SECTION 5 – TECHNICAL DATA
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
55
SYSTEM # 1
SYSTEM # 2
COMPR 1
COMPR 2
COMPR 3 STD FLOW FANS COMPR 1
COMPR 2
COMPR 3 STD FLOW FANS
RLA LRA RLA LRA RLA LRA QTY FLA LRA RLA LRA RLA LRA RLA LRA QTY FLA LRA
106.2 523 106.2 523
4
7.6
44 106.2 523 106.2 523
4
7.6
44
106.2 578 106.2 578
4
7.4
37 106.2 578 106.2 578
4
7.4
37
64.3 355 64.3 355
4
4.5
23.1 64.3 355 64.3 355
4
4.5
23.1
53.1 290 53.1 290
4
4
19
53.1 290 53.1 290
4
4
19
42.5 255 42.5 255
4
2.9
15.3 42.5 255 42.5 255
4
2.9
15.3
106.2 523 106.2 523 106.2 523
5
7.6
44 106.2 523 106.2 523 106.2 523
5
7.6
44
106.2 578 106.2 578 106.2 578
5
7.4
37 106.2 578 106.2 578 106.2 578
5
7.4
37
64.3 355 64.3 355 64.3 355
5
4.5
23.1 64.3 355 64.3 355 64.3 355
5
4.5
23.1
53.1 290 53.1 290 53.1 290
5
4
19
53.1 290 53.1 290 53.1 290
5
4
19
42.5 255 42.5 255 42.5 255
5
2.9
15.3 42.5 255 42.5 255 42.5 255
5
2.9
15.3
106.2 523 106.2 523 106.2 523
5
7.6
44 106.2 523 106.2 523 106.2 523
5
7.6
44
106.2 578 106.2 578 106.2 578
5
7.4
37 106.2 578 106.2 578 106.2 578
5
7.4
37
64.3 355 64.3 355 64.3 355
5
4.5
23.1 64.3 355 64.3 355 64.3 355
5
4.5
23.1
53.1 290 53.1 290 53.1 290
5
4
19
53.1 290 53.1 290 53.1 290
5
4
19
42.5 255 42.5 255 42.5 255
5
2.9
15.3 42.5 255 42.5 255 42.5 255
5
2.9
15.3
102.8 574 102.8 574 102.8 574
6
7.6
44 102.8 574 102.8 574 102.8 574
6
7.6
44
102.8 635 102.8 635 102.8 635
6
7.4
37 102.8 635 102.8 635 102.8 635
6
7.4
37
62.2 355 62.2 355 62.2 355
6
4.5
23.1 62.2 355 62.2 355 62.2 355
6
4.5
23.1
51.4 280 51.4 280 51.4 280
6
4
19
51.4 280 51.4 280 51.4 280
6
4
19
41.1 225 41.1 225 41.1 225
6
2.9
15.3 41.1 225 41.1 225 41.1 225
6
2.9
15.3
138.8 943 138.8 943 138.8 943
6
7.6
44 138.8 943 138.8 943 138.8 943
6
7.6
44
138.8 943 138.8 943 138.8 943
6
7.4
37 138.8 943 138.8 943 138.8 943
6
7.4
37
87.2 564 87.2 564 87.2 564
6
4.5
23.1 87.2 564 87.2 564 87.2 564
6
4.5
23.1
73
408
73
408
73
408
6
4
19
73
408
73
408
73
408
6
4
19
51.9 375 51.9 375 51.9 375
6
2.9
15.3 51.9 375 51.9 375 51.9 375
6
2.9
15.3
NOTE:
• Reference PIN 59 for Pump Model.
• Use this table along with
Table 9 - Pump Electrical Data 60 Hz on page 55
to determine electrical data of the unit plus the pump.
• Does not include Control Transformer.
TABLE 11 -
ELECTRICAL DATA WITHOUT PUMPS (CONT’D)