(4) Additional charge
When the length of the one-way pipe is less than 5m, additional refrigerant charge after vacuuming is not
necessary.
When the length of one-way pipe is over 5m, the quantity to be added is as follows (unit in gram):
Connective pipe length
Air purging method
Additional amount of refrigerant to be charged
Less than 5m
Use refrigerant of outdoor unit
Over 5m
Use vacuum pump or refrigerant
cylinder
30g(length-5m) (capacity
≤
20000btu/h.)
65g(length-5m) (capacity
≥
24000btu/h.)
3. Connect the drain pipe
4. Wiring
Please refer to the Wiring Diagram.
5. Test
operation
(1) The test operation must be carried out after the entire installation has been completed.
(2) Please confirm the following points before the test operation.
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of the refrigerant have been recorded.
The power voltage fits the rated voltage of the air conditioner.
There is no obstacle at the outlet and inlet of the outdoor and indoor units.
The gas-side and liquid-side stop values are both opened.
The air conditioner is pre-heated by turning on the power.
(3) According to the user's requirement, install the remote controller when the remote controller's signal can reach
the indoor unit smoothly.
(4) Test operation
Indoor unit
Whether the switch on the remote controller works well.
Whether the buttons on the remote controller works well.
Whether the air flow louver moves normally.
Whether the room temperature is adjusted well.
Whether the indicator lights normally.
Whether the drainage is normal.
Whether there is vibration or abnormal noise during operation.
Outdoor unit
Whether there is vibration or abnormal noise during operation.
Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood.
Whether any of the refrigerant is leaked.
Summary of Contents for YUHC 18
Page 26: ...Part 9 Wiring diagram 1 YUHC 18 Indoor unit Outdoor unit...
Page 27: ...2 YUHC 24 Indoor unit Outdoor unit...
Page 28: ...3 YUHC 30 YUHC 36 Indoor unit Outdoor unit...
Page 30: ...5 YUHC 60 Indoor unit Outdoor unit...
Page 31: ...Part 10 Outlines and Dimension Indoor units 1 YUKC 18 YUKC 24 2 YUKC 30 YUKC 36 YUKC 48...
Page 32: ...3 YUKC 60 Outdoor units 1 YUJC 18 12 5...
Page 49: ...www johnsoncontrols com SM YUHC 18 60GB 03 07...