5168276-XIM-B-0216
Johnson Controls Unitary Products
31
Table 18: Air Flow Performance - Side Duct Application
ZF180-240 Side Duct Application
ZF180 (15 Ton) Side Duct Imperial
Air Flow
(CFM)
Available External Static Pressure - IWG
1
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
High Static 4.0 HP & Field Supplied Drive
High Static 4.0 HP & OEM Supplied Drive
4400
760 1.56 798 1.90 835 2.20 878 2.47 950 2.81 1014 3.11 1069 3.38 1115 3.61 1154 3.81 1184 3.97 1205 4.09 1218 4.18
4800
786 1.93 824 2.27 861 2.57 904 2.84 976 3.18 1040 3.48 1095 3.75 1142 3.98 1180 4.18 1210 4.34 1231 4.46 1244 4.55
5200
815 2.34 853 2.68 890 2.98 933 3.25 1005 3.59 1068 3.89 1123 4.16 1170 4.39 1208 4.59 1238 4.75 1260 4.87 1273 4.96
5600
845 2.79 883 3.13 920 3.43 963 3.70 1035 4.04 1099 4.34 1154 4.61 1200 4.84 1239 5.04 1269 5.20 1290 5.32 1303 5.41
6000
877 3.28 915 3.62 952 3.92 995 4.19 1067 4.53 1131 4.83 1186 5.10 1232 5.33 1271 5.53
-
-
-
-
-
-
6400
911 3.81 949 4.15 986 4.45 1029 4.72 1101 5.06 1164 5.36 1219 5.63
-
-
-
-
-
-
-
-
-
-
6800
946 4.38 984 4.72 1021 5.02 1064 5.29
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
7200
982 4.98 1020 5.32 1057 5.62
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Field Supplied Motor & Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.838.
ZF180 (15 Ton) Side Duct Metric
Air Flow
M
3
/sec.
Available External Static Pressure - Pa
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
100
149
199
249
299
349
399
448
498
548
598
648
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM Kw RPM kW
High Static 4.0 HP & Field Supplied Drive
High Static 4.0 HP & OEM Drive
2.08
760 1.16 798 1.42 835 1.64 878 1.84 950 2.09 1014 2.32 1069 2.52 1115 2.69 1154 2.84 1184 2.96 1205 3.50 1218 3.12
2.27
786 1.44 824 1.69 861 1.92 904 2.12 976 2.37 1040 2.60 1095 2.80 1142 2.97 1180 3.12 1210 3.24 1231 3.33 1244 2.39
2.45
815 1.75 853 2.00 890 2.22 933 2.42 1005 2.68 1068 2.90 1123 3.10 1170 3.27 1208 3.42 1238 3.54 1260 3.63 1273 3.70
2.64
845 2.08 883 2.33 920 2.56 963 2.76 1035 3.01 1099 3.24 1154 3.44 1200 3.61 1239 3.76 1269 3.88 1290 3.97 1303 4.03
2.83
877 2.45 915 2.70 952 2.92 995 3.12 1067 3.38 1131 3.60 1186 3.80 1232 3.97 1271 4.12
-
-
-
-
-
-
3.02
911 2.84 949 3.10 986 3.32 1029 3.52 1101 3.77 1164 4.00 1219 4.20
-
-
-
-
-
-
-
-
-
-
3.21
946 3.27 984 3.52 1021 3.74 1064 3.94
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3.40
982 3.71 1020 3.97 1057 4.19
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Field Supplied Motor & Drive