JOHNSON CONTROLS
FORM 150.72-EG6 (516)
20
NOMINAL EVAPORATOR WATER FLOW
YLAA
TEMPERATURE (°F)
WATER FLOW (GPM) AIR ON CONDENSER (°F)
MIN
1
MAX
2
MIN
MAX
MIN
3
MAX
4
STANDARD EFFICIENCY
0070SE
40
55
60
285
0
125
0080SE
40
55
100
355
0
125
0089SE
40
55
100
385
0
125
0100SE
40
55
100
385
0
125
0120SE
40
55
150
625
0
125
0136SE
40
55
150
625
0
125
0155SE
40
55
150
625
0
125
0170SE
40
55
150
625
0
125
HIGH EFFICIENCY
0058HE
40
55
60
285
0
125
0065HE
40
55
60
285
0
125
0081HE
40
55
150
625
0
125
0092HE
40
55
100
385
0
125
0101HE
40
55
100
385
0
125
0125HE
40
55
100
385
0
125
0142HE
40
55
150
625
0
125
0156HE
40
55
150
625
0
125
0175HE
40
55
150
625
0
125
Design Parameters
NOTES:
1. For leaving liquid temperature below 40°F (4°C) (to 10°F [-12°C]) optional low temperature glycol kit re-
quired. Contact your nearest Johnson Controls Office for application requirements.
2.
For leaving liquid temperature higher than 55°F (13°C), contact the nearest Johnson Controls Office for
application guidelines.
3. The evaporator is protected against freezing to -20°F (-29°C) with an electric heater as standard.
4. For operation at temperatures above 115°F (46°C), the optional High Ambient Kit will need to be installed
on the system.
Summary of Contents for YLAA
Page 4: ...JOHNSON CONTROLS FORM 150 72 EG6 516 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 35 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 48: ...JOHNSON CONTROLS FORM 150 72 EG6 516 48 Wiring Diagram ...
Page 49: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 49 LD18444 Wiring Diagram Cont d ...