7. Maintenance 

 

7.1 Troubleshooting 

 

 

OB-30, OB-30U

 

Trouble 

Cause 

Remedy 

Temperature does 
not rise. 

1.  Inadequate adjustment. 

1.  Readjust according to “8.2 

Adjustment” on page 8. 

2.  Insufficient drainage from the trap 

of heat exchanger, etc. 

2.  Check the trap and replace it if 

necessary. 

Temperature rises 
excessively. 

1.  Inadequate adjustment. 

1.  Readjust according to “8.2 

Adjustment” on page 8. 

2.  Foreign substances stuck or 

damage on the disc [3] and valve 
seat [5]. 

2.  Remove the foreign substances. If 

there is damage on the parts, please 
contact us to disassemble the product 
and replace the parts. 

3.  The thermal bulb [20] or bellows 

[14] is damaged. 

3.  Replace the sensor. 

Large error of 
temperature 
control. 

1.  The thermal bulb [20] and 

thermometer are installed in wrong 
positions. 

1.  Reinstall them at points where the 

circulation is best. 

2.  Inlet pressure is too high. 

2.  When steam consumption is small, 

lower the inlet pressure for better 
temperature control. 

Outside leakage. 
 

1.  Leakage from the gasket [16]. 

1.  Please contact us to retighten the 

gasket, or disassemble the product to 
replace the part. 

2.  Balance bellows [6] is damaged. 

2.  Please contact us to disassemble the 

product and replace the part. 

 

 OB-31, OB-31U

 

Trouble 

Cause 

Remedy 

Temperature does 
not lower. 

1. Inadequate adjustment. 

1.  Readjust according to “8.2 

Adjustment” on page 8. 

2. The thermal bulb [20] or bellows 

[14] is damaged. 

2.   Replace the sensor. 

Temperature lowers 
excessively. 

1. Inadequate adjustment. 

1.  Readjust according to “8.2 

Adjustment” on page 8. 

2. Foreign substances stuck or 

damage on the disc [3] and valve 
seat [5]. 

2.  Remove the foreign substances. If 

there is damage on the parts, please 
contact us to disassemble the product 
and replace the parts. 

Large error of 
temperature 
control. 

1. The thermal bulb [20] and 

thermometer are installed in wrong 
positions. 

1. Reinstall them at points where the 

circulation is best. 

2. Inlet pressure is too high. 

2. When steam consumption is small, 

lower the inlet pressure for better 
temperature control. 

Outside leakage. 

 

1. Leakage from the gasket [16]. 

1. Please contact us to retighten the 

gasket, or disassemble the product to 
replace the part. 

2. Balance bellows [6] is damaged. 

2. Please contact us to disassemble the 

product and replace the part. 

 

 

Summary of Contents for OB-30

Page 1: ...d result in death or serious injury Caution This symbol indicates a hazardous situation that if not avoided may result in minor or moderate injury or may result in only property damage Table of Conten...

Page 2: ...Pa Material Thermal bulb Copper pipe Nickel chrome plated Capillary tube Copper Flexible tube Stainless steel Standard capillary length 2 m Connection JIS R1 2 screwed Available with thermal well stai...

Page 3: ...Nominal Size d L Weight kg Capillary length Weight 15A Rc 1 2 75 2 1 2 m 0 6 kg 20A Rc 3 4 80 2 2 25A Rc 1 90 2 4 OB 30U OB 31U OB 30U OB 31U Body mm Sensor Nominal Size d L Weight kg Capillary lengt...

Page 4: ...lve When the temperature of the bulb lowers the downward force applied to the spindle by the spring 11 opens the valve The set temperature can be adjusted by turning the handle 12 to change the load o...

Page 5: ...orce to the spindle 7 to open the valve When the temperature of the bulb lowers the downward force applied to the spindle by the spring 11 closes the valve The set temperature can be adjusted by turni...

Page 6: ...P2 and steam flow rate are 0 2 MPa 0 15 MPa and 20 kg h respectively first find intersection point a of the inlet pressure of 0 2 MPa and the outlet pressure of 0 15 MPa Trace down vertically from th...

Page 7: ...re and flow rate are 0 3 MPa 0 15 MPa and 1 m3 h respectively first find intersection point a of the differential pressure P of 0 15 MPa 0 3 MPa 0 15 MPa before and after the valve and the flow rate o...

Page 8: ...Failure to follow this notice hampers correct temperature regulation 11 Do not apply excessive load torque or vibration to the product Failure to follow this notice may result in malfunction or a dra...

Page 9: ...lve Capillary tube 5 4 Assembly of body and sensor Place the bellows follower 13 which is packaged with the body into the bellows 14 with its flat surface facing downward and then screw it into the lo...

Page 10: ...r hammer and can heavily damage the main parts of the product Be sure to follow the procedure below 1 Close the stop valves at the inlet and outlet sides of the product Open the bypass stop valve and...

Page 11: ...t us to retighten the gasket or disassemble the product to replace the part 2 Balance bellows 6 is damaged 2 Please contact us to disassemble the product and replace the part OB 31 OB 31U Trouble Caus...

Page 12: ...hock to the thermal bulb Warning Inspection must be done by experienced professional or valve manufacturer Completely discharge the pressure inside of the product piping and equipment prior to disasse...

Page 13: ...improvement without any prior notice After the discontinuation of the product Yoshitake supplies the repair parts for 5 years otherwise individually agreed 3 This warranty does not cover the damage d...

Reviews: