![background image](http://html.mh-extra.com/html/york/ymge36bno-ms-x/ymge36bno-ms-x_user-manual_913559015.webp)
I&O manual
12
COOLING PERFORMANCE DATA—60HP(380V, 50Hz, 3Ph)
HEATING PERFORMANCE DATA—60HP(380V, 50Hz, 3Ph)
Ent
(
DB
)
(℉)
72
75
78
80
72
75
78
80
72
75
78
80
T C
43.4
48.6
53.4
56.3
44.3
49.6
54.5
57.4
45.2
50.6
55.6
58.6
SC
32.7
37.9
42.7
45.6
33.4
38.7
43.6
46.6
34.1
39.5
44.5
47.5
PI
4.92
4.95
4.97
5.00
4.97
5.00
5.02
5.05
5.02
5.05
5.07
5.10
T C
45.2
51.1
56.5
60.0
46.2
52.1
57.7
61.3
47.1
53.2
58.9
62.5
SC
26.0
31.9
37.3
40.8
26.6
32.5
38.1
41.7
27.1
33.2
38.9
42.5
PI
4.96
4.99
5.01
5.04
5.01
5.04
5.06
5.09
5.06
5.09
5.11
5.14
T C
46.8
53.2
59.1
63.0
47.8
54.3
60.4
64.3
48.8
55.4
61.6
65.6
SC
18.3
24.7
30.6
34.5
18.7
25.2
31.3
35.2
19.1
25.7
31.9
35.9
PI
4.99
5.02
5.04
5.07
5.04
5.07
5.09
5.12
5.09
5.12
5.14
5.17
T C
38.2
43.7
48.8
51.9
39.0
44.6
49.8
53.0
39.8
45.5
50.8
54.1
SC
31.6
37.1
42.1
45.3
32.2
37.8
43.0
46.3
32.9
38.6
43.9
47.2
PI
5.44
5.46
5.49
5.52
5.49
5.52
5.55
5.57
5.55
5.57
5.60
5.63
T C
41.4
47.4
53.2
55.7
42.2
48.4
54.3
56.8
43.1
49.4
55.4
58.0
SC
24.7
30.7
36.5
39.0
25.2
31.4
37.2
39.8
25.7
32.0
38.0
40.6
PI
5.46
5.49
5.52
5.55
5.52
5.55
5.58
5.60
5.58
5.60
5.63
5.66
T C
42.6
48.8
54.8
58.7
43.5
49.8
56.0
59.9
44.4
50.8
57.1
61.1
SC
17.3
23.4
29.5
33.3
17.6
23.9
30.1
34.0
18.0
24.4
30.7
34.7
PI
5.50
5.53
5.56
5.59
5.56
5.59
5.61
5.64
5.61
5.64
5.67
5.70
T C
33.3
39.0
44.4
47.6
34.0
39.8
45.3
48.6
34.7
40.6
46.2
49.6
SC
30.1
35.8
41.2
44.4
30.8
36.6
42.0
45.4
31.4
37.3
42.9
46.3
PI
5.95
5.98
6.01
6.04
6.01
6.04
6.07
6.10
6.07
6.10
6.13
6.16
T C
35.7
41.8
47.6
51.4
36.5
42.6
48.6
52.4
37.2
43.5
49.6
53.5
SC
23.3
29.4
35.2
39.0
23.8
30.0
36.0
39.8
24.3
30.6
36.7
40.6
PI
5.98
6.01
6.04
6.07
6.04
6.07
6.10
6.13
6.10
6.13
6.16
6.19
T C
38.4
44.4
50.4
54.3
39.2
45.3
51.5
55.5
40.0
46.2
52.5
56.6
SC
16.1
22.1
28.1
32.1
16.5
22.5
28.7
32.7
16.8
23.0
29.3
33.4
PI
6.00
6.03
6.07
6.10
6.07
6.10
6.13
6.16
6.13
6.16
6.19
6.22
T C
28.7
34.5
39.9
43.3
29.3
35.2
40.8
44.2
29.9
35.9
41.6
45.1
SC
28.5
34.3
39.7
43.1
29.1
35.0
40.6
44.0
29.7
35.7
41.4
44.9
PI
6.46
6.49
6.52
6.56
6.52
6.56
6.59
6.62
6.59
6.62
6.66
6.69
T C
31.4
37.3
43.3
47.0
32.0
38.1
44.2
48.0
32.7
38.9
45.1
49.0
SC
21.9
27.8
33.8
37.5
22.3
28.4
34.5
38.3
22.8
29.0
35.2
39.1
PI
6.49
6.52
6.55
6.59
6.55
6.59
6.62
6.65
6.62
6.65
6.69
6.72
T C
34.5
40.0
46.0
50.0
35.2
40.9
46.9
51.1
35.9
41.7
47.9
52.1
SC
15.1
20.6
26.6
30.6
15.4
21.1
27.1
31.3
15.7
21.5
27.7
31.9
PI
6.52
6.55
6.58
6.62
6.58
6.62
6.65
6.68
6.65
6.68
6.72
6.75
63
67
71
A
m
bi
ent
T
e
m
p
er
at
ur
e
63
67
71
63
67
71
Air Flow
(
CFM
)
1650
1750
1950
63
67
71
95
105
115
85
Outdoor Temp(
℉
) 70% RH
60
70
75
80
60
70
75
80
17
34.5
33.8
33.5
33.2
4.19
4.45
4.58
4.71
22
38.1
37.4
37.0
36.6
4.42
4.70
4.84
4.98
27
41.7
40.9
40.5
40.1
4.66
4.95
5.10
5.25
32
44.7
43.8
43.3
42.9
4.89
5.20
5.36
5.52
37
49.6
48.6
48.1
47.6
5.19
5.52
5.68
5.85
42
56.3
55.2
54.7
54.2
5.48
5.83
6.01
6.18
47
63.6
62.5
61.9
61.4
5.78
6.15
6.33
6.51
52
68.5
67.3
66.7
66.0
6.05
6.43
6.62
6.81
57
73.4
72.1
71.4
70.7
6.31
6.71
6.91
7.11
62
78.2
76.8
76.1
75.4
6.58
6.99
7.20
7.41
67
83.1
81.6
80.9
80.1
6.84
7.28
7.49
7.71
72
87.9
86.4
85.6
84.8
7.11
7.56
7.79
8.01
Net Capacities(kW)-1850 CFM
Peak Net Heating(kW) at Indicated Dry Bulb(
℉
)
Peak Total Power(KW) at Indicated Dry Bulb(
℉
)
Notes: 1. For other airflows, see heating capacity correction factor tables.
2. Heating capacities and power are integrated to include the effects of defrost in the frost region.
Notes:
1.All capacities are net and have considered indoor fan heat.
2.TC=Total
Capacity.
(Unit:1000Btu/h)
3.SC=SensibleCapacity.
(Unit:1000Btu/h)
4.different air volume in the above table, need to adjust in the field.