Model:
YUHC-60
COOLING
OUTDOOR CONDITIONS
Indoor
Conditions
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
15.46 14.78 14.25 13.44 12.90 12.50 12.10
Sensitive capacity kW
12.36 11.83 11.40 10.75 10.32 10.00 9.68
21ºC D
15ºC W
Input kW.
3.78 4.32 4.86 5.40 5.94 6.48 7.02
Total capacity kW
16.93 16.19 15.60 14.72 14.13 13.69 13.25
Sensitive capacity kW
13.54 12.95 12.48 11.78 11.30 10.95 10.60
24ºC D
17ºC W
Input kW.
3.99 4.56 5.13 5.70 6.27 6.84 7.41
Total capacity kW
18.40 17.60 16.96
16.00
15.36 14.88 14.40
Sensitive capacity kW
14.72 14.08 13.57 12.80 12.29 11.90 11.52
27ºC D
19ºC W
Input kW.
4.20 4.80 5.40
6.00
6.60 7.20 7.80
Total capacity kW
21.16 20.24 19.50 18.40 17.66 17.11 16.56
Sensitive capacity kW
16.93 16.19 15.60 14.72 14.13 13.69 13.25
32ºC D
23ºC W
Input kW.
4.83 5.52 6.21 6.90 7.59 8.28 8.97
HEATING OUTDOOR
CONDITIONS
Indoor
Conditions
24ºC D
18ºC W
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-5ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
24.00 19.20 16.00 14.40 13.60 12.00 11.20 10.40
15ºC
Input kW.
7.20 5.76 4.80 4.56 4.32 4.08 3.84 3.36
Capacity kW
27.00 21.60 18.00 16.20 15.30 13.50 12.60 11.70
18ºC
Input kW.
8.10 6.48 5.40 5.13 4.86 4.59 4.32 3.78
Capacity kW
30.00 24.00
20.00
18.00 17.00 15.00 14.00 13.00
20ºC
Input kW.
9.00 7.20
6.00
5.70 5.40 5.10 4.80 4.20
Capacity kW
33.00 26.40 22.00 19.80 18.70 16.50 15.40 14.30
22ºC
Input kW.
9.90 7.92 6.60 6.27 5.94 5.61 5.28 4.62
Capacity kW
39.00 31.20 26.00 23.40 22.10 19.50 18.20 16.90
27ºC
Input kW.
11.70 9.36 7.80 7.41 7.02 6.63 6.24 5.46
Summary of Contents for YUHC 18
Page 26: ...Part 9 Wiring diagram 1 YUHC 18 Indoor unit Outdoor unit...
Page 27: ...2 YUHC 24 Indoor unit Outdoor unit...
Page 28: ...3 YUHC 30 YUHC 36 Indoor unit Outdoor unit...
Page 30: ...5 YUHC 60 Indoor unit Outdoor unit...
Page 31: ...Part 10 Outlines and Dimension Indoor units 1 YUKC 18 YUKC 24 2 YUKC 30 YUKC 36 YUKC 48...
Page 32: ...3 YUKC 60 Outdoor units 1 YUJC 18 12 5...
Page 49: ...www johnsoncontrols com SM YUHC 18 60GB 03 07...