CCT RU PRI Uin 100 240V...

Page 3: ...ful inclusion 2 Quits after 25 seconds timeout 3 Press and hold down ALL ON OFF button for over 3 seconds or short press the inclusion exclusion button to quit Exclusion Remove the device from a Z Wav...

Page 4: ...ionship between one device controlling another device is called association In order to control a different device the controlling device needs to maintain a list of devices that will receive controll...

Page 5: ...of associated devices using Scene Activation Set Scene ID 0x10 0x20 0x30 0x40 3 Press and hold down Scene button S1 S2 S3 S4 direct control of associated devices using Scene Conf Set Scene ID 0x10 0x...

Page 6: ...the wall controller within 25 seconds to remove the device to be controlled to the association group 3 Operate the device to be controlled to send Node Information Frame please refer to the device ma...

Page 7: ...vation Set Scene ID 0x10 0x20 0x30 0x40 to the last used Group 2 3 4 or 5 Press and hold down Scene button S1 S2 S3 S4 direct control of associated devices using Scene Conf Set Scene ID 0x10 0x20 0x30...

Page 8: ...erations to send out a Node Information Frame How to send out Node Information Frame Set the wall controller into inclusion exclusion mode press and hold down ALL ON OFF button for over 3 seconds or s...

Page 9: ...OLOR COMMAND_CLASS_SCENE_ACTIVATION COMMAND_CLASS_SCENE_ACTUATOR_CONF COMMAND_CLASS_MANUFACTURER_SPECIFIC COMMAND_CLASS_VERSION COMMAND_CLASS_ASSOCIATION_GRP_INFO COMMAND_CLASS_MULTICHANNEL_ASSOCIATIO...

Page 10: ...AC 100 240V AC Power 50 60Hz Wiring diagram Installation Z Wave Controller L N SR ZV9002T4 CCT EU PRI Uin 100 240VAC Iin 15mA MAX Out Z Wave Signal SW1...

Reviews: