Smart Positioner
YT-1000 / 1050 series
Product Manual
Ver. 1.04
41
5. Connection - Air
5.1
Safety
Supply pressure should be clean and dry air
– avoiding moisture, oil or dust.
Always recommended to use air filter regulator (i.e. YT-200 series).
Young Tech Co., Ltd
has not tested positioner’s operation with any other gases
other than clean air. Please contact Young Tech Co., Ltd for any questions.
5.2
Supply Pressure Condition
Dry air with at least 10
℃
lower than ambient temperature.
Avoid from dusty air. Use 5 micron or smaller filter.
Avoid oil.
Comply with ISO 8573-1 or ISA 7.0.01.
Supply pressure range is 0.14 ~0.7 MPa (1.4 ~ 7 bar)
Set air filter regulator’s pressure level 10% higher than actuator’s spring range pressure.
5.3
Piping Condition
Ensure inside of pipe is clean of obstructions.
Do not use pipeline that is squeezed or shows any type of damamges.
Pipeline should have more than 6mm of inner diameter (10mm outer diameter) to
maintain flow rate.
The length of pipeline system should not be extremely long. Longer pipeline system
may affect flow rate due to the friction inside of the pipeline.