background image

13

Warning

Return air MUST NOT be drawn from inside the room where 
the furnace is located.

furnace located in confined sPace

When the furnace is in a utility room, install two open grilles in a 
wall or door opening to the rest of the house. One grille will supply 
combustion air. Locate it near the floor. The other grille is for ven-
tilation. Locate it close to the ceiling. Each grille must have a free 
area of not less than one square inch for each 1000 BTU/hr. of the 
total input rating of all the appliances in the confined space. (See
Fig. 16 below)

FOR EXAMPLE: Your furnace is rated at 150,000 BTU per hour. 
The  water  heater  is  rated  30,000  BTU  per  hour.  The  total  is 
180,000 BTU per hour.

You need two grilles, each with 180 square inches of free opening.
Metal grilles have about 60% free (open) area, so you need two 
metal grilles with 300 square inches each of louvered area. The 
height should be about half the width.

fresh air duct caPacities

Fresh air duct capacities for duct supplying fresh air.

btu Per hour input*

 

 

1/4 in. Mesh 

Wood 

Metal  

 

 

Screen 

Louvers 

Louvers 

 

Size 

BTU 

BTU 

BTU 

  3-1/4 x 12 in. 

144,000 

36,000 

108,000 

 

8 in. round 

200,000 

50,000 

150,000 

 

8 x 12 in. 

382,000 

96,000 

288,000

 

8 x 16 in. 

512,000 

128,000 

384,000

* Based on opening covered by 1/4 inch mesh screen, wood or metal louvers.

Warning

Enough air insures proper combustion and assures that no haz-

ard will develop due to the lack of oxygen.

note

If you have a fireplace, a kitchen, bath fan or water heater that 
vents  to  the  outside,  add  enough  duct  size  to  your  fresh  air 
requirements to accommodate their air needs.

Summary of Contents for Klondike Eagle IV

Page 1: ...pliance Alpha American Co 10 Industrial Blvd Palisade MN 56469 www yukon eagle com YUKON EAGLE OWNER S MANUAL Assembly Installation Operation Repair Parts Model No LW 000 Series CAUTION Read Rules And...

Page 2: ...d during operation Do not operate with flue draft exceeding 03 W C Do not store flammable materials within marked installa tion clearances Frequently inspect and clean heat exchanger smoke pipe and ch...

Page 3: ...8 Duct Work and Blower Speed Adjustment 18 Testing Installations for Efficiency 18 Test Procedure 10 MAINTENANCE Cleaning the Chimney Smoke Pipe and Heat Exchanger 19 In Case of Chimney Fire 19 Servic...

Page 4: ...lt in failure of heat exchanger and cause dangerous operation 4 You must have a sufficient supply of combustion air to the area in which the furnace is located page 4 5 Factory Built Chimneys Connect...

Page 5: ...should occur be sure ash door and firedoor are closed Turn thermostat down to close primary air damper In the event of an electrical power failure be sure ash door and fire door remain closed In the...

Page 6: ...eat with second baffle making sure baffles interlock as shown in Fig 6 When properly installed baffles will not move more than 1 4 in any direction Failure to have baffles properly installed will seve...

Page 7: ...pre selected location making sure it is level Proceed as follows Before Installing check DRAW COLLAR Attach the draw collar around the smoke pipe and tight against the furnace cabinet so room air cann...

Page 8: ...r and place the 4 square box the furnished wiring harness over cable connector and replace the lock nut Secure the square box to the furnace with two sheet metal screws Connect the 34 long conduit to...

Page 9: ......

Page 10: ...ent outward into the collar and thus make a better joint WHEN FINISHED THE OPENING INTO THE FLUE MUST BE EQUAL IN SIZE TO THE COLLAR OF THE DRAFT CONTROL If flue pipe is made of material too heavy to...

Page 11: ...stible wall is allowed if the space is insulated according to NFPA 90B table 6 5 1 2 DO NOT CONNECT THIS FURNACE TO A CHIMNEY SERVING ANOTHER APPLIANCE The chimney should be no less than 8 inches insi...

Page 12: ...r chimney must terminate at least 2 feet above the peak of the roof Adding more chimney height sometimes cures the problem See Fig 12 page 14 5 Home located on side of hill When the wind blows over a...

Page 13: ...You need two grilles each with 180 square inches of free opening Metal grilles have about 60 free open area so you need two metal grilles with 300 square inches each of louvered area The height should...

Page 14: ...chim ney Outside air is also needed to replace any air expelled by kitchen or bathroom fans as well as water heater chimneys or fans Failure to provide outside air to the area in which the furnace is...

Page 15: ...verload your furnace with wood Failure or damage to the firebox could result Never allow the hot coals to build up above the lower firebricks BEST WOOD TO BURN All solid fuel whether it is coal pine o...

Page 16: ...ople and is recommended for use in this furnace Anthracite coal is hard and burns like the charcoal that is used in your barbecue grill The coals must touch each other to ignite Therefore the smaller...

Page 17: ...e ash pan on a daily basis and should never be allowed to accumulate high enough to come in contact with the grates Such a condition could cut off necessary air circulation and could also result in a...

Page 18: ...R CONDITIONING See air circulating fan performance curve charts on page 21 Service factors for factory furnished motors are 1 3 HP 1 35 1 2 HP 1 25 3 4 HP 1 15 All motors are Class A with Class B insu...

Page 19: ...ainer until all cinders have thoroughly cooled CLEANING THE CHIMNEY SMOKE PIPE AND HEAT EXCHANGER Avoid chimney fires On a regular schedule check for creosote and soot buildup in the chimney smoke pip...

Page 20: ...ht Check for obstruction such as loose mortar bird nests and squirrel nests Clean chimney to eliminate obstructions Check for obstructions in combustion air inlet See page 14 Too cold a chimney will c...

Page 21: ...21...

Page 22: ...22 9 10100700 10100700 lower upper...

Page 23: ...23...

Page 24: ...24 T 8000...

Page 25: ...______________________________________________________________ _____________________________________________________________________________________ Notes _____________________________________________...

Page 26: ...26...

Page 27: ...27...

Page 28: ...TRACTOR ONLINE AT OUR WEBSITE OR FROM OUR FACTORY PHONE 1 800 358 0060 FAX 1 800 440 1994 E MAIL yukon mlecmn net WEBSITE www yukon eagle com Alpha American Co 10 Industrial Blvd Palisade MN 56469 www...

Reviews: