York ZK Series Installation Manual Download Page 52

5566228-BIM-A-0818

52

Johnson Controls Ducted Systems

Check blower drive belt tension.

6.

Check the unit supply air (CFM).

7.

Measure evaporator fan motor's amp draw.

8.

Set the room thermostat fan switch to off.

9.

Turn unit electrical power off.

Operating Instructions

1.

Turn unit electrical power on.

NOTE: 

Prior to each cooling season, the crankcase heaters 
must be energized at least 10 hours before the system 
is put into operation.

2.

Set the room thermostat setting to lower than the room 
temperature.

3.

First stage compressors will energize after the built-in time 
delay (five minutes).

Post Start Check List

1.

Verify proper system pressures.

2.

Measure the temperature drop across the evaporator coil.

Start-Up (Gas Heat)

Pre-Start Check List

Complete the following checks before starting the unit.
1.

Check the type of gas being supplied. Be sure that it is the 
same as listed on the unit nameplate.

2.

Make sure that the vent outlet and combustion air inlet are 
free of any debris or obstruction.

Operating Instructions

Lighting The Main Burners

1.

Turn “OFF” electric power to unit.

2.

Turn room thermostat to lowest setting.

3.

Turn gas valve counter-clockwise to “ON” position (See 
Figure 32).

4.

Turn “ON” electric power to unit.

5.

If thermostat set temperature is above room temperature, 
the main burners will ignite. If a second stage of heat is 
called for, the main burners for second stage heat will 
ignite for the second stage heat.

Post Start Checklist

After the entire control circuit has been energized and the 
heating section is operating, make the following checks:
1.

Check for gas leaks in the unit piping as well as the supply 
piping.

2.

Check for correct manifold gas pressures. (See CHECKING 
GAS INPUT.)

3.

Check the supply gas pressure. It must be within the limits 
shown on the rating nameplate. Supply pressure should be 
checked with all gas appliances in the building at full fire. At 
no time should the standby gas pressure exceed 10.5 in. or 
the operating pressure drop below 4.5 in for natural gas 
units. If gas pressure is outside these limits, contact the 
local gas utility or propane supplier for corrective action.

Shut Down

1.

Set the thermostat to the lowest temperature setting.

2.

Turn “OFF” all electric power to unit.

3.

Open gas heat access panel.

4.

Turn gas valve clockwise to “OFF” position (See Figures 32 
and 33).

Checking Gas Heat Input

Single Stage Gas Heat

This unit has a single stage of gas heat. The intended input for 
each furnace is shown in Table 28. The table applies to units 
operating on 60 Hz power only.

To determine the rate of gas flow (Single Stage).

1.

Turn off all other gas appliances connected to the gas 
meter. 

2.

Turn on the furnace and make sure the thermostat is 
calling for heat.

3.

Measure the time needed for one revolution of the hand on 
the smallest dial on the meter. A typical gas meter has a 1/ 
2 or a 1 cubic foot test dial.

4.

 Using the number of seconds it takes for one revolution of 
the dial, calculate the cubic feet of gas consumed per hour. 
(See example below).

This furnace is equipped with an automatic re-ignition 
system. DO NOT attempt to manually light the pilot.

FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result 
in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a 
commercially available soap solution made specifically 
for the detection of leaks to check all connections. A fire 
or explosion may result causing property damage, 
personal injury or loss of life.

Summary of Contents for ZK Series

Page 1: ...thru A5 Bottom Duct Application 41 19 RPM Selection 42 20 Indoor Blower Specifications 42 21 Power Exhaust Specifications 42 22 Motor Sheave Datum Diameters 44 23 Additional Static Resistance 45 24 El...

Page 2: ...test edition Wear safety glasses and work gloves Use quenching cloth and have a fire extinguisher available during brazing operations Improper installation may create a condition where the operation o...

Page 3: ...d directly on combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials 4 For use with natural gas convertible to LP with kit This product must be insta...

Page 4: ...erv 13 4 Coil Guard CG STD Filter 5 2 Pleated Filter CG 6 4 Pleated Filter CG A Std Cabinet E SSD SST Drain Pan R Reverse Drain Pan A No Economizer B Economizer w Barometric RLF D Economizer w Power E...

Page 5: ...Bracket 2 Turn each bracket toward the ground and the protective plywood covering will drop to the ground 3 Remove the condenser coil external protective covering prior to operation 4 Remove the tooll...

Page 6: ...operate the cooling system down to 0 F when this product is applied in a comfort cooling application for people An economizer is typically included in this type of application When applying this prod...

Page 7: ...the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimension acr...

Page 8: ...s Center of Gravity 4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F A3 3 ZK 851 846 47 25 24 00 161 183 266 235 105 114 124 181 167 154 A4 4 ZK 870 865 4...

Page 9: ...Johnson Controls Ducted Systems 9 Figure 8 ZK A3 Physical Dimensions 25 31 59 00 15 51 29 75 59 LEFT 11 3 8 21 3 16 89 27 5 16 4 3 16 FRONT See detail A for gas inlet A See detail B for drain locatio...

Page 10: ...Controls Ducted Systems Figure 9 ZK A4 thru A5 Physical Dimensions 24 47 TYP 2 PL 15 38 15 38 59 00 15 25 29 69 59 LEFT 11 3 8 21 3 16 89 27 5 16 4 3 16 FRONT See detail A for gas inlet A See detail B...

Page 11: ...3 16 15 3 16 6 3 16 42 CABINET 3 126 2 000 3 184 4 727 7 705 14 594 Gas Pipe Inlet Gas Exhaust Vent 5 3 8 1 FPT Table 5 ZK A3 thru A5 Unit Clearances Direction Distance in Direction Distance in Top1 1...

Page 12: ...Unit Bottom Duct Openings Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPLY AIR RIGHT LEFT 20 1 8 19 1 8 17 1 8 6 13 16 6 13 16 32 11 16 14 1 2 16 3 8 18 1 16 25 9 16 12 5 16 27...

Page 13: ...ith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8 FRONT Dot Plugs 5 5 32 31 11 16 2 31 32 18 1 4 Return Air Supply Air A B C D...

Page 14: ...ru A5 Roof Curb 4 5 16 A C B Table 7 Left End Duct Dimensions Unit Model Number Dimension in A B C ZK A3 30 357 13 365 22 516 ZK A4 30 357 13 365 22 516 ZK A5 30 357 13 365 22 516 8 or 14 50 1 2 30 20...

Page 15: ...r bottom duct application no duct cover changes are necessary For side duct application remove the side duct covers and install over the bottom duct openings The panels removed from the side duct conn...

Page 16: ...ing must conform to local codes Use a sealing compound on male pipe threads Install condensate drain line from the 1 inch NPT female connection on the unit to an open drain Figure 20 Condensate Drain...

Page 17: ...red If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire A disconnect must be uti...

Page 18: ...he unit nameplate Refer to Electrical Data Table 9 to size power wiring fuses and disconnect switch Power wiring is brought into the unit through the side of the unit or the basepan inside the curb Fi...

Page 19: ...F THERMOSTATS 1 4 3 1 4 Second stage ot required on single stage he g units Jumper is required for any co of R RC or RH 5 5 OCC is an output from the thermostat to indicate the Occupied on X is an inp...

Page 20: ...4 45 8 52 6 50 60 E20 15 2 41 6 58 5 65 4 60 70 230 13 8 83 1 22 2 1 5 2 5 5 None 26 7 32 2 35 45 E06 6 1 14 4 26 7 32 2 35 45 E08 9 1 21 7 33 6 40 5 40 45 E15 15 2 36 1 51 6 58 5 60 60 E20 20 2 48 1...

Page 21: ...1 12 5 26 7 32 2 35 45 E08 6 8 1 18 9 30 1 37 40 45 E15 11 3 2 31 4 45 8 52 6 50 60 E20 15 2 41 6 58 5 65 4 60 70 230 13 8 83 1 22 2 1 5 2 5 5 None 26 7 32 2 35 45 E06 6 1 14 4 26 7 32 2 35 45 E08 9...

Page 22: ...5 1 12 5 36 7 42 2 50 50 E08 6 8 1 18 9 42 6 49 5 50 50 E15 11 3 2 31 4 58 3 65 1 60 70 E20 15 2 41 6 71 77 9 80 80 230 13 8 83 1 22 2 1 5 2 5 5 20 None 36 7 42 2 50 50 E06 6 1 14 4 37 43 9 50 50 E08...

Page 23: ...5 1 12 5 36 7 42 2 50 50 E08 6 8 1 18 9 42 6 49 5 50 50 E15 11 3 2 31 4 58 3 65 1 60 70 E20 15 2 41 6 71 77 9 80 80 230 13 8 83 1 22 2 1 5 2 5 5 20 None 36 7 42 2 50 50 E06 6 1 14 4 37 43 9 50 50 E08...

Page 24: ...8 No stages 1 1 1 1 1 1 1 1 1 Temperature Rise Range F 20 50 F 25 65 F 50 80 F 20 50 F 25 65 F 50 80 F 25 65 F 35 65 F 45 75 F Gas Limit Setting F 235 200 255 235 200 255 200 245 240 Gas piping conne...

Page 25: ...ntrifugal Centrifugal Centrifugal Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44 Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59 Belt A47 A47 A47 A47 A47 A47 Motor HP each 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2...

Page 26: ...2 22 21 22 22 22 22 22 Temperature Rise Range F 20 50 F 25 65 F 50 80 F 20 50 F 25 65 F 50 80 F 25 65 F 35 65 F 45 75 F Gas Limit Setting F 235 200 255 235 200 255 200 245 240 Gas piping connection in...

Page 27: ...ntrifugal Centrifugal Centrifugal Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44 Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59 Belt A47 A47 A47 A47 A47 A47 Motor HP each 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2...

Page 28: ...ith the local gas utility Figure 23 Side Entry Gas Piping NOTE Routing of gas piping must not interfere with the flue or heat compartment access Figure 24 Bottom Entry Gas Piping NOTE Maximum capacity...

Page 29: ...del numbers 1NP0454 or 1NP0455 All LP gas equipment must conform to the safety standards of the National Fire Protection Association Table 13 Gas Heat Minimum Supply Air Size Tons Model Heat Size Supp...

Page 30: ...t least once a year For specific troubleshooting and maintenance procedures please refer to the smoke detector s installation instructions which accompanies the unit Motorized Outdoor Damper The Motor...

Page 31: ...y fan system both set points should be set to the same value Free Cooling Four types of free cooling options are available dry bulb changeover single enthalpy dual enthalpy changeover and Auto Dry Bul...

Page 32: ...e stage of cooling If the economizer output goes to minimum position and the SAT is less than Economizer Setpoint 1 F the control starts a 12 minute timer to de energize a compressor output If at any...

Page 33: ...mistor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Page 34: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Page 35: ...egative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HOT...

Page 36: ...ield supplied disconnect to obtain proper rotation Blower Rotation Check for proper supply air blower rotation If the blower is rotating backwards the line voltage at the unit point of power connectio...

Page 37: ...e the air at high altitude is less dense less static pressure will be generated and less power will be required than a similar application at sea level Air density correction factors are shown in Tabl...

Page 38: ...iven is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 0 6 832 0 72 Enter the blower table at 1 400 sCFM and...

Page 39: ...r and drive 5 turns open will achieve 1230 RPM Example Supply Air Blower Performance Air Flow CFM Available External Static Pressure IWG 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP...

Page 40: ...627 0 5 719 0 6 801 0 6 876 0 7 943 0 8 1005 0 9 1063 1 0 1117 1 1 1169 1 2 1400 537 0 5 639 0 5 731 0 6 813 0 7 888 0 7 955 0 8 1017 0 9 1075 1 0 1129 1 1 1181 1 2 1500 549 0 5 650 0 6 742 0 6 824 0...

Page 41: ...7 0 8 942 0 8 994 0 9 1046 1 0 1100 1 2 1157 1 3 1400 617 0 5 705 0 6 781 0 6 847 0 7 907 0 8 962 0 9 1014 1 0 1066 1 1 1119 1 2 1177 1 3 1500 637 0 6 724 0 6 800 0 7 867 0 8 927 0 8 981 0 9 1034 1 0...

Page 42: ...on Size Tons Model Airflow Option HP Max BHP Motor Sheave Blower Sheave 6 Turns Open 5 Turns Open 4 Turns Open 3 Turns Open 2 Turns Open 1 Turn Open Fully Closed A3 3 0 ZK Std 1 5 1 5 1VP34 AK61 N A 5...

Page 43: ...motor sheave is open 5 Select the correct blower performance table for the unit from Tables 17 and 18 Tables are presented for side and down flow configuration 6 Determine the unit Measured CFM from...

Page 44: ...llation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in static pressure and BHP BHP and AMP draw...

Page 45: ...2 0 03 0 01 0 01 0 01 0 02 0 02 0 02 1200 0 04 0 00 0 04 0 01 0 01 0 01 0 02 0 02 0 02 1300 0 03 0 01 0 05 0 01 0 01 0 01 0 03 0 03 0 03 1400 0 03 0 03 0 07 0 02 0 02 0 02 0 03 0 03 0 03 1500 0 03 0 0...

Page 46: ...onomizer The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes the compressor...

Page 47: ...calling for cooling the UCB will operate in the low ambient mode Low ambient mode operates the compressors in this manner 10 minutes on 5 minutes off The indoor blower is operated throughout the cycl...

Page 48: ...the unit continues to operate with refrigerant flow in the reheat coil and condenser coil 1 See Figure 29 Indoor blower operation is initiated upon a call for first stage cooling second stage cooling...

Page 49: ...The control circuit includes the following safety controls Limit Switch LS This control is located inside the heater compartment and is set to open at the temperature indicated in the Electric Heat L...

Page 50: ...attempts the furnace is locked out for one hour The furnace is monitored during this one hour period for unsafe conditions Recycle Operation When a flame is lost after the flame stabilization period a...

Page 51: ...r 2 seconds the GV will be de energized the ignition cycle is aborted and the ICB flashes the appropriate code See Table 31 Ignition Control Flash Codes The draft motor is energized until the pressure...

Page 52: ...k for correct manifold gas pressures See CHECKING GAS INPUT 3 Check the supply gas pressure It must be within the limits shown on the rating nameplate Supply pressure should be checked with all gas ap...

Page 53: ...a 1 cubic foot test dial 5 Using the number of seconds it takes for one revolution of the dial calculate the cubic feet of gas consumed per hour See example below 6 If necessary adjust the low pressur...

Page 54: ...unit on first stage 9 Once pressure has been checked replace the plastic cap covering the HI and LO pressure adjustment screws NOTE When using natural gas the manifold pressure for second stage 100 i...

Page 55: ...ource 1 P N S1 JC MAP1810 OP 3 MAP Gateway Quick Start Guide P N 24 10737 16 4 MAP Gateway Instruction P N 24 10737 8 For more information on the Smart Equipment unit control board navigation refer to...

Page 56: ...microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in series Connec...

Page 57: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Page 58: ...C reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for re...

Page 59: ...ut for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permis...

Page 60: ...er of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Page 61: ...indicates the UCB is supplying power to the communication sub board 1 When wiring unit and other devices using the SA Bus and FC Bus see Table 30 Table 29 Smart Equipment UCB Details Continued Descri...

Page 62: ...incline manometer digital manometer or Magnehelic gauge teed into the pressure switch sensing line verify that the negative pressure exceeds the setting listed on the induced draft pressure switch lab...

Page 63: ...16 6 7 95 171 71 383 102 14 7 3 400 Cfm Ton 75 63 75 138 62 288 82 21 6 3 85 141 62 321 90 20 6 7 95 144 61 372 98 18 7 2 Table 33 ZK A4 Charging Table Air Flow Indoor Db Wb Outdoor DB Suction Pressur...

Page 64: ...70 114 26 8 4 300 Cfm Ton 80 72 75 140 59 376 97 28 7 2 85 145 61 425 106 26 7 9 95 150 63 475 115 24 8 5 300 Cfm Ton 75 62 75 135 57 368 95 25 7 2 85 135 57 415 104 25 7 8 95 136 57 461 112 25 8 4 40...

Page 65: ...WLDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HT...

Page 66: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Page 67: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Page 68: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Page 69: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Page 70: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: