Safe carrying capacity of rubber or plastic insulated wire(1)

specification

mm

nominal cross

section

mm2

Safe carrying capacity

A

BX

BLX

BV

BLV

1*1.13

1

20

18

1*1.37

1.5

25

22

1*1.76

2.5

33

25

30

23

1*2.24

4

42

33

40

30

1*2.73

6

55

42

50

40

7*1.33

10

80

55

75

55

7*1.76

16

105

80

100

75

7*2.12

25

140

105

130

100

7*2.50

35

170

140

160

125

19*1.83

50

225

170

205

150

19*2.14

75

280

225

255

185

19*2.50

95

340

280

320

240

Note

BX(BLX

copper

aluminum

core rubber insulated wire or BV(BLV

copper

aluminum

core PVC plastic insulated wire

widely used in 500V or less than 500V AC and DC power

distribution system. The temperature for the data listed in the above table is 35

the safe

carrying capacity value for the wire on single coved.

Summary of Contents for DDS-1Y

Page 1: ......

Page 2: ...2kg and 76mm Width 2 2 2 2 Technical Technical Technical Technical Parameters Parameters Parameters Parameters Voltage 230V Current 10 100 A Accuracy class 1 0 Standard IEC62052 11 IEC62053 21 Frequency 50 60Hz Impulse constant 1600imp kWh Display Counter 5 1 Power consumption 8VA 0 4W Starting current 0 004Ib Working Temperature 25 70 Storage Temperature 40 80 Average humidity value of year 75 Ma...

Page 3: ...y flame resistant ABS Base Bottom Grey flame resistant ABS 4 4 4 4 Connection Connection Connection Connection Diagram Diagram Diagram Diagram 5 5 5 5 Meter Meter Meter Meter Dimensions Dimensions Dimensions Dimensions 76mm 100 mm 6 mm 5 4 5mm 36 m m Height 100mm Width 76mm Depth 65mm Weight 0 3092kg Net ...

Page 4: ...ation Installation Instruction Instruction Instruction Instruction Choose 35mm standard Din Rail the length is confirmed by yourself fixed them in the location which are waiting for installation Put the meter into the upper Din Rail then push down the clip in the meter bottom see Fig 1 After the bottom of the meter install into the Din Rail successfully release the clip to make sure the meter have...

Page 5: ...2 2 Fig Fig Fig Fig 3 3 3 3 Fig 4 is after installation Fig Fig Fig Fig 4 4 4 4 Fig Fig Fig Fig 5 5 5 5 Making the connection according to the wiring diagram After connection use lead sealing to seal terminal cover see Fig 5 ...

Page 6: ...25 30 23 1 2 24 4 42 33 40 30 1 2 73 6 55 42 50 40 7 1 33 10 80 55 75 55 7 1 76 16 105 80 100 75 7 2 12 25 140 105 130 100 7 2 50 35 170 140 160 125 19 1 83 50 225 170 205 150 19 2 14 75 280 225 255 185 19 2 50 95 340 280 320 240 Note BX BLX copper aluminum core rubber insulated wire or BV BLV copper aluminum core PVC plastic insulated wire widely used in 500V or less than 500V AC and DC power dis...

Page 7: ...el personnel personnel personnel Installation and operation of this equipment described in this manual may only be performed by qualified personal Only people that are authorized to install connect and use this equipment and have the proper knowledge about labeling and grounding electrical equipment and circuits and can do so according to safety and regulatory standards are considered qualified pe...

Page 8: ...ke sure the integrity of the unit If in doubt don t use the equipment and contact technical staff Mounting of electric appliances must be carried out only by skilled electricians It is imperative to observe the generally applicable safety measures In case of failure and or malfunctioning of the device turn off it For any repair only contact technical staff Failure to comply with the above may comp...

Reviews: