8. Electric Characteristics
Indoor Units
Power Supply
Indoor fan motor
Power input(W)
Model
Hz
Voltage
Min. Max.
MCA
MFA
kW
FLA
Cooling
Heating
YOCA 12
YOHA 12
YOCA 18
YOHA 18
YOCA 24
YOHA 24
YOCA 36
YOHA 36
YOCA 36
YOHA 36
YOCA 48
YOHA 48
YOCA 60
YOHA 60
7.6
15
0.03
0.145
1370
7.6
15
0.03
0.145
1370
1350
10.6
20
0.055
0.52
1900
11.0
20
0.055
0.52
1900
1850
17.6
50
0.055
0.52
3100
17.0
50
0.055
0.52
2800
2860
22.5
70
0.08
0.59
4050
220~240
198
264
22.0
70
0.08
0.59
3700
3350
8.9
20
0.08
0.59
4050
8.2
20
0.08
0.59
3700
3350
10.6
30
0.12
0.78
4800
10.3
30
0.12
0.78
4700
4900
12.5
30
0.12
0.78
6570
50
380
342
418
12.5
30
0.12
0.78
6570
6900
Symbols:
MCA: Min. Circuit Amps.
MFA: Max. Fuse Amps..
FLA: Full Load Amps.
Kw: Rate Motor Output
Notes:
3. Voltage range should not over the value of above table.
4. Maximum allowable voltage variation between phase is 2%
5. Selection wire size based on the larger value of MCA.
6. MCA/MFA
MCA = 1.25
×
FLA
MFA
≤
4
×
FLA
(Next lower standard fuse rating min. 15A)
5. Instead of fuse, circuit breaker is also acceptable.