5566228-BIM-A-0818
64
Johnson Controls Ducted Systems
Table 34: ZK-A5 Charging Table
Air Flow
Indoor Db/Wb
Outdoor
DB
Suction
Pressure
Suction
Temp.
Liquid
Pressure
Liquid
Temp.
Delta T
Db
Compr.
amps
300 Cfm/Ton
80/62
75
142
59
374
96
-27
7.2
85
140
59
419
105
-28
7.8
95
139
59
465
113
-28
8.4
300 Cfm/Ton
80.000001/66.999999
75
141
59
375
97
-27
7.2
85
143
60
422
105
-27
7.8
95
145
61
470
114
-26
8.4
300 Cfm/Ton
80/72
75
140
59
376
97
-28
7.2
85
145
61
425
106
-26
7.9
95
150
63
475
115
-24
8.5
300 Cfm/Ton
75/62
75
135
57
368
95
-25
7.2
85
135
57
415
104
-25
7.8
95
136
57
461
112
-25
8.4
400 Cfm/Ton
80/62
75
147
62
380
98
-25
7.3
85
148
62
427
106
-24
7.9
95
148
62
474
114
-24
8.5
400 Cfm/Ton
80.000001/66.999999
75
147
62
379
98
-25
7.3
85
148
62
427
106
-24
7.9
95
150
63
476
115
-23
8.5
400 Cfm/Ton
80/72
75
147
62
379
98
-25
7.3
85
149
63
428
106
-24
7.9
95
152
64
477
115
-23
8.5
400 Cfm/Ton
75/62
75
141
59
374
96
-22
7.2
85
142
60
421
105
-22
7.8
95
143
60
468
114
-21
8.4