6
Low
pressure
High pressure
Low pressure
High pressure
Description
Correct
Incorrect
Install the product below a
device which generates
condensate.
Install the products for each
device independently.
The diameter of collecting pipe
shall be more than summation
of sectional areas of discharge
pipes.
In addition, install check valves
for back flow prevention.
For condensate recovery,
connect the discharge pipe to
the upper part of collecting
pipe.
For traps of different pressure
lines, install collecting pipes
individually for each pressure.
In addition, install check valves
for back flow prevention.
* Re-evaporated steam in high
pressure line increases the back
pressure of low pressure trap.