PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-
connecting line tubing.
2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.
4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evap adder for line set.
Additional R-22 Charge / TXV Size for Various Matched Systems
Outdoor Unit
YMA02411
YMA03011
YMA03611
YMA04211
YMA04811
YMA06011
Unit
Orifice
(s)
63 69 78 87 -
96
Approved System Thermal Expansion Valve
1,2
1TV0701 1TV0701 1TV0702 1TV0702 1TV0703
-
Factory R-22 Charge, lbs-oz
7 - 2
7 - 12
8 - 6
8 - 12
9 - 1
14 - 2
Indoor Coil
3
Coil Orifice
4
Orifice - Additional Charge, Oz
G2FD030(S,H)17
65
63/(701) + 2
69/(701) + 0
-
-
-
G2FD035(S,H)14
65
63/(701) + 2
69/(701) + 0
-
-
-
G2FD036(S,H)17
65
-
-
78/(702) + 3
-
-
-
G2FD036(S,H)21
75
-
-
78/(702) + 5
-
-
-
G2FD048(S,H)21,24
84
-
-
-
87/(702) + 3
-
-
G2FD060(S,H)24 90
-
-
-
-
703 + 6
96 + 6
G2FD061H24 90
-
-
-
-
703 + 12
96 + 12
G1HA036H14
75
63/(701) + 8
69/(701) + 6
78/(702) + 5
-
-
-
G1HA036H17
78
63/(701) +12 69/(701) + 9
78/(702) + 8
-
-
-
G1HA048H21
84
-
-
-
87/(702) + 4
-
-
G1HA060H24 90
-
-
-
-
703 + 6
96 + 6
G1HD036
69
63/(701) + 8
69/(701) + 5
78/(702) + 5
-
-
-
G1HD048
81
-
-
-
87/(702) + 0
-
-
G1HD060 93
-
-
-
-
703 + 0
96 + 0
G1NA036S17J
67
63/(701) + 4
69/(701) + 2
78/(702) + 1
-
-
-
G1NA036S21C
67
63/(701) + 4
69/(701) + 2
78/(702) + 1
-
-
-
G1NA060S24T
87
-
-
-
87/(702) + 8
703 + 1
96 + 0
G1FA/G1UA036S14
73
63/(701) + 4
69/(701) + 2
78/(702) + 1
-
-
-
G1FA/G1UA036S17,21
73
63/(701) + 2
69/(701) + 0
78/(702) + 0
-
-
-
G1FA/G1UA048S21
84
-
-
-
87/(702) + 5
-
-
G1FA/G1UA060S21,24 90
-
-
-
-
703 + 6
96 + 6
F2RC/F2FC036
75
63/(701) + 2
69/(701) + 0
-
-
-
-
F2RP024
61
63/(701) + 0
-
-
-
-
-
F2RP/F2FP030
65
63/(701) + 2
69/(701) + 0
-
-
-
-
F2RP/F2FP036
75
-
-
78/(702) + 5
-
-
-
F2FP040
63
-
-
78/(702) + 8
-
-
-
F2RP/F2FP042
78
-
-
78/(702) + 8
-
-
-
F2FP045 78
-
-
-
-
703 + 6
-
F2FP048
84
-
-
-
87/(702) + 7
-
-
F2FP060 90
-
-
-
-
703 + 6
96 + 6
F2FV060 90
-
-
-
-
703 + 6
96 + 6
Indoor Coil with factory
installed TXV
2,4
Factory installed
coil orifice
3
Additional Charge, Oz.
G2FD030(S,H)17T -
2
0
-
-
-
G2FD035(S,H)14T -
2
0
-
-
-
G2FD036(S,H)17T -
-
-
3
-
-
-
G2FD036(S,H)21T -
-
-
5
-
-
-
G2FD060(S,H)24T -
-
-
-
-
6
-
G1HA036H14T -
-
-
5
-
-
-
G1HA036H17T -
-
-
8
-
-
-
G1HA060H24T -
-
-
-
-
6
-
G1FA/G1UA036S14T -
-
-
1
-
-
-
G1FA/G1UA036S17,21T -
-
-
0 -
-
-
G1FA/G1UA060S21,24T -
-
-
-
-
6
-
F3RP024 -
0
-
-
-
-
-
F3RP030 -
2
0
-
-
-
-
F3RP036 -
-
-
5
-
-
-
F3RP042 -
-
-
8
-
-
-
F3FP040 -
-
-
8
-
-
-
F3FP060 -
-
-
-
-
6
-
F3FV060 -
-
-
-
-
6
-
FOOTNOTES:
1
Only the TXV kits listed above are approved for use in these systems. The charge adder is the same as that listed for the orifice.
2
Models with reciprocating compressors require start kits when matched to TXV indoor coils.
3
Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit
2FD06700224.
4
These orifices or TXVs are factory mounted in the flow device of each indoor coil (701, 702, 703 indicates 1TV07…series). A “T”
suffix indicates a coil or air handler with a factory mounted TXV.