background image

5121835-TIM-J-1118

Johnson Controls Ducted Systems

51

Economizer with power exhaust

A unit equipped with an economizer (single or dual enthalpy) 
and a power exhaust operates as specified above with one 
addition. The power exhaust motor is energized 45 seconds 
after the actuator position exceeds the exhaust fan setpoint on 
the economizer control. As always, the R to G connection 
provides minimum position but does not provide power exhaust 
operation.

Motorized outdoor air dampers

This system operation is the same as the units with no outdoor 
air options with one exception. When the R to G circuit is 
complete, the motorized damper drives open to a position set 
by the thumbwheel on the damper motor. When the R to G 
circuit is opened, the damper spring returns fully closed.

Cooling operation errors

Each cooling system is monitored for operation outside of the
intended parameters. Errors are handled as described below. All
system errors override minimum run times for compressors.

NOTE: 

The following components are needed to access the 
control points in the Smart Equipment™ control. 

1.

Local LCD on the unit control board.

OR

2.

Mobile Access Portal (MAP) Gateway (Portable).

• Source 1 P/N S1-JC-MAP1810-OP
• MAP Gateway Quick Start Guide P/N 24-10737-16
• MAP Gateway Instruction P/N 24-10737-8

High-pressure limit switch

During cooling operation, if a high-pressure limit switch opens, 
the UCB de-energizes the associated compressor, initiates the 
ASCD (Anti-short cycle delay), and, if the other compressor is 
idle, stops the condenser fans. If the call for cooling is still 
present at the conclusion of the ASCD, the UCB re-energizes 
the halted compressor.

If a high-pressure switch opens three times within two hours of 
operation, the UCB locks out the associated compressor. If the 
other compressor is inactive, the condenser fans is de-
energized.

Low-pressure limit switch

The low-pressure limit switch is not monitored during the initial 
30 seconds of a cooling system's operation. For the following 
30 seconds, the UCB monitors the low-pressure switch to 
ensure it closes. If the low-pressure switch fails to close after 
the 30-second monitoring phase, the UCB de-energizes the 
associated compressor, initiates the ASCD, and, if the other 
compressor is idle, stops the condenser fans.

When the low-pressure switch is proven (closed during the 30-
second monitor period described above), the UCB monitors the 
low-pressure limit switch for any openings. If the low-pressure 
switch opens for greater than 5 seconds, the UCB de-energizes 

the associated compressor, initiates the ASCD, and, if the other 
compressor is idle, stops the condenser fans.

If the call for cooling is still present at the conclusion of the 
ASCD, the UCB re-energizes the halted compressor.

If a low-pressure switch opens three times within one hour of 
operation, the UCB locks out the associated compressor. If the 
other compressor is inactive, the condenser fans are de-
energized.

Evaporator low limit 

During cooling operation, if the 

Evaporator Low Limit Sensor 

(EC1, 2)

 (Located on the Suction Line at the Evaporator Coil.) 

detects a temperature below 26°F (default), the UCB de-
energizes the associated compressor, initiate the ASCD, and, if 
the other compressor is idle, stops the condenser fans. If the 
call for cooling is still present at the conclusion of the ASCD, the 
UCB re-energizes the halted compressor. If the UCB detects 
the evaporator low limit sensor 

(EC1, 2)

 falling below 26ºF 

(default) three times within two hours of operation, the UCB 
locks out the associated compressor. If the other compressor is 
inactive, the condenser fans are de-energized.

Low ambient cooling

To determine when to operate in low ambient mode, the UCB 
has an 

Outdoor Air Temperature Sensor (OAT)

 with a low 

ambient setpoint at 45ºF (default). When the 

OAT Sensor

 

senses a temperature below the low ambient setpoint and the 
thermostat is calling for cooling, the UCB operates in the low 
ambient mode.

Low ambient mode operates the compressors in this manner: 
10 minutes on, 5 minutes off. The indoor blower is operated 
throughout the cycle. The 5-minute off period is necessary to 
defrost the indoor coil.

Low ambient mode always begins with compressor operation. 
Compressor minimum run time may extend the minutes of 
compressor operation. The off cycle will begin immediately 
following the elapse of the minimum run time.

When operating in low ambient mode, an evaporator low limit 
sensor

 (EC1, 2)

 temperature below 26ºF de-energizes the 

associated compressor. If the call for cooling is still present at 
the end of the ASCD and the and the evaporator temperature 
sensor 

(EC1, 2)

 temperature is above 26°F, the unit resumes 

operation.

Safety controls

The unit control board monitors the following inputs for each 
cooling system:

1.

An evaporator low limit sensor 

(EC1, 2) 

(Located on the 

Suction Line at the Evaporator Coil.) to protect against low 
evaporator temperatures due to a low airflow or a low 
return air temperature, set at 26°F.

2.

A high-pressure switch to protect against excessive 
discharge pressures due to a blocked condenser coil or a 
condenser motor failure, (opens at 625 ± 25 psig).

Summary of Contents for ZKT06

Page 1: ...ide duct application 42 20 Airflow performance bottom duct application 44 21 RPM selection 45 22 Indoor blower specifications 46 23 Power exhaust specifications 46 24 Motor sheave datum diameters 48 2...

Page 2: ...precautions and codes including ANSI Z223 1 or CSA B149 1 latest edition Wear safety glasses and work gloves Use quenching cloth and have a fire extinguisher available during brazing operations Impro...

Page 3: ...nd may be installed directly on combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials For use with natural gas The unit can be converted to LP with...

Page 4: ...hrowaway Filters 2 2 Pleated Filters Merv 8 3 2 Cleanable Filters 4 4 Pleated Filters Merv 13 A None C BACnet MSTP Modbus N2 COM Card F Fault Detection and Diagnostics FDD E Verasys Single Zone G Vera...

Page 5: ...ure 1 Unit shipping bracket 2 Turn each bracket toward the ground The protective plywood covering drops to the ground 3 Remove the condenser coil protective covering 4 Remove the toolless doorknobs an...

Page 6: ...ate If components are added to a unit to meet local codes they are installed at the dealer s and or customer s expense The size of the unit for the proposed installation must be based on a heat loss h...

Page 7: ...Filter access 2 in or 4 in filter options O Compressor 1 access high efficiency compressor E Filter drier solid core P Side entry power and control knockouts F Micro channel aluminum tube aluminum fin...

Page 8: ...nd proper unit operation Rigging and handling Exercise care when you move the unit Do not remove any packaging until the unit is near the place of installation To rig the unit attach chain or cable sl...

Page 9: ...g cables so that it lifts evenly All panels must be secured in place when the unit is lifted The condenser coils must be protected from rigging cable damage with plywood or other suitable material D A...

Page 10: ...t2 110 110 1 Weight given is for the maximum heater size available 54KW 2 Weight given is for the maximum number of tube heat exchangers available 8 tube LEFT A 59 00 C D E F 4 19 27 31 89 00 21 19 11...

Page 11: ...3 16 5 1 4 Base Pan 17 13 16 View of Wall Across from Coil Gas Pipe Inlet 5 3 8 Table 6 ZKT06 through T12 unit clearances Direction Distance in Direction Distance in Top1 1 Units must be installed out...

Page 12: ...Figure 12 ZKT06 through T10 unit side duct openings Item Description A Disconnect switch cover B Power entry 2 1 2 C Control entry 7 8 D Power entry 2 1 2 E Convenience outlet cover F Convenience out...

Page 13: ...Unit model number Dimension in A B C D ZKT06 27 3 4 12 1 16 27 1 2 16 ZKT07 27 3 4 12 1 16 27 1 2 16 ZKT08 28 1 4 18 1 16 28 1 4 18 1 4 ZKT10 28 1 4 18 1 16 28 1 4 18 1 4 ZKT12 28 1 4 18 1 16 28 1 4 1...

Page 14: ...of curb 8 or 14 50 1 2 30 20 20 80 5 8 6 A B E G D F C Roof curb components Item Description A Return air B Supply air C Right side of the unit D Front side of the unit E 2 typ F Insulated deck under...

Page 15: ...he following steps 1 Remove the side duct covers 2 Orient the supply panel with the painted surface up 3 Slide the supply panel between the heat exchanger and the unit bottom The painted surface must...

Page 16: ...ere POE polyolester compressor lubricants are known to cause long term damage to some synthetic roofing materials Procedures that risk oil leakage include but are not limited to the following Compress...

Page 17: ...of a disconnect on the unit Confirm compliance with local code before you install a disconnect on the unit Electrical line must be sized properly to carry the load Note Use copper conductors only Each...

Page 18: ...g unit with or without electric heat Figure 23 Typical field wiring disconnect cooling unit with gas heat THREE PHASE POWER SUPPLY FACTORY OR FIELD SUPPLIED DISCONNECT GROUND LUG TERMINAL BLOCK TB1 L1...

Page 19: ...ostat to indicate the Occupied on X is an input to the thermostat to display Error Status condi ons 3 W2 Y1 G OCC Y2 X R SD 24 C W1 24V COM OUT Return or Space Humidity Sensor 0 10VDC TB4 3 823 R RAH...

Page 20: ...50 E09 6 8 1 18 9 38 9 44 4 50 50 E18 13 5 2 37 5 53 3 60 2 60 70 E24 18 0 2 50 0 69 0 75 8 70 80 E36 25 5 2 70 8 95 0 101 9 100 110 230 13 1 83 1 20 5 2 1 5 2 5 5 0 0 None 38 9 44 4 50 50 E09 9 0 1...

Page 21: ...90 90 E24 18 0 2 50 0 74 5 81 3 90 90 E36 25 5 2 70 8 100 5 107 4 110 110 E54 40 6 2 112 7 152 9 159 7 175 175 230 22 4 149 0 35 0 2 1 9 6 5 5 0 0 None 68 4 73 9 90 90 E18 18 0 2 43 3 68 4 73 9 90 90...

Page 22: ...18 9 43 3 48 8 50 60 E18 13 5 2 37 5 58 8 65 7 60 70 E24 18 0 2 50 0 74 5 81 3 80 90 E36 25 5 2 70 8 100 5 107 4 110 110 230 13 1 83 1 20 5 2 1 9 6 5 5 0 0 None 43 3 48 8 50 60 E09 9 0 1 21 7 43 3 48...

Page 23: ...0 100 E24 18 0 2 50 0 80 0 86 8 90 100 E36 25 5 2 70 8 106 0 112 9 110 125 E54 40 6 2 112 7 158 4 165 2 175 175 230 22 4 149 0 35 0 2 1 14 0 5 5 0 0 None 72 8 78 3 90 100 E18 18 0 2 43 3 72 8 78 5 90...

Page 24: ...9 48 9 54 4 60 60 E18 13 5 2 37 5 65 8 72 7 70 80 E24 18 0 2 50 0 81 5 88 3 90 90 E36 25 5 2 70 8 107 5 114 4 110 125 230 13 1 83 1 20 5 2 1 5 2 5 5 10 0 None 48 9 54 4 60 60 E09 9 0 1 21 7 48 9 54 4...

Page 25: ...9 100 100 E24 18 0 2 50 0 87 0 93 8 100 100 E36 25 5 2 70 8 113 0 119 9 125 125 E54 40 6 2 112 7 165 4 172 2 175 175 230 22 4 149 0 35 0 2 1 9 6 5 5 10 0 None 78 4 83 9 100 100 E18 18 0 2 43 3 78 6 85...

Page 26: ...8 9 53 3 58 8 60 70 E18 13 5 2 37 5 71 3 78 2 80 80 E24 18 0 2 50 0 87 0 93 8 90 100 E36 25 5 2 70 8 113 0 119 9 125 125 230 13 1 83 1 20 5 2 1 9 6 5 5 10 0 None 53 3 58 8 60 70 E09 9 0 1 21 7 53 3 58...

Page 27: ...100 110 E24 18 0 2 50 0 92 5 99 3 100 110 E36 25 5 2 70 8 118 5 125 4 125 150 E54 40 6 2 112 7 170 9 177 7 175 200 230 22 4 149 0 35 0 2 1 14 0 5 5 10 0 None 82 8 88 3 100 110 E18 18 0 2 43 3 84 1 91...

Page 28: ...44 192 AFUE Steady state efficiency 80 80 80 80 80 80 80 80 80 80 No burners 4 6 4 6 4 6 6 8 6 8 No stages 24 24 24 24 24 24 24 24 24 24 Temperature rise range F 20 50 35 65 15 45 30 60 10 40 25 55 20...

Page 29: ...er sheave AK74 AK64 AK74 AK61 AK89 AK74 AK84 AK74 AK74 BK77 Belt A49 A49 A49 A49 A56 A54 A56 A54 A54 BX55 Motor HP each 1 1 2 2 1 1 2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 172...

Page 30: ...uperseded by local codes or gas utility requirements See Table 14 Gas pipe sizing capacity of pipe on page 31 The heating value of the gas may vary by locality You must check the value with the local...

Page 31: ...d scale Hammer on the outside of the pipe and blow out loose particles Before initial start up make sure that all gas lines external to the unit are purged of air The gas supply must be a separate lin...

Page 32: ...compartment with the heating elements extending into the supply air chamber All electric heaters are fused and intended for use with single point power supply Motorized outdoor damper The motorized ou...

Page 33: ...nts should be set to the same value Free cooling Four types of free cooling options are available dry bulb changeover single enthalpy dual enthalpy changeover and Auto Dry bulb changeover For dry bulb...

Page 34: ...f cooling If the economizer output goes to minimum position and the SAT is less than Economizer setpoint 1 F the control starts a 12 minute timer to de energize a compressor output If at any time the...

Page 35: ...cts through circuit trace to 24V IN pin HOT C COM Mixed air temperature sensor input from 10K 77 F Type III negative temperature coefficient thermistor The MAT parameter reports input status F C 3 65...

Page 36: ...tation sensor MOA Range parameter sets the cubic feet per minute liters per second measured by the air monitoring station sensor when it outputs 10 VDC Fr Air parameter reports input status 0 50000CFM...

Page 37: ...o the 4 stage board and or fault detection diagnostics board 1 When wiring the unit and other devices using the SA Bus and FC Bus see Table 32 Smart Equipment economizer board analog outputs Location...

Page 38: ...economizer actuator Connects through circuit trace to 24V IN pin COM EX FAN 24 VAC hot output to energize power exhaust fan contactor coil VFD enable relay coil ExFan parameter reports output status O...

Page 39: ...elt nuts Figure 28 Belt adjustment CFM static pressure and power altitude and temperature corrections Use the information below to assist in the application of the product at altitudes at or exceeding...

Page 40: ...is assumed The 1 5 in static pressure given is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80...

Page 41: ...95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will ach...

Page 42: ...94 1 43 1147 1 56 1201 1 67 1254 1 78 1309 1 90 1366 2 02 2600 902 0 97 962 1 16 1020 1 33 1076 1 47 1130 1 61 1183 1 73 1237 1 85 1291 1 96 1346 2 07 1402 2 19 2800 941 1 16 1002 1 35 1059 1 52 1115...

Page 43: ...1 1 Blower performance includes gas heat exchangers and 2 in filters See the static resistance table for additional applications 2 See the RPM selection table to determine the required motor sheave se...

Page 44: ...1347 1 84 1424 1 98 1503 2 14 1586 2 31 2600 957 1 10 1030 1 30 1102 1 47 1174 1 62 1246 1 76 1320 1 89 1394 2 03 1471 2 17 1551 2 33 1634 2 51 2800 1009 1 32 1082 1 51 1154 1 69 1225 1 84 1298 1 98...

Page 45: ...HP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 3 HP and field supplied drive Standard 3 HP and drive High static 5 HP and drive 3200 837 1 44 889 1 57 940 1 69 989 1 81 1036 1 93 1...

Page 46: ...r 10 12 hours run time Method two 1 Drill two 5 16 inch holes one in the return air duct as close to the inlet of the unit as possible and another in the supply air duct as close to the outlet of the...

Page 47: ...are presented for side and bottom duct configuration 6 Determine the unit measured CFM from the blower performance table external static pressure and the number of turns the variable motor sheave is o...

Page 48: ...review the installation for any installation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in stat...

Page 49: ...0 17 0 18 0 21 0 22 0 26 3900 0 09 0 29 0 23 0 19 0 20 0 23 0 24 0 28 4100 0 09 0 31 0 24 0 21 0 22 0 25 0 26 0 31 4300 0 10 0 30 0 25 0 23 0 24 0 28 0 29 0 34 4500 0 11 0 35 0 26 0 25 0 26 0 30 0 31...

Page 50: ...ressor 1 is energized If compressor 1 is active for first stage cooling or the first compressor is locked out compressor 2 is energized In free cooling mode if the call for the second stage of cooling...

Page 51: ...ressure switch opens for greater than 5 seconds the UCB de energizes the associated compressor initiates the ASCD and if the other compressor is idle stops the condenser fans If the call for cooling i...

Page 52: ...n within the Smart Equipment Controller menu Those modes consist of a Normal Alternate and Aux each mode is described below Normal cooling mode When there is a call for first stage cooling with or wit...

Page 53: ...is a call for cooling and the economizer is operating as first stage of cooling All safety devices function as previously described Optional Aux mode The Aux mode available with hot gas reheat units i...

Page 54: ...ce Reducing the value below the correct setpoint gives shorter ON cycles and may result in the lowering of the temperature within the conditioned space See Table 28 for the required electric heat anti...

Page 55: ...Flame sense Flame sensing occurs at all times If W1 is not present and a flame is sensed for 2 seconds the draft motor is energized and the GV is kept off The ICB halts any operation until a flame is...

Page 56: ...e thermostat setting lower than the conditioned space temperature This resets any flash codes Gas heat anticipator setpoints The anticipator setpoint must be correct Too high of a setting results in l...

Page 57: ...is unit has two stages of gas heat The first stage is 60 of the full fire input and is considered the minimum input for the furnace The intended input for each furnace is shown in Table 32 The table a...

Page 58: ...just the second stage 100 input pressure first then adjust first stage 60 input pressure 1 Turn off electrical power to the unit 2 Using the outlet pressure port on the gas valve connect a manometer t...

Page 59: ...e Figure 33 Typical flame Figure 34 Typical gas valve Charging the unit All ZK units use thermal expansion devices Charge the unit to nameplate charge Navigation components for the Smart Equipment con...

Page 60: ...e also effective for economizer free cooling supply air temperature reset when the ClgStgs parameter is set for 1 or more G Continuous indoor blower request 24 VAC input switched from R OCC Occupancy...

Page 61: ...erminate temporary occupancy COM Common for ST and SSO inputs Negative of VDC circuit for ST and SSO inputs SSO Space Sensor Offset input from 0 to 20K potentiometer Positive of VDC circuit 3 625 VDC...

Page 62: ...hot return from Air Proving Switch When this optional input is enabled the air proving switch must close within 30 seconds of initiation of indoor blower operation and not open for greater than 10 se...

Page 63: ...ntilation cooling reheat or heat pump heating demands C2 24 VAC hot output for compressor 2 Not effective for one stage compressor UCBs If demand is present and permissions allow compressor 2 operatio...

Page 64: ...f the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8 6 pin phone jack connecto...

Page 65: ...than FC bus BACnet MSTP communication circuit FC FC Field Connected BUS BACnet MSTP communication Positive of the VDC typically a fluctuating 1 5 to 3 5 volts reading to COM at least 0 25 volts lower...

Page 66: ...air Cable2 2 We recommend 26 AWG solid 6 wire 3 twisted pairs cable as the best fit for fabricating modular cables with the modular jack housing assembly Be sure the cable you use fits the modular jac...

Page 67: ...WLDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HT...

Page 68: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Page 69: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Page 70: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Page 71: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Page 72: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: