12.  Find your VSD model from the list below, 

and set the adjustments to the setting val-

ues in the following table. If your model is 

not listed below, look for it in the next table of 

drive model numbers with the ratings plug value.

a.  TV2CMPRBW-40A
b.  TV2CMPRBW-65A

c.  TV2CMPRBW-50C

d.  TV2CMPRBW-68A
e.  TV2CMPRBW-46A

ADjUSTMeNT

SeTTiNG VAlUe

Long Time Pickup IR~ 

G

Long Time Delay TLD(S) LONG

2

Short Time Delay ISD(XIR) 
SHORT 

2

Ground Fault Pickup IG(XIN) 
GND 

0.2

Ground Fault Delay TSD/
TG(MS) SHORT/GND

J

Find your model from the list below, check the ratings 

plug values in the first table, and set the setting values 

for the adjustments listed in the second table:

DRiVe MODel NO.

RATiNGS PlUG VAlUe

TV2CMPRBW-40B

600

TV2CMPRBW-40C

800

TV2CMPRBW-65B

600

TV2CMPRBW-65C

800

TV2CMPRBW-50B

600

TV2CMPRBW-50C

800

TV2CMPRBW-68B

600

TV2CMPRBW-68C

800

TV2CMPRBW-46B

600

TV2CMPRBW-58B

600

ADjUSTMeNT

SeTTiNG VAlUeS

Short Delay Pick-up

2

Short Delay Time

INST

Ground Fault Pick-up

1

Ground Fault Time

150

The settings for the circuit breaker should 

not be changed from the settings. The war-

ranty will be voided if the breaker settings 

are changed.

13.  Check the chiller for refrigerant leaks at joints or 

water piping leaks.  .............................................

14.  Make sure 9 liters (2.38 gallons) of compressor 

oil were added to both circuits.  ..........................

15.  Make sure the control panel is free of foreign 

material (wires, metal chips, tools, documents, 

etc.). Check for signs of water or moisture.  .......

16.  Make sure the leaving liquid temperature sensor 

is coated with the heat conductive compound 

(P/N 013-00890-000), and is inserted to the bot-

tom of the water outlet sensor well in the cooler. 

This sensor must always be fully inserted in the 

water outlet sensor well.  ....................................

17.  Make sure the flow switches are connected be-

tween Terminals 2 and 12 and 2 and 13 on Ter-

minal Block 1TB in the control panel.  .................

18.  Check whenever the pump contacts are used, 

the coil of the pump starter should be suppressed 

with an RC suppressor (P/N 031-00808-000).  ...

B. START-UP
Panel check

Only qualified individuals are permit-

ted to service this product, and are to 

be knowledgeable of, and adhere to, all 

safe work practices as required by local 

codes. Use proper personal protection 

where and when required.

1.  Verify that the voltage supply corresponds to 

the unit requirement, and is within the limits as 

specified in SECTION 4 - TECHNICAL DATA in 

Form 201.30-ICOM2

.

  .........................................

2.  Make sure the unit switch at the bottom of the 

keypad is in the OFF (O) position.  .....................

3.  Apply 3-phase power to the chiller. Turn on the 

optional panel circuit breaker, if supplied.  ..........

4.  Verify the control panel display is illuminated. 

To prevent the compressors from starting, make 

sure that the SYSTEM SWITCHES key is off for 

both systems. . ....................................................

5.  Use a clamp-on ammeter to make sure the both 

compressor heaters are turned on. Heater cur-

rent draw is approximately 3A.  ...........................

6.  Confirm that the compressor overload current 

settings have been correctly adjusted by the fac-

tory. These are not normally required to be re-

set. Use the VSD DATA key on the control panel, 

navigate to the COMP1 MOTOR OVERLOAD = 

### AMPS and COMP2 MOTOR OVERLOAD 

= ### AMPS screens. The values should match 

the values on the overload setting label, which is 

located inside of the VSD cabinet. If the values 

do not match, an adjustment is required inside 

the VSD cabinet by qualified service personnel. .

(continued on following page)