5.2 Self-diagnosis
5.2.1 Indoor unit
No. Type
Contents
LED
Flashing
Remark
1
protection
Over current protection of the compressor
occurs 4 times in 1h
Lamps of operation, timer,
defrosting (only fan )
flashing simultaneously at
5Hz.
Whole unit is shut down.
It cannot recover unless
power is cut off
2
protection
Outdoor protection (absent phrase, phrase
sequence and temperature protection)
All lamps flashing at 5Hz
3
error
Room temperature sensor checking channel
is abnormal
Timer lamp flashing at 5Hz
4
error
Evaporator sensor checking channel is
abnormal
Operation lamp flashing at
5Hz
5
error
Condenser sensor checking channel is
abnormal
Defrosting lamp flashing at
5Hz
6
error
Temperature fuse is melt(reserved)
Operation lamp and timer
lamp flashing at 5Hz
Recover automatically
after errors are
eliminated(For T3
malfunction of 5HP, can”t
recover automatically)
5.2.2 LEDs for the indication of outdoor trouble(3 phase type,3.5~7HP)
Type
Contents
LED1 LED2 LED3
Trouble Phase
sequence
Flash
Off
Off
Trouble
Lack of phase
Flash
Off
Off
Trouble
Protection of pressure
Flash
Flash
Off
Trouble
Overload of current
Off
Off
Flash
Trouble
Open-circuit and short-circuit trouble of T3
Off
Flash
Flash
Trouble
Open-circuit and short-circuit trouble of T4
Off
Flash
Off
Trouble
High temperature protection of
condenser
Flash Flash Flash
Summary of Contents for YUHC 18
Page 26: ...Part 9 Wiring diagram 1 YUHC 18 Indoor unit Outdoor unit...
Page 27: ...2 YUHC 24 Indoor unit Outdoor unit...
Page 28: ...3 YUHC 30 YUHC 36 Indoor unit Outdoor unit...
Page 30: ...5 YUHC 60 Indoor unit Outdoor unit...
Page 31: ...Part 10 Outlines and Dimension Indoor units 1 YUKC 18 YUKC 24 2 YUKC 30 YUKC 36 YUKC 48...