![York YMA024 Technical Manual Download Page 11](http://html2.mh-extra.com/html/york/yma024/yma024_technical-manual_4250020011.webp)
036-21570-002 Rev. D (0605)
Unitary Products Group
11
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YMA02411
INDOOR COIL MODEL NO.
G2FD030S17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
600
800
1000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
22.5 25.1 25.1 28.2 30.0 25.0 26.4 26.4 29.2 30.1 27.5 27.6 27.8 30.1 30.3
S.C.
24.5 21.7 18.2 18.3 14.5 27.1 25.5 20.8 19.9 14.8 29.6 29.3 23.3 21.5 15.1
K.W.
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
75
T.C.
21.3 23.4 23.5 26.4 28.8 23.6 24.9 24.7 27.4 29.3 26.0 26.3 25.9 28.4 29.8
S.C.
23.2 20.9 17.5 17.6 14.0 25.6 24.5 20.1 19.5 14.7 28.1 28.1 22.6 21.5 15.4
K.W.
1.8 1.8 1.8 1.9 1.9 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
85
T.C.
20.1 21.7 22.0 24.7 27.7 22.3 23.3 23.0 25.7 28.5 24.5 25.0 24.1 26.8 29.3
S.C.
21.8 20.1 16.8 16.8 13.5 24.2 23.5 19.4 19.2 14.6 26.5 27.0 22.0 21.5 15.7
K.W.
1.9 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.1
95
T.C.
18.9 20.0 20.4 22.9 26.5 20.9 21.8 21.3 24.0 27.7 23.0 23.7 22.2 25.1 28.9
S.C.
20.5 19.3 16.1 16.1 13.0 22.7 22.5 18.7 18.8 14.5 24.9 25.8 21.4 21.5 16.1
K.W.
2.1 2.1 2.1 2.2 2.2 2.1 2.1 2.1 2.2 2.3 2.2 2.2 2.2 2.2 2.3
105
T.C.
17.5 18.3 18.4 20.7 24.2 19.3 20.0 19.4 21.7 25.1 21.1 21.6 20.3 22.6 26.1
S.C.
19.0 18.3 15.2 15.3 12.1 20.9 20.9 17.7 17.9 13.7 22.9 23.5 20.3 20.5 15.3
K.W.
2.2 2.2 2.2 2.3 2.4 2.3 2.3 2.2 2.3 2.4 2.4 2.3 2.3 2.4 2.4
115
T.C.
16.1 16.7 16.5 18.6 21.8 17.6 18.1 17.5 19.4 22.6 19.2 19.6 18.5 20.3 23.4
S.C.
17.4 17.3 14.3 14.5 11.2 19.1 19.3 16.7 17.0 12.8 20.9 21.2 19.2 19.5 14.4
K.W.
2.4 2.4 2.3 2.4 2.5 2.4 2.4 2.4 2.5 2.6 2.5 2.5 2.4 2.5 2.6
125
T.C.
14.7 15.0 14.5 16.5 19.5 16.0 16.3 15.6 17.2 20.1 17.4 17.6 16.7 17.9 20.7
S.C.
15.9 16.4 13.4 13.7 10.4 17.3 17.6 15.8 16.1 12.0 18.9 18.9 18.2 18.5 13.6
K.W.
2.5 2.5 2.5 2.6 2.7 2.6 2.6 2.5 2.6 2.7 2.7 2.6 2.5 2.6 2.8
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C. S.C. KW
F2RC/F2FC036
1.00 1.00 1.00
F2RP/F2FP/F3FP024
0.98 0.99 0.98
F2RP/F2FP/F3FP030
1.00 1.00 1.00
N1VSB12
G2FD030(S,H)17(T) 1.01 0.98 0.92
N1AHB08
G2FD030(S,H)17(T) 1.00 1.00 1.00
N1AHB12
G2FD030(S,H)17(T) 1.00 1.00 1.00
G1FA036S14
1.01 1.02 1.00
G1FA036S17,21
1.00 1.00 1.00
G2FD030(S,H)17(T) 1.00 1.00 1.00
G2FD035(S,H)14(T) 1.00 1.00 1.00
G1NA036S17J
1.01 1.00 1.00
G1NA036S21C
1.01 1.00 1.00
G1HD036
1.02 1.03 1.00
G1HA036H14
1.03 1.00 1.00
G1HA036H17
1.03 1.01 0.99
Variable Speed
Furnace
Coil
T.C. S.C. KW
P*DUA12V
G1FA036S14
1.02 0.98 0.93
P*DUA12V
G2FD035(S,H)14(T) 1.01 0.98 0.92
P*DUB16V
G1FA036S17
1.02 1.01 0.93
P*DUB16V
G2FD030(S,H)17(T) 1.02 1.01 0.93
P*DUC20V
G1FA036S21
1.02 1.01 0.93
P1XUB12V
G1FA036S17
1.02 1.01 0.93
P1XUB12V
G2FD030(S,H)17(T) 1.02 1.01 0.93
P1XUC16V
G1FA036S21
1.01 0.99 0.92
P1XUC20V
G1FA036S21
1.02 1.01 0.92
P1XDB12V
G2FD030(S,H)17(T) 1.02 1.02 0.93
P1XDB12V
G1HA036H17
1.03 1.01 0.93