5168276-XIM-B-0216
Johnson Controls Unitary Products
33
Table 19: Air Flow Performance - Bottom Duct Application
ZF180 (15 Ton) Bottom Duct Imperial
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static 4.0 HP &
Field Supplied Drive
High Static 4.0 HP & OEM Drive
Field Supplied Motor & Drive
4400
803 1.70 841 2.00 877 2.28 919 2.52 991 2.84 1055 3.13 1110 3.38 1155 3.59 1193 3.78 1221 3.93 1242 4.04 1253 4.12
4800
832 2.11 870 2.42 906 2.69 948 2.93 1020 3.25 1084 3.54 1139 3.79 1185 4.01 1222 4.19 1250 4.34 1271 4.45 1282 4.53
5200
863 2.55 900 2.86 936 3.14 979 3.38 1051 3.70 1115 3.99 1169 4.24 1215 4.46 1253 4.64 1281 4.79 1301 4.90 1313 4.98
5600
896 3.03 933 3.34 969 3.62 1011 3.86 1084 4.19 1147 4.47 1202 4.73 1248 4.94 1285 5.13 1314 5.27 1334 5.39 1345 5.47
6000
930 3.54 967 3.86 1003 4.13 1045 4.38 1118 4.70 1181 4.99 1236 5.24 1282 5.46
-
-
-
-
-
-
-
-
6400
965 4.09 1002 4.41 1038 4.68 1081 4.93 1153 5.25 1217 5.54
-
-
-
-
-
-
-
-
-
-
-
-
6800
1002 4.67 1039 4.99 1075 5.27 1117 5.51
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7200
1040 5.28 1077 5.60
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ZF180 (15 Ton) Bottom Duct Metric
Air Flow
M
3
/sec.
Available External Static Pressure - Pa
1
100
149
199
249
299
349
399
448
498
548
598
648
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
High Static 4.0 HP & Field Supplied Drive
High Static 4.0 HP & OEM Drive
Field Supplied Motor & Drive
2.08
803 1.27 841 1.49 877 1.70 919 1.88 991 2.12 1055 2.33 1110 2.52 1155 2.68 1193 2.82 1221 2.93 1242 3.01 1253 3.07
2.27
832 1.57 870 1.80 906 2.01 948 2.18 1020 2.42 1084 2.64 1139 2.83 1185 2.99 1222 3.12 1250 3.24 1271 3.32 1282 3.38
2.45
863 1.90 900 2.13 936 2.34 979 2.52 1051 2.76 1115 2.98 1169 3.16 1215 3.33 1253 3.46 1281 3.57 1301 3.65 1313 3.71
2.64
896 2.26 933 2.49 969 2.70 1011 2.88 1084 3.12 1147 3.33 1202 3.53 1248 3.68 1285 3.83 1314 3.93 1334 4.02 1345 4.08
2.83
930 2.64 967 2.88 1003 3.08 1045 3.27 1118 3.50 1181 3.72 1236 3.91 1282 4.07
-
-
-
-
-
-
-
-
3.02
965 3.05 1002 3.29 1038 3.49 1081 3.68 1153 3.91 1217 4.13
-
-
-
-
-
-
-
-
-
-
-
-
3.21
1002 3.48 1039 3.72 1075 3.93 1117 4.11
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3.40
1040 3.94 1077 4.18
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.