20
4) If the compressor cumulative running time
reaches 120 minutes and T3<-15
℃
.
Defrost Stop Conditions
If any one of the following conditions is satisfied,
defrosting ends and the unit returns to normal
heating mode:
----T3 rises above than TCDE1
℃
.
----T3 remains at TCDE2
℃
or above for 80
seconds.
----The machine runs for 10 consecutive minutes
in defrosting mode.
Defrosting Action
:
off
on
Cool-F9
10S
30S
TimeA
10S
4-way valve
defrosting
Defrosting over
compressor
Indoor fan
Outdoor fan
EXV open
frequency
Max 10 minutes
frequency
Compressor stops
off
Anti-cold control
off
480P
480P for 240s
Condition of ending defrosting:
If any one of following items is satisfied,
defrosting will stop and the machine will turn to
normal heating mode.
①
T3 > TempQuitDefrost_ADD
℃
;.
②
The defrosting time achieves 10min.
③
Turn to other modes or off.
5.4.3 Outdoor Fan Control
5.4.3.1 Cooling Mode
Under normal operating conditions, the system
chooses the running fan speed according to the
ambient temperature:
Outdoor temperature
℃
45
43
Supper high fan speed
28
26
High fan speed
25
23
Middle fan speed
22
20
Low fan speed
19
17
Supper low fan speed
10
9
Breeze fan speed
0
-1
F fan speed
-5
-6
G fan speed
-10
-11
H fan speed
I fan speed
When low ambient cooling is in effect::
Outdoor fan speed control logic (low ambient
cooling)
When T4
<
15
℃
(59
℉
) and T3 < 30
℃
(86
℉
),
the unit enters into low ambient cooling mode.
The outdoor fan chooses a speed according to T3.
When T3
≥
38
℃
(100.4
℉
) or when T4
≥
20
℃
(68
℉
), the outdoor fan chooses a speed
according to T4 again.
38
Exit low ambient cooling
mode
,
run with high fan
for 1 minute
Low
30
27
23
off
Summary of Contents for YU2E18YJ6AMHO-Y
Page 3: ...3 YU4E36YJ6AMHO Y WD30 metal plate 110 YU5E48YJ6AMHO Y WE30 metal plate 117...
Page 23: ...23 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor YU2E18YJ6AMHO Y...
Page 24: ...24 6 2 Wiring diagram of 1 drive 3 outdoor YU3E27YJ6AMHO Y...
Page 25: ...25 6 3 Wiring diagram of 1 drive 4 outdoor YU4E36YJ6AMHO Y...
Page 26: ...26 6 4 Wiring diagram of 1 drive 5 outdoor YU5E48YJ6AMHO Y...
Page 37: ...37 Operating Standby Pic 2 IPM for 2 zone 3 zone...
Page 44: ...44...
Page 45: ...45 7 4 1 7 Over voltage or under voltage protection diagnosis and solution...
Page 48: ...48 7 4 1 11 High temperature protection of IPM board diagnosis and solution...
Page 51: ...51...
Page 53: ...53 Operating Standby Pic 2 IPM board for 2 zone 3 zone...
Page 55: ...55 PIC 4 Check point button press 1 time for check how many indoor units are connected...
Page 60: ...60 IPM board for 2 zone 3 zone...
Page 62: ...62 IPM board for 4 zone...
Page 65: ...65 Two ports of the inductance Inductance...
Page 68: ...68 Vs Vcc Vsp FG...
Page 70: ...70...
Page 71: ...71...
Page 73: ...73...
Page 74: ...74...
Page 76: ...76...
Page 77: ...77...
Page 90: ...90 6 EXV check Disconnect the connectors...
Page 92: ...92 Red Blue Red Yellow...
Page 93: ...93 Brown Orange...
Page 94: ...94 Brown White...
Page 104: ...104 Screws of right rear panel Screws of terminal board...