39
7.4.1.3 Zero-crossing signal detection error diagnosis and solution.
Malfunction conditions
When PCB does not receive zero crossing signal feedback for
4 minutes or the zero crossing signal time interval is abnormal.
Potential causes
●
Connection mistake
●
Faulty PCB
Trouble shooting:
Check if the connections and
power supply is normal ?
Correct the connections . Turn on the
unit when the power supply is good .
No
Yes
Indoor main PCB is
defective. Replace indoor
main PCB.
PIC 4: Check point button, press 1 time for check
how many indoor units are connected.
Summary of Contents for YU2E18YJ6AMHO-Y
Page 3: ...3 YU4E36YJ6AMHO Y WD30 metal plate 110 YU5E48YJ6AMHO Y WE30 metal plate 117...
Page 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor YU2E18YJ6AMHO Y...
Page 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor YU3E27YJ6AMHO Y...
Page 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor YU4E36YJ6AMHO Y...
Page 26: ...26 6 4 Wiring diagram of 1 drive 5 outdoor YU5E48YJ6AMHO Y...
Page 37: ...37 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Page 44: ...44...
Page 45: ...45 7 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Page 48: ...48 7 4 1 11 High temperature protection of IPM board diagnosis and solution...
Page 51: ...51...
Page 53: ...53 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Page 55: ...55 PIC 4 Check point button press 1 time for check how many indoor units are connected...
Page 60: ...60 IPM board for 2 zone 3 zone...
Page 62: ...62 IPM board for 4 zone...
Page 65: ...65 Two ports of the inductance Inductance...
Page 68: ...68 Vs Vcc Vsp FG...
Page 70: ...70...
Page 71: ...71...
Page 73: ...73...
Page 74: ...74...
Page 76: ...76...
Page 77: ...77...
Page 90: ...90 6 EXV check Disconnect the connectors...
Page 92: ...92 Red Blue Red Yellow...
Page 93: ...93 Brown Orange...
Page 94: ...94 Brown White...
Page 104: ...104 Screws of right rear panel Screws of terminal board...