York ZK Series Installation Manual Download Page 62

5566228-BIM-A-0818

62

Johnson Controls Ducted Systems

Table 31: Flash Codes for the Gas Heat Ignition Control Board

Flash 
Code

Description

Technician Corrective Action

Heartbeat

Normal Operation - no staus or error information 
currently needs to be displayed

Steady 

Off

No Power to Control - 24v AC is not present to the 
control's 24VAC and C terminals.                         
Alternately: The control has catastrophic damage that 
will not allow the LED display - It is likely that there will 
be visible physical evidence of the damage 

Verify line voltage is present at the primary of the 75VA transformer, verify 
24v AC is present at the secondary of the 75VA transformer. Verify 24v AC is 
present from the Smart Equipment control's C to SD terminals indicating the 
3.2A control circuit breaker and phase monitor contacts are closed. Verify 
24v AC is present from the ignition control's C to 24VAC terminals indicating 
the Smart Equipment to Ignition control wiring is intact.

Steady 

On

The Control's Microprocessor Has Not Passed its Self-
check

Cycle power to the control to eliminate the possibility that transient voltage 
conditions such as surges, brownouts, etc. have not created a false 
indication. If the steady on LED indication repeats, the control will need to be 
replaced and potential causes for failure, such as excessive voltage, RF 
interference, etc. should be investigated.

2 Flashes

The Induced Draft Pressure Switch is Stuck Closed - 
24v AC is received to the control's PS terminal at the 
same time as 24v AC to initiate heating operation is 
received at the control's W1 terminal

Verify that the induced draft pressure switch contacts are not stuck or welded 
closed. Verify that the ignition control's INDUCER contacts are not stuck or 
welded closed causing the induced draft motor to run continuously. Verify 
that the wiring from the ignition control's W1 terminal through the induced 
draft pressure switch and rollout switch to the ignition control's PS terminal is 
not shorted.

3 Flashes

The Induced Draft Pressure Switch Did Not Close - 
24v AC was not received to the control's PS terminal 
within 5 seconds of the ignition control energizing the 
induced draft motor or 24v AC was later lost to the 
control's PS terminal while the ignition control 
energized the induced draft motor

Verify that the induced draft motor is operable, the ignition control's 
INDUCER contacts are not open, the induced draft blower wheel is intact and 
there are no blockages in the combustion air / induced draft path. Verify that 
the induced draft pressure switch sensing tubing is intact. With an incline 
manometer, digital manometer or Magnehelic® gauge teed into the pressure 
switch sensing line verify that the negative pressure exceeds the setting 
listed on the induced draft pressure switch label and the switch's contacts 
correctly close at the setting listed 

4 Flashes

Open Limit - 24v AC has been lost to the control's L 
terminal

Verify proper gas manifold pressure. Correct the inadequate indoor airflow 
condition. Verify filters, indoor coil and blower wheel are clean. Verify that the 
blower belt is properly maintained and adjusted; the blower contactor and 
motor are operable and wheel has the correct rotation. Verify that the ducting 
is not restrictive. Verify indoor air volume is at least the minimum required for 
the heat section by measuring the indoor coil pressure drop and comparing 
the reading to the chart in the Installation Manual. Verify heating mode 
blower on/off delays are proper for the heat type and provide adequate heat 
section cooling at the termination of the heating cycle. Verify wiring for main 
and auxiliary limits is intact

5 Flashes

Flame has been sensed when the MV1 output is off, or 
24v AC is present at the MV1 output without 24v AC to 
the W1 input, or 24v AC is present at the MV2 output 
without 24v AC at the MV1 output

Verify that the gas valve is not slow to shut off, leaks by or otherwise does 
not completely shut off gas flow when de-energized. Verify gas valve wiring 
to the control's MV1 and MV2 terminals is intact and not shorted in a manner 
that would improperly allow 24v AC from another circuit to be applied to the 
control's MV1 or MV2 terminals. Verify the control's contacts for MV1 and 
MV2 outputs are not shorted.  

6 Flashes

Ignition lockout - A flame signal of 1.0

μ

a or greater 

could not be established in 3 attempts for ignition at 
the initiation of the heating cycle / or / the flame signal 
has dropped below 1.0

μ

a 5 times during the heating 

cycle

Verify that combustion air openings are without blockages and that the unit 
has proper clearance to the structure and adjacent units .Verify that the 
burners are clean and without blockages that could interfere with gas flow. 
Verify that the ignitor sparks with an ≈1/8" gap to the crossover area of the 
left burner. Verify that the flame sensor is intact and positioned with an ≈1/8" 
gap to the right burner. Verify that the gas lines have been purged of air and 
proper gas inlet pressure. Verify that the gas valve is opening and adjusted to 
provide proper manifold pressure. Verify that the wiring to the gas valve is 
intact. Verify that there is no wind, rain or snow entering the heat 
compartment to interfere with ignition or the burners. Verify that there are no 
conditioned air leaks or heat exchanger breaches to interfere with ignition or 
the burners 

Summary of Contents for ZK Series

Page 1: ...thru A5 Bottom Duct Application 41 19 RPM Selection 42 20 Indoor Blower Specifications 42 21 Power Exhaust Specifications 42 22 Motor Sheave Datum Diameters 44 23 Additional Static Resistance 45 24 El...

Page 2: ...test edition Wear safety glasses and work gloves Use quenching cloth and have a fire extinguisher available during brazing operations Improper installation may create a condition where the operation o...

Page 3: ...d directly on combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials 4 For use with natural gas convertible to LP with kit This product must be insta...

Page 4: ...erv 13 4 Coil Guard CG STD Filter 5 2 Pleated Filter CG 6 4 Pleated Filter CG A Std Cabinet E SSD SST Drain Pan R Reverse Drain Pan A No Economizer B Economizer w Barometric RLF D Economizer w Power E...

Page 5: ...Bracket 2 Turn each bracket toward the ground and the protective plywood covering will drop to the ground 3 Remove the condenser coil external protective covering prior to operation 4 Remove the tooll...

Page 6: ...operate the cooling system down to 0 F when this product is applied in a comfort cooling application for people An economizer is typically included in this type of application When applying this prod...

Page 7: ...the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimension acr...

Page 8: ...s Center of Gravity 4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F A3 3 ZK 851 846 47 25 24 00 161 183 266 235 105 114 124 181 167 154 A4 4 ZK 870 865 4...

Page 9: ...Johnson Controls Ducted Systems 9 Figure 8 ZK A3 Physical Dimensions 25 31 59 00 15 51 29 75 59 LEFT 11 3 8 21 3 16 89 27 5 16 4 3 16 FRONT See detail A for gas inlet A See detail B for drain locatio...

Page 10: ...Controls Ducted Systems Figure 9 ZK A4 thru A5 Physical Dimensions 24 47 TYP 2 PL 15 38 15 38 59 00 15 25 29 69 59 LEFT 11 3 8 21 3 16 89 27 5 16 4 3 16 FRONT See detail A for gas inlet A See detail B...

Page 11: ...3 16 15 3 16 6 3 16 42 CABINET 3 126 2 000 3 184 4 727 7 705 14 594 Gas Pipe Inlet Gas Exhaust Vent 5 3 8 1 FPT Table 5 ZK A3 thru A5 Unit Clearances Direction Distance in Direction Distance in Top1 1...

Page 12: ...Unit Bottom Duct Openings Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPLY AIR RIGHT LEFT 20 1 8 19 1 8 17 1 8 6 13 16 6 13 16 32 11 16 14 1 2 16 3 8 18 1 16 25 9 16 12 5 16 27...

Page 13: ...ith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8 FRONT Dot Plugs 5 5 32 31 11 16 2 31 32 18 1 4 Return Air Supply Air A B C D...

Page 14: ...ru A5 Roof Curb 4 5 16 A C B Table 7 Left End Duct Dimensions Unit Model Number Dimension in A B C ZK A3 30 357 13 365 22 516 ZK A4 30 357 13 365 22 516 ZK A5 30 357 13 365 22 516 8 or 14 50 1 2 30 20...

Page 15: ...r bottom duct application no duct cover changes are necessary For side duct application remove the side duct covers and install over the bottom duct openings The panels removed from the side duct conn...

Page 16: ...ing must conform to local codes Use a sealing compound on male pipe threads Install condensate drain line from the 1 inch NPT female connection on the unit to an open drain Figure 20 Condensate Drain...

Page 17: ...red If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire A disconnect must be uti...

Page 18: ...he unit nameplate Refer to Electrical Data Table 9 to size power wiring fuses and disconnect switch Power wiring is brought into the unit through the side of the unit or the basepan inside the curb Fi...

Page 19: ...F THERMOSTATS 1 4 3 1 4 Second stage ot required on single stage he g units Jumper is required for any co of R RC or RH 5 5 OCC is an output from the thermostat to indicate the Occupied on X is an inp...

Page 20: ...4 45 8 52 6 50 60 E20 15 2 41 6 58 5 65 4 60 70 230 13 8 83 1 22 2 1 5 2 5 5 None 26 7 32 2 35 45 E06 6 1 14 4 26 7 32 2 35 45 E08 9 1 21 7 33 6 40 5 40 45 E15 15 2 36 1 51 6 58 5 60 60 E20 20 2 48 1...

Page 21: ...1 12 5 26 7 32 2 35 45 E08 6 8 1 18 9 30 1 37 40 45 E15 11 3 2 31 4 45 8 52 6 50 60 E20 15 2 41 6 58 5 65 4 60 70 230 13 8 83 1 22 2 1 5 2 5 5 None 26 7 32 2 35 45 E06 6 1 14 4 26 7 32 2 35 45 E08 9...

Page 22: ...5 1 12 5 36 7 42 2 50 50 E08 6 8 1 18 9 42 6 49 5 50 50 E15 11 3 2 31 4 58 3 65 1 60 70 E20 15 2 41 6 71 77 9 80 80 230 13 8 83 1 22 2 1 5 2 5 5 20 None 36 7 42 2 50 50 E06 6 1 14 4 37 43 9 50 50 E08...

Page 23: ...5 1 12 5 36 7 42 2 50 50 E08 6 8 1 18 9 42 6 49 5 50 50 E15 11 3 2 31 4 58 3 65 1 60 70 E20 15 2 41 6 71 77 9 80 80 230 13 8 83 1 22 2 1 5 2 5 5 20 None 36 7 42 2 50 50 E06 6 1 14 4 37 43 9 50 50 E08...

Page 24: ...8 No stages 1 1 1 1 1 1 1 1 1 Temperature Rise Range F 20 50 F 25 65 F 50 80 F 20 50 F 25 65 F 50 80 F 25 65 F 35 65 F 45 75 F Gas Limit Setting F 235 200 255 235 200 255 200 245 240 Gas piping conne...

Page 25: ...ntrifugal Centrifugal Centrifugal Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44 Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59 Belt A47 A47 A47 A47 A47 A47 Motor HP each 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2...

Page 26: ...2 22 21 22 22 22 22 22 Temperature Rise Range F 20 50 F 25 65 F 50 80 F 20 50 F 25 65 F 50 80 F 25 65 F 35 65 F 45 75 F Gas Limit Setting F 235 200 255 235 200 255 200 245 240 Gas piping connection in...

Page 27: ...ntrifugal Centrifugal Centrifugal Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44 Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59 Belt A47 A47 A47 A47 A47 A47 Motor HP each 1 1 2 1 1 2 1 1 2 1 1 2 1 1 2...

Page 28: ...ith the local gas utility Figure 23 Side Entry Gas Piping NOTE Routing of gas piping must not interfere with the flue or heat compartment access Figure 24 Bottom Entry Gas Piping NOTE Maximum capacity...

Page 29: ...del numbers 1NP0454 or 1NP0455 All LP gas equipment must conform to the safety standards of the National Fire Protection Association Table 13 Gas Heat Minimum Supply Air Size Tons Model Heat Size Supp...

Page 30: ...t least once a year For specific troubleshooting and maintenance procedures please refer to the smoke detector s installation instructions which accompanies the unit Motorized Outdoor Damper The Motor...

Page 31: ...y fan system both set points should be set to the same value Free Cooling Four types of free cooling options are available dry bulb changeover single enthalpy dual enthalpy changeover and Auto Dry Bul...

Page 32: ...e stage of cooling If the economizer output goes to minimum position and the SAT is less than Economizer Setpoint 1 F the control starts a 12 minute timer to de energize a compressor output If at any...

Page 33: ...mistor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Page 34: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Page 35: ...egative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HOT...

Page 36: ...ield supplied disconnect to obtain proper rotation Blower Rotation Check for proper supply air blower rotation If the blower is rotating backwards the line voltage at the unit point of power connectio...

Page 37: ...e the air at high altitude is less dense less static pressure will be generated and less power will be required than a similar application at sea level Air density correction factors are shown in Tabl...

Page 38: ...iven is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 0 6 832 0 72 Enter the blower table at 1 400 sCFM and...

Page 39: ...r and drive 5 turns open will achieve 1230 RPM Example Supply Air Blower Performance Air Flow CFM Available External Static Pressure IWG 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP...

Page 40: ...627 0 5 719 0 6 801 0 6 876 0 7 943 0 8 1005 0 9 1063 1 0 1117 1 1 1169 1 2 1400 537 0 5 639 0 5 731 0 6 813 0 7 888 0 7 955 0 8 1017 0 9 1075 1 0 1129 1 1 1181 1 2 1500 549 0 5 650 0 6 742 0 6 824 0...

Page 41: ...7 0 8 942 0 8 994 0 9 1046 1 0 1100 1 2 1157 1 3 1400 617 0 5 705 0 6 781 0 6 847 0 7 907 0 8 962 0 9 1014 1 0 1066 1 1 1119 1 2 1177 1 3 1500 637 0 6 724 0 6 800 0 7 867 0 8 927 0 8 981 0 9 1034 1 0...

Page 42: ...on Size Tons Model Airflow Option HP Max BHP Motor Sheave Blower Sheave 6 Turns Open 5 Turns Open 4 Turns Open 3 Turns Open 2 Turns Open 1 Turn Open Fully Closed A3 3 0 ZK Std 1 5 1 5 1VP34 AK61 N A 5...

Page 43: ...motor sheave is open 5 Select the correct blower performance table for the unit from Tables 17 and 18 Tables are presented for side and down flow configuration 6 Determine the unit Measured CFM from...

Page 44: ...llation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in static pressure and BHP BHP and AMP draw...

Page 45: ...2 0 03 0 01 0 01 0 01 0 02 0 02 0 02 1200 0 04 0 00 0 04 0 01 0 01 0 01 0 02 0 02 0 02 1300 0 03 0 01 0 05 0 01 0 01 0 01 0 03 0 03 0 03 1400 0 03 0 03 0 07 0 02 0 02 0 02 0 03 0 03 0 03 1500 0 03 0 0...

Page 46: ...onomizer The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor If the outdoor air enthalpy is above the setpoint Y1 energizes the compressor...

Page 47: ...calling for cooling the UCB will operate in the low ambient mode Low ambient mode operates the compressors in this manner 10 minutes on 5 minutes off The indoor blower is operated throughout the cycl...

Page 48: ...the unit continues to operate with refrigerant flow in the reheat coil and condenser coil 1 See Figure 29 Indoor blower operation is initiated upon a call for first stage cooling second stage cooling...

Page 49: ...The control circuit includes the following safety controls Limit Switch LS This control is located inside the heater compartment and is set to open at the temperature indicated in the Electric Heat L...

Page 50: ...attempts the furnace is locked out for one hour The furnace is monitored during this one hour period for unsafe conditions Recycle Operation When a flame is lost after the flame stabilization period a...

Page 51: ...r 2 seconds the GV will be de energized the ignition cycle is aborted and the ICB flashes the appropriate code See Table 31 Ignition Control Flash Codes The draft motor is energized until the pressure...

Page 52: ...k for correct manifold gas pressures See CHECKING GAS INPUT 3 Check the supply gas pressure It must be within the limits shown on the rating nameplate Supply pressure should be checked with all gas ap...

Page 53: ...a 1 cubic foot test dial 5 Using the number of seconds it takes for one revolution of the dial calculate the cubic feet of gas consumed per hour See example below 6 If necessary adjust the low pressur...

Page 54: ...unit on first stage 9 Once pressure has been checked replace the plastic cap covering the HI and LO pressure adjustment screws NOTE When using natural gas the manifold pressure for second stage 100 i...

Page 55: ...ource 1 P N S1 JC MAP1810 OP 3 MAP Gateway Quick Start Guide P N 24 10737 16 4 MAP Gateway Instruction P N 24 10737 8 For more information on the Smart Equipment unit control board navigation refer to...

Page 56: ...microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in series Connec...

Page 57: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Page 58: ...C reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for re...

Page 59: ...ut for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permis...

Page 60: ...er of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Page 61: ...indicates the UCB is supplying power to the communication sub board 1 When wiring unit and other devices using the SA Bus and FC Bus see Table 30 Table 29 Smart Equipment UCB Details Continued Descri...

Page 62: ...incline manometer digital manometer or Magnehelic gauge teed into the pressure switch sensing line verify that the negative pressure exceeds the setting listed on the induced draft pressure switch lab...

Page 63: ...16 6 7 95 171 71 383 102 14 7 3 400 Cfm Ton 75 63 75 138 62 288 82 21 6 3 85 141 62 321 90 20 6 7 95 144 61 372 98 18 7 2 Table 33 ZK A4 Charging Table Air Flow Indoor Db Wb Outdoor DB Suction Pressur...

Page 64: ...70 114 26 8 4 300 Cfm Ton 80 72 75 140 59 376 97 28 7 2 85 145 61 425 106 26 7 9 95 150 63 475 115 24 8 5 300 Cfm Ton 75 62 75 135 57 368 95 25 7 2 85 135 57 415 104 25 7 8 95 136 57 461 112 25 8 4 40...

Page 65: ...WLDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HT...

Page 66: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Page 67: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Page 68: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Page 69: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Page 70: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: