4.2.2 If the lower display window alternately display “HIAL”, “LoAL”, “HdAL” or “LdAL”, it means high limit
alarm, low limit alarm, deviation high alarm, and deviation low alarm occurs. The alarm display can also be
turned off by setting parameter “cF”.
4.2.3. For program type instruments AI-518P, run is for common status. the lower display may alternately
display between SV and “StoP”, “HoLd”, or “rdy” which means the program control is stop, pause and ready.
There are 10 indication lights on the front pannel:
“PRG” on indicates program control status, flashing means that the program is in that status of hold or ready,
and off means the program stops.
Light “MAN” on means manual output status, and off means auto control status.
MIO, OP1, OP2, AL1, AL2, AU1 and AU2 respectiviely indicate I/O operation of the corresponding module.
For example, That the COMM indicator is lighting means that the instrument is communicating with
computer.
When current module X or X4 is installed on OUTP socket, the brightness of OP1 and OP2 indicates the
magnitude of the current. When K5 single phase shifting module is installed on OUTP sockets, OP2 on
indicates that the external power is on, and the brightness of OP1 shows the magnitude of phase-shifting
trigger output.
4.2 Operation Description
4.2.1 Display status switch
Depending on the instrument model, press
key can switch between different display status.
AI-518P can switch between 1,2,3while AI-518P can only in 1 ,no need switch.
4.2.2 Set Value Setting
In basic display status, if the parameter lock “Loc” isn't locked, we can set setpoint (SV) by pressing
、
or
. Press
key to decrease the value,
key to increase the value, and
key to
move to the digit expected to modify. Keep pressing
or
, the speed of decreasing or inscreasing
value gets quick.
4.2.3 Parameter Setting
In basic display status, press
and hold for about 2 seconds can access Field Parameter Table.
Pressing
can go to the next parameter; pressing
、
or
can modify a parameter. Press
and hold
can return to the preceding parameter. Press
(don't release) and then press
key
simultaneously can escape from the parameter table. The instrument will escape auomatically from the
parameter table if no key is pressed within 25 seconds, and the change of the last parameter will not be
saved. In Field Parameter Table, press
till the last field parameter “Loc” appears. Setting Loc=808
and then press
can access System Parameter Table.Please refer to the table,specially Loc