Isolator Details (Cont'd)
EQUIPMENT
BASE
(BY OTHERS)
POSITIONING
PIN
LD18443
ONE INCH DEFLECTION SPRING ISOLATOR (CPX-X-)
MOUNT
DIMENSION DATA INCHES (MM)
W
D
L
B
C
T
H
CP1
3 (76)
0.625 (16) 7.75 (197) 6.5 (165) 4.75 (121)
0.5 (13) 4.625 (117)
CP2
3 (76)
0.625 (16) 10.5 (267) 9.25 (235) 7.75 (197) 0.5625 (14) 6 (152)
MOUNT
RATED CAPACITY
LBS (KG)
DEFLECTION
RATED IN (MM)
COLOR CODE
CP1-1D-85
85 (39)
1020 (463)
LT. PURPLE
CP1-1D-120
120 (54)
1.2 (30)
DK. YELLOW
CP1-1D-175
175 (79)
1.17 (30)
DK. BLUE
CP1-1D-250
250 (113)
1.4 (36)
YELLOW
CP1-1D-340
340 (154)
1.13 (29)
RED
CP1-1D-510
510 (231)
1.02 (26)
BLACK
CP1-1D-675
675 (306)
1.32 (34)
DK. PURPLE
CP1-1D-900
900 (408)
1.02 (26)
DK. GREEN
CP1-1D-1200
1200 (544)
0.9 (23)
GRAY
CP1-1D-1360
1360 (617)
0.77 (20)
WHITE
CP1-1D-1785N
1785 (810)
0.88 (22)
GRAY/RED
MOUNT
RATED CAPACITY
LBS (KG)
DEFLECTION
RATED IN (MM)
COLOR CODE
CP2-1D-1020
1020 (463)
1.020 (46)
BLACK
CP2-1D-1350
1350 (612)
1.32 (34)
DK. PURPLE
CP2-1D-1800
1800 (816)
1.02 (26)
DK. GREEN
CP2-1D-2400
2400 (1089)
0.9 (23)
GRAY
CP2-1D-2720
2720 (1234)
0.77 (20)
WHITE
CP2-1D-3570N
3570 (1619)
0.88 (22)
GRAY/RED
Summary of Contents for YLAA
Page 4: ...JOHNSON CONTROLS FORM 150 72 EG6 516 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 35 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 48: ...JOHNSON CONTROLS FORM 150 72 EG6 516 48 Wiring Diagram ...
Page 49: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 49 LD18444 Wiring Diagram Cont d ...