background image

0

service hints

if floors are cold...

Possible cause

Return (cold) air grilles blocked

Air filter is dirty

System is out of balance

if blower/motor is noisy...

Check motor bearings

Check blower bearings

Air filter is dirty

smoke puffs out through doors...

Chimney draft incorrect

Soot and creosote buildup in heat exchanger or chimney

Chimney too low

Obstruction in chimney

Not enough fresh air to furnace room

Chimney diameter too large

Chimney clean-out door partially open

Other fuel burning device connected to same chimney

if your furnace is not giving you enough heat...

Thermostat not set correctly

No electric power to furnace

Using excessive amount of wood, but not heating

damper control fails to open...

Improper thermostat wiring

No power to damper control

Damper does not open

if you don't seem to be getting enough air circulation...

Air filter is dirty

Registers and grilles are obstructed

What to do

Check to make sure rugs and carpets are not covering return air 

grilles.

Clean or replace air filter, as necessary.

Check supply pipe dampers or registers to balance system.

Replace motor if necessary

Replace bearings if necessary

Clean or replace air filter, as necessary

Check chimney draft. With normal wood fire, chimney should draw 

.03 inch water column between furnace and barometric control

Clean if necessary.

Increase chimney height.

Check for obstruction such as loose mortar, bird nests and squirrel 

nests. Clean chimney to eliminate obstructions.

Check for obstructions in combustion air inlet. See page 14.

Too cold a chimney will chill flue gases as they rise up the chim-

ney. As this gas cools, it becomes heavy and other gases from the 

fire try to penetrate this heavy column of cool air. This results in 

back puffing, and may cause odors in your home. Obviously, the 

solution lies in improving your chimney.

Make sure chimney clean-out door is tightly closed.

Install separate chimney.

Reset thermostat above room temperature.

Check fuse or circuit breaker. If fuse is blown, replace. If breaker is 

tripped, reset. Check to make sure that electrical switch is on.

Baffles in firebox out of place or barometric damper set too high. 

Check baffle position, page 6, Fig. 6. Set barometric control to .03 

or less.

Recheck field wiring against wiring diagram.

Check 24 Volt side of transformer, check 115 Volt power to trans-

former.  Check  for  burn  spot  on  damper  control  relay.  Replace 

board if defective.

Check power to solenoid. Replace if defective.

Clean or replace filter, as necessary.

Check  supply  pipes  or  damper  positions.  Check  registers  and 

grilles to make sure they are not closed or obstructed by carpet, 

draperies, furniture or clothing. Remove obstructions.

note

Multiple coats of paint on registers and grilles may reduce the amount of free air opening causing restriction of 
air flow and reduction of warm air circulation. Registers and grilles in this condition should be replaced.

Summary of Contents for Klondike Eagle IV

Page 1: ...pliance Alpha American Co 10 Industrial Blvd Palisade MN 56469 www yukon eagle com YUKON EAGLE OWNER S MANUAL Assembly Installation Operation Repair Parts Model No LW 000 Series CAUTION Read Rules And...

Page 2: ...d during operation Do not operate with flue draft exceeding 03 W C Do not store flammable materials within marked installa tion clearances Frequently inspect and clean heat exchanger smoke pipe and ch...

Page 3: ...8 Duct Work and Blower Speed Adjustment 18 Testing Installations for Efficiency 18 Test Procedure 10 MAINTENANCE Cleaning the Chimney Smoke Pipe and Heat Exchanger 19 In Case of Chimney Fire 19 Servic...

Page 4: ...lt in failure of heat exchanger and cause dangerous operation 4 You must have a sufficient supply of combustion air to the area in which the furnace is located page 4 5 Factory Built Chimneys Connect...

Page 5: ...should occur be sure ash door and firedoor are closed Turn thermostat down to close primary air damper In the event of an electrical power failure be sure ash door and fire door remain closed In the...

Page 6: ...eat with second baffle making sure baffles interlock as shown in Fig 6 When properly installed baffles will not move more than 1 4 in any direction Failure to have baffles properly installed will seve...

Page 7: ...pre selected location making sure it is level Proceed as follows Before Installing check DRAW COLLAR Attach the draw collar around the smoke pipe and tight against the furnace cabinet so room air cann...

Page 8: ...r and place the 4 square box the furnished wiring harness over cable connector and replace the lock nut Secure the square box to the furnace with two sheet metal screws Connect the 34 long conduit to...

Page 9: ......

Page 10: ...ent outward into the collar and thus make a better joint WHEN FINISHED THE OPENING INTO THE FLUE MUST BE EQUAL IN SIZE TO THE COLLAR OF THE DRAFT CONTROL If flue pipe is made of material too heavy to...

Page 11: ...stible wall is allowed if the space is insulated according to NFPA 90B table 6 5 1 2 DO NOT CONNECT THIS FURNACE TO A CHIMNEY SERVING ANOTHER APPLIANCE The chimney should be no less than 8 inches insi...

Page 12: ...r chimney must terminate at least 2 feet above the peak of the roof Adding more chimney height sometimes cures the problem See Fig 12 page 14 5 Home located on side of hill When the wind blows over a...

Page 13: ...You need two grilles each with 180 square inches of free opening Metal grilles have about 60 free open area so you need two metal grilles with 300 square inches each of louvered area The height should...

Page 14: ...chim ney Outside air is also needed to replace any air expelled by kitchen or bathroom fans as well as water heater chimneys or fans Failure to provide outside air to the area in which the furnace is...

Page 15: ...verload your furnace with wood Failure or damage to the firebox could result Never allow the hot coals to build up above the lower firebricks BEST WOOD TO BURN All solid fuel whether it is coal pine o...

Page 16: ...ople and is recommended for use in this furnace Anthracite coal is hard and burns like the charcoal that is used in your barbecue grill The coals must touch each other to ignite Therefore the smaller...

Page 17: ...e ash pan on a daily basis and should never be allowed to accumulate high enough to come in contact with the grates Such a condition could cut off necessary air circulation and could also result in a...

Page 18: ...R CONDITIONING See air circulating fan performance curve charts on page 21 Service factors for factory furnished motors are 1 3 HP 1 35 1 2 HP 1 25 3 4 HP 1 15 All motors are Class A with Class B insu...

Page 19: ...ainer until all cinders have thoroughly cooled CLEANING THE CHIMNEY SMOKE PIPE AND HEAT EXCHANGER Avoid chimney fires On a regular schedule check for creosote and soot buildup in the chimney smoke pip...

Page 20: ...ht Check for obstruction such as loose mortar bird nests and squirrel nests Clean chimney to eliminate obstructions Check for obstructions in combustion air inlet See page 14 Too cold a chimney will c...

Page 21: ...21...

Page 22: ...22 9 10100700 10100700 lower upper...

Page 23: ...23...

Page 24: ...24 T 8000...

Page 25: ...______________________________________________________________ _____________________________________________________________________________________ Notes _____________________________________________...

Page 26: ...26...

Page 27: ...27...

Page 28: ...TRACTOR ONLINE AT OUR WEBSITE OR FROM OUR FACTORY PHONE 1 800 358 0060 FAX 1 800 440 1994 E MAIL yukon mlecmn net WEBSITE www yukon eagle com Alpha American Co 10 Industrial Blvd Palisade MN 56469 www...

Reviews: