SMART POSITIONER
TMP-3000
PRODUCT MANUAL
Ver. 1.03
26
6.7.1
Input Signal Selection (SEL IN)
The input signal should be 0 ~ 20/4 ~ 20mA or 0 ~ 5 / 10V and the input signal must
be selected after wiring according to the desired input signal. Input signal range
according to input signal setting value is as follows.
Parameter Value
Input Signal
0
4 ~ 20mA
1
0 ~ 20mA
2
0 ~ 10V
3
0 ~ 5V
6.7.2
Zero-Point (PV_ZERO) and End-Point (PV_END)
PV_ZERO mode is the mode to change the zero point of the valve, and PV_END is the
mode to change the end point.
6.7.3
Zero-Point (TR_ZERO) and End-Point (TR_END)
TR_ZERO is the zero point of the feedback output signal, and TR_END is the mode in
which the end point can be changed. It is used when the feedback output signal is not
the same as the actual valve opening or when the output signal is unstable and needs to
be readjusted. Equipment such as an ammeter to see the feedback signal is required, and
the wiring should be connected as shown in the table of contents 5.2 Connection of
terminals.
<ENTER>
6 sec.
<DOWN>
3 times
<ENTER>
<DOWN>
1 time
<ENTER>
<UP>/<DOWN>
<ENTER>
Zero Point Adjust
<ESC>
<DOWN>
<ENTER>
End Point Adjust
<UP>/<DOWN>
<ENTER>
<ENTER>