1.2.8 Parameters relating to defrost
Parameters relating to defrost
Parameters
Description
Level
VS
Unit
Max.
Min.
Value
d01
Defrost operation:
0= Absent (function not available)
1= Present
U
7 (R/W)
-
1
0
1
d02
Defrost at time or temperature:
0= Time (function not available)
1= Temperature / Pressure
U
8 (R/W)
-
1
0
1
d03
Defrost start pressure
U
19 (R/W)
bar
d04
/11
5,8
d04
Defrost end pressure
U
21 (R/W)
bar
/12
d03
18
d05
Minimum defrost start time
U
37 (R/W)
Seconds
150
10
10
d06
Minimum defrost duration
U
38 (R/W)
Seconds
150
0
0
d07
Maximum defrost duration
U
39 (R/W)
Minutes
15
1
6
d08
Time between two defrost cycles
U
40 (R/W)
Minutes
150
10
30
d11
Activation of heaters during defrost:
0= No
1= Yes
U
9 (R/W)
-
0
1
1
d12
Compressor stoppage before defrost
F
43 (R/W)
Minutes
3
0
1
d13
Compressor stoppage after defrost
F
44 (R/W)
Minutes
3
0
1
d16
Forced ventilation time at defrost end (if
F13=2 only)
F
47 (R/W)
Minutes
360
0
60
A
Defrost end tempera‐
ture (d04)
E
Minimum defrost start time
(d05)
B
Defrost start
F
Timer start
C
Defrost end
G Defrost start temperature
(d03)
D
Maximum defrost du‐
ration (d06)
1
User manual
1.2
Operating instructions µC2 (YLHA 50, 60 and 80)