036-21570-002 Rev. D (0605)

Unitary Products Group

3

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-

connecting line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for 

evap adder for line set.

Additional R-22 Charge / TXV Size for Various Matched Systems

Outdoor Unit 

YMA02411

YMA03011

YMA03611

YMA04211

YMA04811

YMA06011

Unit 

Orifice 

(s) 

63 69 78 87  -

96

Approved System Thermal Expansion Valve

1,2

1TV0701 1TV0701 1TV0702 1TV0702 1TV0703 

-

Factory R-22 Charge, lbs-oz

7 - 2

7 - 12

8 - 6

8 - 12

9 - 1

14 - 2

Indoor Coil

3

Coil Orifice 

4

Orifice - Additional Charge, Oz

G2FD030(S,H)17 

65 

63/(701) + 2 

69/(701) + 0 

-

-

-

G2FD035(S,H)14 

65 

63/(701) + 2 

69/(701) + 0 

-

-

-

G2FD036(S,H)17 

65 

-

-

78/(702) + 3 

-

-

-

G2FD036(S,H)21 

75 

-

-

78/(702) + 5 

-

-

-

G2FD048(S,H)21,24 

84 

-

-

-

87/(702) + 3 

-

-

G2FD060(S,H)24 90 

-

-

-

-

703 + 6 

96 + 6 

G2FD061H24 90 

-

-

-

-

703 + 12 

96 + 12 

G1HA036H14 

75 

63/(701) + 8 

69/(701) + 6 

78/(702) + 5 

-

-

-

G1HA036H17 

78 

63/(701) +12  69/(701) + 9 

78/(702) + 8 

-

-

-

G1HA048H21 

84 

-

-

-

87/(702) + 4 

-

-

G1HA060H24 90 

-

-

-

-

703 + 6 

96 + 6 

G1HD036 

69 

63/(701) + 8 

69/(701) + 5 

78/(702) + 5 

-

-

-

G1HD048 

81 

-

-

-

87/(702) + 0 

-

-

G1HD060 93 

-

-

-

-

703 + 0 

96 + 0 

G1NA036S17J 

67 

63/(701) + 4 

69/(701) + 2 

78/(702) + 1 

-

-

-

G1NA036S21C 

67 

63/(701) + 4 

69/(701) + 2 

78/(702) + 1 

-

-

-

G1NA060S24T 

87 

-

-

-

87/(702) + 8 

703 + 1 

96 + 0 

G1FA/G1UA036S14 

73 

63/(701) + 4 

69/(701) + 2 

78/(702) + 1 

-

-

-

G1FA/G1UA036S17,21 

73 

63/(701) + 2 

69/(701) + 0 

78/(702) + 0 

-

-

-

G1FA/G1UA048S21 

84 

-

-

-

87/(702) + 5 

-

-

G1FA/G1UA060S21,24 90 

-

-

-

-

703 + 6 

96 + 6 

F2RC/F2FC036 

75 

63/(701)  +  2 

69/(701)  +  0 

-

-

-

-

F2RP024 

61 

63/(701) + 0 

-

-

-

-

-

F2RP/F2FP030 

65 

63/(701) + 2 

69/(701) + 0 

-

-

-

-

F2RP/F2FP036 

75 

-

-

78/(702) + 5 

-

-

-

F2FP040 

63 

-

-

78/(702) + 8 

-

-

-

F2RP/F2FP042 

78 

-

-

78/(702) + 8 

-

-

-

F2FP045 78 

-

-

-

-

703 + 6 

-

F2FP048 

84 

-

-

-

87/(702) + 7 

-

-

F2FP060 90 

-

-

-

-

703 + 6 

96 + 6 

F2FV060 90 

-

-

-

-

703 + 6 

96 + 6 

Indoor Coil with factory
installed TXV

2,4

 

Factory installed 

coil orifice

Additional Charge, Oz.

G2FD030(S,H)17T -

-

-

-

G2FD035(S,H)14T -

-

-

-

G2FD036(S,H)17T -

-

-

-

-

-

G2FD036(S,H)21T -

-

-

-

-

-

G2FD060(S,H)24T -

-

-

-

-

-

G1HA036H14T -

-

-

-

-

-

G1HA036H17T -

-

-

-

-

-

G1HA060H24T -

-

-

-

-

-

G1FA/G1UA036S14T -

-

-

-

-

-

G1FA/G1UA036S17,21T -

-

-

0  -

-

-

G1FA/G1UA060S21,24T -

-

-

-

-

-

F3RP024 -

-

-

-

-

-

F3RP030 -

-

-

-

-

F3RP036 -

-

-

-

-

-

F3RP042 -

-

-

-

-

-

F3FP040 -

-

-

-

-

-

F3FP060 -

-

-

-

-

-

F3FV060 -

-

-

-

-

-

FOOTNOTES:

1

Only the TXV kits listed above are approved for use in these systems. The charge adder is the same as that listed for the orifice.

2

Models with reciprocating compressors require start kits when matched to TXV indoor coils.

3

Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit  
2FD06700224.

4

These orifices or TXVs are factory mounted in the flow device of each indoor coil (701, 702, 703 indicates 1TV07…series). A “T” 
suffix indicates a coil or air handler with a factory mounted TXV.

Summary of Contents for YMA024

Page 1: ...Durable Finish Automotive quality finish provides the ulti mate protection from harmful U V rays and rust creep ensur ing long lasting high quality appearance A powder paint topcoat is applied over a...

Page 2: ...Nominal CFM 2 300 3 500 3 500 3 850 3 500 3 300 Coil Face Area Sq Ft 14 86 17 15 20 58 20 58 20 58 20 58 Rows Deep 1 1 1 1 1 2 Fins Inch 22 22 22 22 22 22 Liquid Line Set OD Field Installed 3 8 3 8 3...

Page 3: ...D036 69 63 701 8 69 701 5 78 702 5 G1HD048 81 87 702 0 G1HD060 93 703 0 96 0 G1NA036S17J 67 63 701 4 69 701 2 78 702 1 G1NA036S21C 67 63 701 4 69 701 2 78 702 1 G1NA060S24T 87 87 702 8 703 1 96 0 G1FA...

Page 4: ...0 15 20 25 30 24 G2FD060 S H 24 T 1600 46 0 35 0 12 50 10 65 N1VSD20 8 10 15 20 25 30 24 G2FD061H24 1600 46 5 35 4 12 50 10 70 YMA06011 N1VSD20 8 10 15 20 25 30 24 G2FD060 S H 24 1780 53 5 40 6 12 00...

Page 5: ...8 27 0 12 00 12 00 10 95 17 21 G1FA036S17 21 T 1200 34 6 27 0 12 00 12 00 10 95 17 G2FD036 S H 17 T 1200 35 2 27 2 12 00 12 00 11 05 21 G2FD036 S H 21 T 1200 35 6 28 0 12 00 12 00 11 30 17 G1NA036S17...

Page 6: ...30 4 23 0 13 00 13 00 12 05 P1XDB12V G2FD030 S H 17 T 17 1000 30 2 23 2 13 00 13 00 11 75 P1XDB12V G1HA036H17 17 950 31 0 23 2 13 00 13 00 11 50 YMA03611 P DUA12V G1FA036S14 T 14 1185 35 0 27 0 12 25...

Page 7: ...0 YMA06011 P DUC20V G1FA060S21 21 1730 53 5 41 2 12 00 10 60 P DUC20V G2FD060 S H 24 24 1730 53 5 41 2 12 00 10 60 P DUC20V G2FD061H24 24 1730 54 0 41 9 12 00 10 70 P1XUC16V G1FA060S21 21 1600 53 5 40...

Page 8: ...2 2 48 39 7 2 94 N1VSC16 G2FD036 S H 21 T 34 8 3 76 2 71 20 6 2 72 2 22 8 50 11 2 1 90 15 9 2 06 22 9 2 32 25 1 2 42 39 6 2 88 YMA04211 N1VSC16 G2FD048 S H 21 T 41 0 3 64 3 30 27 2 2 60 3 07 8 50 17 9...

Page 9: ...17 T 35 2 3 54 2 91 21 0 2 54 2 42 8 00 11 5 2 10 16 3 2 26 23 2 2 52 25 4 2 62 39 9 3 08 G2FD036 S H 21 T 35 2 3 54 2 91 21 0 2 54 2 42 8 00 11 5 2 10 16 3 2 26 23 2 2 52 25 4 2 62 39 9 3 08 G1NA036S...

Page 10: ...ectronic programmable 7 day thermostat For the most current accessory information refer to the price book or consult factory SOUND POWER RATINGS Rated in accordance with ARI 270 95 Standards PERFORMAN...

Page 11: ...2 3 105 T C 17 5 18 3 18 4 20 7 24 2 19 3 20 0 19 4 21 7 25 1 21 1 21 6 20 3 22 6 26 1 S C 19 0 18 3 15 2 15 3 12 1 20 9 20 9 17 7 17 9 13 7 22 9 23 5 20 3 20 5 15 3 K W 2 2 2 2 2 2 2 3 2 4 2 3 2 3 2...

Page 12: ...7 2 6 2 6 2 6 2 7 2 8 2 7 2 7 2 7 2 7 2 8 105 T C 23 0 24 1 23 4 26 8 30 5 24 6 25 5 24 4 27 4 30 8 26 3 27 0 25 4 28 0 31 0 S C 23 0 22 7 19 1 19 5 15 9 24 6 24 9 21 5 22 0 17 3 26 3 27 1 23 9 24 5...

Page 13: ...17 6 29 4 29 8 24 9 26 0 18 8 31 0 31 8 27 2 28 4 19 9 K W 3 3 3 3 3 3 3 4 3 5 3 4 3 4 3 3 3 4 3 5 3 4 3 4 3 4 3 5 3 6 115 T C 25 6 26 2 24 0 28 8 30 4 27 2 27 4 24 7 29 5 30 7 28 8 28 6 25 4 30 3 30...

Page 14: ...41 3 41 8 35 0 35 0 25 2 K W 3 9 3 9 3 9 3 9 4 0 3 9 3 9 3 9 3 9 4 0 3 9 3 9 3 9 4 0 4 0 105 T C 33 7 35 1 34 3 38 5 40 3 35 8 36 5 35 0 39 1 40 8 37 9 37 8 35 7 39 7 41 4 S C 35 6 34 7 29 0 29 0 21...

Page 15: ...44 7 48 9 S C 38 4 38 2 32 6 32 6 25 6 39 8 39 9 34 9 34 8 26 8 41 1 41 6 37 1 37 0 27 9 K W 5 1 5 1 5 1 5 1 5 2 5 1 5 1 5 1 5 1 5 2 5 1 5 1 5 1 5 2 5 2 115 T C 36 2 37 4 37 0 40 8 44 6 37 6 38 5 37 9...

Page 16: ...5 0 50 1 51 7 50 3 51 2 45 8 51 3 52 1 S C 45 8 45 8 38 3 38 3 28 3 38 9 47 7 40 4 40 7 29 4 48 7 49 5 42 6 43 0 30 4 K W 5 7 5 7 5 7 5 8 5 9 5 7 5 7 5 7 5 8 5 9 5 8 5 8 5 7 5 8 5 9 115 T C 44 5 44 8...

Page 17: ...6 1 7 2 1 13 6 1 7 2 3 10 60 11 8 1 6 2 2 12 8 1 6 2 4 13 8 1 6 2 6 70 10 8 1 6 2 0 11 7 1 6 2 1 12 6 1 6 2 3 80 9 8 1 6 1 7 10 6 1 6 1 9 11 4 1 6 2 1 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1...

Page 18: ...5 80 14 9 2 2 2 0 15 7 2 2 2 1 16 5 2 2 2 2 10 60 16 4 2 1 2 3 16 7 2 1 2 4 17 1 2 0 2 4 70 14 5 2 1 2 0 14 9 2 1 2 1 15 3 2 1 2 2 80 12 7 2 1 1 8 13 1 2 1 1 8 13 6 2 1 1 9 NOTE ALL CAPACITIES INCLUDE...

Page 19: ...80 18 3 2 4 2 3 18 2 2 4 2 3 18 2 2 3 2 3 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP F2RP F2FP F3FP036 0 99 0 99 0 99 F2FP F3FP040 0 99 1 00 0 99 F2R...

Page 20: ...8 9 3 1 2 7 29 3 3 1 2 8 70 27 6 3 4 2 4 28 0 3 3 2 5 28 4 3 2 2 6 80 26 8 3 5 2 2 27 1 3 4 2 3 27 4 3 4 2 4 10 60 27 9 2 8 2 9 28 5 2 8 3 0 29 1 2 7 3 1 70 26 0 3 1 2 4 26 4 3 1 2 5 26 8 3 0 2 6 80 2...

Page 21: ...6 2 2 27 9 3 6 2 3 28 2 3 6 2 3 80 26 8 4 0 2 0 27 2 4 0 2 0 27 6 4 0 2 0 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP F2FP045 0 99 1 01 0 98 F2FP F3F...

Page 22: ...7 3 2 38 4 3 7 3 0 70 38 4 4 0 2 8 37 0 4 1 2 7 35 6 4 1 2 6 80 35 0 4 4 2 4 34 0 4 4 2 3 32 9 4 4 2 2 NOTE ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH 1000 CFM Air Handler Coil MBH KW COP F2...

Page 23: ...UPFLOW HORIZONTAL AND DOWNFLOW Available with factory installed horizontal drain pan ADD ON COILS FOR FURNACE APPLICATIONS G1FA FULL CASED UPFLOW G1HA FULL CASED HORIZONTAL AIR HANDLERS FOR NON FURNA...

Page 24: ...without notice Printed in U S A 036 21570 002 Rev D 0605 Copyright by York International Corp 2005 All rights reserved Supersedes 036 21570 002 Rev C 0405 Unitary 5005 Norman Products York OK Group D...

Reviews: