18
If the outdoor ambient temperature is higher than
the set frequency during oil return, the unit stops
the oil return process.
5.3.11
Low Outdoor Ambient Temperature
Protection
When the compressor is off and T4 is lower than -
35
℃
for 10 seconds, the unit stops and displays
“
LP.
”
When the compressor is on and T4 remains lower
than -40
℃
for 10 seconds, the unit stops and
displays
“
LP.
”
When T4 is no lower than -32
℃
for 10 seconds,
the unit exits protection.
5.4 Control and Functions
5.4.1 Capacity Request Calculation
For Old Console series, Old Duct/Cassette/Floor
Ceiling, Old Vertu/Luna Series:
Total capacity Request=Σ(Norm code × HP) /10×
modify rate+ correction
For All new models(New Wall mounted(Hi-Wall)
series, New Duct/Cassette/Console/Floor Ceiling):
Total capacity Request=Σ(Norm code × HP) /40×
modify rate+ correction
Cooling Mode:
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
Capacity area
a
b
c
d
e
f
Norm code (N)
3
2 1.5 1 0.5 0
Model
9K
12K
18K
24K
HP
1.0
1.2
1.5
2.5
Note: The final result is an integer.
Use the following table and final capacity
request to confirm the operating frequency.
Frequency
(Hz)
0
COO
L_F1
COO
L_F2
…
…
COOL
_F24
COO
L_F2
5
Amendatory
capacity
demand.
0
1
2
…
…
24
25
The maximum running frequency is adjusted
according to the outdoor ambient temperature
℃
55
54
Fmax=
T4FREMAXC0
51.5
50.5
Fmax= T4FREMAXC1
45.5
44.5
Fmax= T4FREMAXC2
39
38
Fmax= T4FREMAXC3
33
32
Fmax= T4FREMAXC4
30
29
Fmax= T4FREMAXC5
22
20
Fmax= T4FREMAXC6
10
8
Fmax= T4FREMAXC7
0
-2
Fmax= T4FREMAXC8
-10
-12
Fmax= T4FREMAXC9
Fmax= T4FREMAXC10
Heating Mode
T1 Ts
4
0
a
3
1
-1
3
1
2
0
b
c
d
e
f
2
Summary of Contents for YU2E18YJ6AMHO-Y
Page 3: ...3 YU4E36YJ6AMHO Y WD30 metal plate 110 YU5E48YJ6AMHO Y WE30 metal plate 117...
Page 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor YU2E18YJ6AMHO Y...
Page 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor YU3E27YJ6AMHO Y...
Page 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor YU4E36YJ6AMHO Y...
Page 26: ...26 6 4 Wiring diagram of 1 drive 5 outdoor YU5E48YJ6AMHO Y...
Page 37: ...37 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Page 44: ...44...
Page 45: ...45 7 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Page 48: ...48 7 4 1 11 High temperature protection of IPM board diagnosis and solution...
Page 51: ...51...
Page 53: ...53 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Page 55: ...55 PIC 4 Check point button press 1 time for check how many indoor units are connected...
Page 60: ...60 IPM board for 2 zone 3 zone...
Page 62: ...62 IPM board for 4 zone...
Page 65: ...65 Two ports of the inductance Inductance...
Page 68: ...68 Vs Vcc Vsp FG...
Page 70: ...70...
Page 71: ...71...
Page 73: ...73...
Page 74: ...74...
Page 76: ...76...
Page 77: ...77...
Page 90: ...90 6 EXV check Disconnect the connectors...
Page 92: ...92 Red Blue Red Yellow...
Page 93: ...93 Brown Orange...
Page 94: ...94 Brown White...
Page 104: ...104 Screws of right rear panel Screws of terminal board...